type,address,name,data_type,control_address,pics_address,pics_data_type,notes
Discrete_Input,10008,Sts_PumpAlarm,bool,18,,,
Coil,18,Sts_PumpAlarm_ctrl,bool,,430001,Integer,
Discrete_Input,10016,Supply_Valve_Timer_Alarm,bool,16,,,
Coil,16,Supply_Valve_Timer_Alarm_ctrl,bool,,430005,Integer,
Discrete_Input,10041,Sts_HumidiStat,bool,41,,,
Coil,41,Sts_HumidiStat_ctrl,bool,,430009,Integer,
Input_Register,30044,Operation_Mode,uint32,43044,,,
Holding_Register,43044,Operation_Mode_ctrl,uint32,,430013,Float,Act Op Mode - Config*Off*Dry Pad*Switch Off*
Input_Register,30057,Space_Temp,uint32,43057,,,
Holding_Register,43057,Space_Temp_ctrl,uint32,,430017,Float,
Input_Register,30060,Space_Dewpoint,uint32,43060,,,
Holding_Register,43060,Space_Dewpoint_ctrl,uint32,,430021,Float,
Holding_Register,40008,Operation_Mode_Switch,uint32,,430025,Float,Op Mode Switch - Auto*Off*On
Holding_Register,406005,Relative_Humidity,uint32,,430029,Float,Relative Humidity Sensor Value
Holding_Register,406030,Relative_Humidity_SP,uint32,,430033,Float,Humidity Setpoint
Holding_Register,410001,Flow_Alarm,uint16,,430037,Integer,Optional Flow Indicator Alarm - Normal * Alarm
Holding_Register,410005,Sts_Leak,uint16,,430041,Integer,Water Leak Detection
Holding_Register,411012,Fan_Status,uint16,,430045,Integer,SDU Fan - Off * On
Holding_Register,412005,Fan_Alarm,uint16,,430049,Integer,SDU Fan Fault - Normal * Alarm
Holding_Register,415015,System_Status,uint16,,430053,Integer,
Holding_Register,415021,Boiler_Alarm,uint16,,430057,Integer,0 = Normal 1 = FailedPump 2 =
Holding_Register,415025,Sts_Oper,uint16,,430061,Integer,"0=Off, 1=On"
Coil,1,OCmd_ResetAckAll,bool,,430065,Integer,Acknowledge All Alarms/Reset
Coil,10,OCmd_Stop,bool,,430069,Integer,Remote Stop (Modbus)
Coil,12,OCmd_Start,bool,,430073,Integer,Remote Start (Modbus)
1 type address name data_type control_address pics_address pics_data_type notes
2 Discrete_Input 10008 Sts_PumpAlarm bool 18
3 Coil 18 Sts_PumpAlarm_ctrl bool 430001 Integer
4 Discrete_Input 10016 Supply_Valve_Timer_Alarm bool 16
5 Coil 16 Supply_Valve_Timer_Alarm_ctrl bool 430005 Integer
6 Discrete_Input 10041 Sts_HumidiStat bool 41
7 Coil 41 Sts_HumidiStat_ctrl bool 430009 Integer
8 Input_Register 30044 Operation_Mode uint32 43044
9 Holding_Register 43044 Operation_Mode_ctrl uint32 430013 Float Act Op Mode - Config*Off*Dry Pad*Switch Off*
10 Input_Register 30057 Space_Temp uint32 43057
11 Holding_Register 43057 Space_Temp_ctrl uint32 430017 Float
12 Input_Register 30060 Space_Dewpoint uint32 43060
13 Holding_Register 43060 Space_Dewpoint_ctrl uint32 430021 Float
14 Holding_Register 40008 Operation_Mode_Switch uint32 430025 Float Op Mode Switch - Auto*Off*On
15 Holding_Register 406005 Relative_Humidity uint32 430029 Float Relative Humidity Sensor Value
16 Holding_Register 406030 Relative_Humidity_SP uint32 430033 Float Humidity Setpoint
17 Holding_Register 410001 Flow_Alarm uint16 430037 Integer Optional Flow Indicator Alarm - Normal * Alarm
18 Holding_Register 410005 Sts_Leak uint16 430041 Integer Water Leak Detection
19 Holding_Register 411012 Fan_Status uint16 430045 Integer SDU Fan - Off * On
20 Holding_Register 412005 Fan_Alarm uint16 430049 Integer SDU Fan Fault - Normal * Alarm
21 Holding_Register 415015 System_Status uint16 430053 Integer
22 Holding_Register 415021 Boiler_Alarm uint16 430057 Integer 0 = Normal 1 = FailedPump 2 =
23 Holding_Register 415025 Sts_Oper uint16 430061 Integer 0=Off, 1=On
24 Coil 1 OCmd_ResetAckAll bool 430065 Integer Acknowledge All Alarms/Reset
25 Coil 10 OCmd_Stop bool 430069 Integer Remote Stop (Modbus)
26 Coil 12 OCmd_Start bool 430073 Integer Remote Start (Modbus)