type,address,name,data_type,control_address,pics_address,pics_data_type,notes,,,,,,,,,,,,,,,, Discrete_Input,100051,Water_Detected_Alarm,bool,51,,,Unit flooding detector alarm,,,,,,,,,,,,,,51 bools,, Coil,51,_Water_Detected_Alarm,bool,,,,Unit flooding detector alarm,,,,,,,,,,,,,,57 uints,,57 Discrete_Input,100118,High_Temperature_Supply_Air,bool,118,,,High supply air temperature alarm,,,,,,,,,,,,,,,,36 Coil,118,_High_Temperature_Supply_Air,bool,,,,High supply air temperature alarm,,,,,,,,,,,,,,,,21 Discrete_Input,100122,Low_Temperature_Supply_Air,bool,122,,,Low supply air temperature alarm,,,,,,,,,,,,,,,, Coil,122,_Low_Temperature_Supply_Air,bool,,,,Low supply air temperature alarm,,,,,,,,,,,,,,,, Discrete_Input,100131,Fan_Alarm1,bool,131,,,Fan Alarm 1,,,,,,,,,,,,,,,, Coil,131,_Fan_Alarm1,bool,,,,Fan Alarm 1,,,,,,,,,,,,,,,, Discrete_Input,100132,Fan_Alarm2,bool,132,,,Fan Alarm 2,,,,,,,,,,,,,,,, Coil,132,_Fan_Alarm2,bool,,,,Fan Alarm 2,,,,,,,,,,,,,,,, Discrete_Input,100133,Fan_Alarm3,bool,133,,,Fan Alarm 3,,,,,,,,,,,,,,,, Coil,133,_Fan_Alarm3,bool,,,,Fan Alarm 3,,,,,,,,,,,,,,,, Discrete_Input,100134,Fan_Alarm4,bool,134,,,Fan Alarm 4,,,,,,,,,,,,,,,, Coil,134,_Fan_Alarm4,bool,,,,Fan Alarm 4,,,,,,,,,,,,,,,, Discrete_Input,100135,Fan_Alarm5,bool,135,,,Fan Alarm 5,,,,,,,,,,,,,,,, Coil,135,_Fan_Alarm5,bool,,,,Fan Alarm 5,,,,,,,,,,,,,,,, Discrete_Input,100136,Fan_Alarm6,bool,136,,,Fan Alarm 6,,,,,,,,,,,,,,,, Coil,136,_Fan_Alarm6,bool,,,,Fan Alarm 6,,,,,,,,,,,,,,,, Discrete_Input,100146,Supply_Sensor_Failure_Alarm,bool,146,,,Supply air temperature sensor fault,,,,,,,,,,,,,,,, Coil,146,_Supply_Sensor_Failure_Alarm,bool,,,,Supply air temperature sensor fault,,,,,,,,,,,,,,,, Discrete_Input,101096,Filter_Alarm,bool,1096,,,Dirty filter alarm,,,,,,,,,,,,,,,, Coil,1096,_Filter_Alarm,bool,,,,Dirty filter alarm,,,,,,,,,,,,,,,, Discrete_Input,101099,Low_Temperature_Return_Air,bool,1099,,,Low return air temperature alarm,,,,,,,,,,,,,,,, Coil,1099,_Low_Temperature_Return_Air,bool,,,,Low return air temperature alarm,,,,,,,,,,,,,,,, Discrete_Input,101245,Return_Sensor_Failure_Alarm,bool,1245,,,Return air temperature sensor fault,,,,,,,,,,,,,,,, Coil,1245,_Return_Sensor_Failure_Alarm,bool,,,,Return air temperature sensor fault,,,,,,,,,,,,,,,, Discrete_Input,101246,Humidity_Sensor_Failure_Alarm,bool,1246,,,Return air humidity sensor fault,,,,,,,,,,,,,,,, Coil,1246,_Humidity_Sensor_Failure_Alarm,bool,,,,Return air humidity sensor fault,,,,,,,,,,,,,,,, Discrete_Input,101250,Filter_Diff_Press_Sensor_Failure,bool,1250,,,Filter differential pressure sensor fault,,,,,,,,,,,,,,,, Coil,1250,_Filter_Diff_Press_Sensor_Failure,bool,,,,Filter differential pressure sensor fault,,,,,,,,,,,,,,,, Discrete_Input,101307,High_Humidity_Return_Air,bool,1307,,,High return air humidity alarm,,,,,,,,,,,,,,,, Coil,1307,_High_Humidity_Return_Air,bool,,,,High return air humidity alarm,,,,,,,,,,,,,,,, Discrete_Input,101308,Low_Humidity_Return_Air,bool,1308,,,Low return air humidity alarm,,,,,,,,,,,,,,,, Coil,1308,_Low_Humidity_Return_Air,bool,,,,Low return air humidity alarm,,,,,,,,,,,,,,,, Discrete_Input,101342,Common_Alarm,bool,1342,,,Common alarm status,,,,,,,,,,,,,,,, Coil,1342,_Common_Alarm,bool,,,,Common alarm status,,,,,,,,,,,,,,,, Discrete_Input,101360,Fan_Alarm7,bool,1360,,,Fan Alarm 7,,,,,,,,,,,,,,,, Coil,1360,_Fan_Alarm7,bool,,,,Fan Alarm 7,,,,,,,,,,,,,,,, Discrete_Input,101361,Fan_Alarm8,bool,1361,,,Fan Alarm 8,,,,,,,,,,,,,,,, Coil,1361,_Fan_Alarm8,bool,,,,Fan Alarm 8,,,,,,,,,,,,,,,, Discrete_Input,101362,Fan_Alarm9,bool,1362,,,Fan Alarm 9,,,,,,,,,,,,,,,, Coil,1362,_Fan_Alarm9,bool,,,,Fan Alarm 9,,,,,,,,,,,,,,,, Discrete_Input,101367,High_Temperature_Return_Air,bool,1367,,,High return air temperature alarm,,,,,,,,,,,,,,,, Coil,1367,_High_Temperature_Return_Air,bool,,,,High return air temperature alarm,,,,,,,,,,,,,,,, Discrete_Input,101368,Smoke_Detected,bool,1368,,,Smoke alarm status,,,,,,,,,,,,,,,, Coil,1368,_Smoke_Detected,bool,,,,Smoke alarm status,,,,,,,,,,,,,,,, Discrete_Input,101369,Fire_SD_Alarm,bool,1369,,,Fire alarm status,,,,,,,,,,,,,,,, Coil,1369,_Fire_SD_Alarm,bool,,,,Fire alarm status,,,,,,,,,,,,,,,, Discrete_Input,101370,Cond_Pump_Fail,bool,1370,,,Condensate pump alarm status,,,,,,,,,,,,,,,, Coil,1370,_Cond_Pump_Fail,bool,,,,Condensate pump alarm status,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Input_Register,300053,Fan1_Speed,uint16,430053,,,Speed-EC FAN#1,,,,,,,,,,,,,,,, Holding_Register,430053,_Fan1_Speed,uint16,,410001,Integer,Speed-EC FAN#1,,,,,,,,,,,,,,,, Input_Register,300070,Return_Humidity,uint32,430070,,,Return air humidity reading,,,,,,,,,,,,,,,, Holding_Register,430070,_Return_Humidity,uint32,,410005,Float,Return air humidity reading,,,,,,,,,,,,,,,, Input_Register,300099,Air_Supply_Temp,uint32,430099,,,Supply air temperature reading,,,,,,,,,,,,,,,, Holding_Register,430099,_Air_Supply_Temp,uint32,,410009,Float,Supply air temperature reading,,,,,,,,,,,,,,,, Input_Register,300101,Air_Return_Temp,uint32,430101,,,Return air temperature,,,,,,,,,,,,,,,, Holding_Register,430101,_Air_Return_Temp,uint32,,410013,Float,Return air temperature,,,,,,,,,,,,,,,, Input_Register,300106,Supply_Filter_Diff_Press,uint32,430106,,,,,,,,,,,,,,,,,,, Holding_Register,430106,_Supply_Filter_Diff_Press,uint32,,410017,Float,,,,,,,,,,,,,,,,, Input_Register,300228,Fan2_Speed,uint16,430228,,,Speed-EC FAN#2,,,,,,,,,,,,,,,, Holding_Register,430228,_Fan2_Speed,uint16,,410021,Integer,Speed-EC FAN#2,,,,,,,,,,,,,,,, Input_Register,300229,Fan3_Speed,uint16,430229,,,Speed-EC FAN#3,,,,,,,,,,,,,,,, Holding_Register,430229,_Fan3_Speed,uint16,,410025,Integer,Speed-EC FAN#3,,,,,,,,,,,,,,,, Input_Register,300230,Fan4_Speed,uint16,430243,,,Speed-EC FAN#4,,,,,,,,,,,,,,,, Holding_Register,430243,_Fan4_Speed,uint16,,410029,Integer,Speed-EC FAN#4,,,,,,,,,,,,,,,, Input_Register,300231,Fan5_Speed,uint16,430231,,,Speed-EC FAN#5,,,,,,,,,,,,,,,, Holding_Register,430231,_Fan5_Speed,uint16,,410033,Integer,Speed-EC FAN#5,,,,,,,,,,,,,,,, Input_Register,300232,Fan6_Speed,uint16,430232,,,Speed-EC FAN#6,,,,,,,,,,,,,,,, Holding_Register,430232,_Fan6_Speed,uint16,,410037,Integer,Speed-EC FAN#6,,,,,,,,,,,,,,,, Input_Register,300233,Fan2_Hrs,uint16,430233,,,Operating hours-EC FAN#2,,,,,,,,,,,,,,,, Holding_Register,430233,_Fan2_Hrs,uint16,,410041,Integer,Operating hours-EC FAN#2,,,,,,,,,,,,,,,, Input_Register,300235,Fan4_Hrs,uint16,430235,,,Operating hours-EC FAN#4,,,,,,,,,,,,,,,, Holding_Register,430235,_Fan4_Hrs,uint16,,410045,Integer,Operating hours-EC FAN#4,,,,,,,,,,,,,,,, Input_Register,300236,Fan5_Hrs,uint16,430236,,,Operating hours-EC FAN#5,,,,,,,,,,,,,,,, Holding_Register,430236,_Fan5_Hrs,uint16,,410049,Integer,Operating hours-EC FAN#5,,,,,,,,,,,,,,,, Input_Register,300244,Fan3_Hrs,uint16,430244,,,Operating hours-EC FAN#3,,,,,,,,,,,,,,,, Holding_Register,430244,_Fan3_Hrs,uint16,,410053,Integer,Operating hours-EC FAN#3,,,,,,,,,,,,,,,, Input_Register,300245,Fan6_Hrs,uint16,430245,,,Operating hours-EC FAN#6,,,,,,,,,,,,,,,, Holding_Register,430245,_Fan6_Hrs,uint16,,410057,Integer,Operating hours-EC FAN#6,,,,,,,,,,,,,,,, Input_Register,300274,Fan1_Hrs,uint16,430274,,,Operating hours-EC FAN#1,,,,,,,,,,,,,,,, Holding_Register,430274,_Fan1_Hrs,uint16,,410061,Integer,Operating hours-EC FAN#1,,,,,,,,,,,,,,,, Input_Register,300486,Fan7_Hrs,uint16,430486,,,Operating hours-EC FAN#7,,,,,,,,,,,,,,,, Holding_Register,430486,_Fan7_Hrs,uint16,,410065,Integer,Operating hours-EC FAN#7,,,,,,,,,,,,,,,, Input_Register,300487,Fan8_Hrs,uint16,430487,,,Operating hours-EC FAN#8,,,,,,,,,,,,,,,, Holding_Register,430487,_Fan8_Hrs,uint16,,410069,Integer,Operating hours-EC FAN#8,,,,,,,,,,,,,,,, Input_Register,300488,Fan9_Hrs,uint16,430488,,,Operating hours-EC FAN#9,,,,,,,,,,,,,,,, Holding_Register,430488,_Fan9_Hrs,uint16,,410073,Integer,Operating hours-EC FAN#9,,,,,,,,,,,,,,,, Input_Register,300496,Cooling_Valve_Output,uint32,430496,,,Chilled water valve feedback signal,,,,,,,,,,,,,,,, Holding_Register,430496,_Cooling_Valve_Output,uint32,,410077,Float,Chilled water valve feedback signal,,,,,,,,,,,,,,,, Input_Register,300678,Fan7_Speed,uint16,430678,,,Speed-EC FAN#7,,,,,,,,,,,,,,,, Holding_Register,430678,_Fan7_Speed,uint16,,410081,Integer,Speed-EC FAN#7,,,,,,,,,,,,,,,, Input_Register,300679,Fan8_Speed,uint16,430679,,,Speed-EC FAN#8,,,,,,,,,,,,,,,, Holding_Register,430679,_Fan8_Speed,uint16,,410085,Integer,Speed-EC FAN#8,,,,,,,,,,,,,,,, Input_Register,300680,Fan9_Speed,uint16,430680,,,Speed-EC FAN#9,,,,,,,,,,,,,,,, Holding_Register,430680,_Fan9_Speed,uint16,,410089,Integer,Speed-EC FAN#9,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400005,Fan_Speed_Max_SP,uint32,,410097,Float,Setting the EC fan maximum speed,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400029,Fan_Speed,uint32,,410101,Float,Fan Speed Feedback,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400111,Air_Return_Temp_Alm_Hi_SP,uint32,,410105,Float,High return air temperature alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400114,Air_Return_Temp_Alm_Lo_SP,uint32,,410109,Float,Low return air temperature alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400118,Air_Supply_Temp_Alm_Hi_SP,uint32,,410113,Float,High supply air temperature alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400122,Air_Supply_Temp_Alm_Lo_SP,uint32,,410117,Float,Low supply air temperature alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400681,Air_Return_Temp_SP,uint32,,410121,Float,Return air temperature setpoint,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400685,Return_Humidity_Alm_Hi_SP,uint32,,410125,Float,High return air humidity alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400689,Return_Humidity_Alm_Lo_SP,uint32,,410129,Float,Low return air humidity alarm limit,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400693,Space_Temp_SP,uint32,,410133,Float,Setting the room temperature,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Holding_Register,400695,Fan_Speed_Min_SP,uint32,,410137,Float,Setting the EC fan minimum speed,,,,,,,,,,,,,,,, ,,,,,,,,,,,,,,,,,,,,,,, Coil,301,BMS_StartStop,bool,,,,,,,,,,,,,,,,,,,,