type,address,name,data_type,control_address,pics_address,pics_data_type,notes
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000071,Ground_Overcurrent_Flt,bool,,,,Coil to trigger Groud Overcurrent
|
|
|
|
|
Discrete_Input,100071,Ground_Overcurrent,bool,000071,,,Alarm for Ground Overcurrent
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000070,Neutral_Overcurrent_Flt,bool,,,,Coil to trigger Neutral Overcurrent
|
|
|
|
|
Discrete_Input,100070,Neutral_Overcurrent,bool,000070,,,Alarm for Neutral Overcurrent
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000066,Panel_Overvoltage_Flt,bool,,,,Coil to trigger Panel Overvoltage
|
|
|
|
|
Discrete_Input,100066,Panel_Overvoltage,bool,000066,,,Alarm for Panel Overvoltage
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000068,Phase_Overcurrent_Flt,bool,,,,Coil to trigger Phase Overcurrent
|
|
|
|
|
Discrete_Input,100068,Phase_Overcurrent,bool,000068,,,Alarm for Phase Overcurrent
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000069,Phase_Overcurrent_Wrn_Flt,bool,,,,Coil to trigger Phase Overcurrent Warning
|
|
|
|
|
Discrete_Input,100069,Phase_overcurrent_Wrn,bool,000069,,,Alarm for Phase Overcurrent Warning
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000065,Summary_Alm_Flt,bool,,,,Coil to trigger Summary Alarm
|
|
|
|
|
Discrete_Input,100065,Summary_Alm,bool,000065,,,Alarm for Summary
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Coil,000067,Panel_Undervoltage_Flt,bool,,,,Coil to trigger Panel Undervoltage
|
|
|
|
|
Discrete_Input,100067,Panel_Undervoltage,bool,000067,,,Alarm for Panel Undervoltage
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Holding_Register,41110,Amps_A,uint16,,430001,Integer,Amps_A
|
|
|
|
|
Holding_Register,41111,Amps_B,uint16,,430003,Integer,Amps_B
|
|
|
|
|
Holding_Register,41112,Amps_C,uint16,,430005,Integer,Amps_C
|
|
|
|
|
Holding_Register,41113,Amps_N,uint16,,430007,Integer,Amps_N
|
|
|
|
|
Holding_Register,41114,Amps_G,uint16,,430009,Integer,Amps_G
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Input_Register,300463,Breaker_Columns,uint16,400463,,,Breaker_Columns
|
|
|
|
|
Holding_Register,400463,Breaker_Columns_Ovr,uint16,,430713,Integer,Breaker_Columns_Ovr
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Holding_Register,420657,CT01_Amps,uint16,,430011,Integer,CT01_Amps
|
|
|
|
|
Holding_Register,420001,CT01_kW,uint16,,430013,Integer,CT01_kW
|
|
|
|
|
Holding_Register,420821,CT01_kWH,uint32,,430015,Float,CT01_kWH
|
|
|
|
|
Holding_Register,420698,CT02_Amps,uint16,,430019,Integer,CT02_Amps
|
|
|
|
|
Holding_Register,420042,CT02_kW,uint16,,430021,Integer,CT02_kW
|
|
|
|
|
Holding_Register,420903,CT02_kWH,uint32,,430023,Float,CT02_kWH
|
|
|
|
|
Holding_Register,420658,CT03_Amps,uint16,,430027,Integer,CT03_Amps
|
|
|
|
|
Holding_Register,420002,CT03_kW,uint16,,430029,Integer,CT03_kW
|
|
|
|
|
Holding_Register,420823,CT03_kWH,uint32,,430031,Float,CT03_kWH
|
|
|
|
|
Holding_Register,420699,CT04_Amps,uint16,,430035,Integer,CT04_Amps
|
|
|
|
|
Holding_Register,420043,CT04_kW,uint16,,430037,Integer,CT04_kW
|
|
|
|
|
Holding_Register,420905,CT04_kWH,uint32,,430039,Float,CT04_kWH
|
|
|
|
|
Holding_Register,420659,CT05_Amps,uint16,,430043,Integer,CT05_Amps
|
|
|
|
|
Holding_Register,420003,CT05_kW,uint16,,430045,Integer,CT05_kW
|
|
|
|
|
Holding_Register,420825,CT05_kWH,uint32,,430047,Float,CT05_kWH
|
|
|
|
|
Holding_Register,420700,CT06_Amps,uint16,,430051,Integer,CT06_Amps
|
|
|
|
|
Holding_Register,420044,CT06_kW,uint16,,430053,Integer,CT06_kW
|
|
|
|
|
Holding_Register,420907,CT06_kWH,uint32,,430055,Float,CT06_kWH
|
|
|
|
|
Holding_Register,420660,CT07_Amps,uint16,,430059,Integer,CT07_Amps
|
|
|
|
|
Holding_Register,420004,CT07_kW,uint16,,430061,Integer,CT07_kW
|
|
|
|
|
Holding_Register,420827,CT07_kWH,uint32,,430063,Float,CT07_kWH
|
|
|
|
|
Holding_Register,420701,CT08_Amps,uint16,,430067,Integer,CT08_Amps
|
|
|
|
|
Holding_Register,420045,CT08_kW,uint16,,430069,Integer,CT08_kW
|
|
|
|
|
Holding_Register,420911,CT08_kWH,uint32,,430071,Float,CT08_kWH
|
|
|
|
|
Holding_Register,420661,CT09_Amps,uint16,,430075,Integer,CT09_Amps
|
|
|
|
|
Holding_Register,420005,CT09_kW,uint16,,430077,Integer,CT09_kW
|
|
|
|
|
Holding_Register,420829,CT09_kWH,uint32,,430079,Float,CT09_kWH
|
|
|
|
|
Holding_Register,420702,CT10_Amps,uint16,,430083,Integer,CT10_Amps
|
|
|
|
|
Holding_Register,420046,CT10_kW,uint16,,430085,Integer,CT10_kW
|
|
|
|
|
Holding_Register,420913,CT10_kWH,uint32,,430087,Float,CT10_kWH
|
|
|
|
|
Holding_Register,420662,CT11_Amps,uint16,,430091,Integer,CT11_Amps
|
|
|
|
|
Holding_Register,420006,CT11_kW,uint16,,430093,Integer,CT11_kW
|
|
|
|
|
Holding_Register,420831,CT11_kWH,uint32,,430095,Float,CT11_kWH
|
|
|
|
|
Holding_Register,420703,CT12_Amps,uint16,,430099,Integer,CT12_Amps
|
|
|
|
|
Holding_Register,420047,CT12_kW,uint16,,430101,Integer,CT12_kW
|
|
|
|
|
Holding_Register,420915,CT12_kWH,uint32,,430103,Float,CT12_kWH
|
|
|
|
|
Holding_Register,420663,CT13_Amps,uint16,,430107,Integer,CT13_Amps
|
|
|
|
|
Holding_Register,420007,CT13_kW,uint16,,430109,Integer,CT13_kW
|
|
|
|
|
Holding_Register,420833,CT13_kWH,uint32,,430111,Float,CT13_kWH
|
|
|
|
|
Holding_Register,420704,CT14_Amps,uint16,,430115,Integer,CT14_Amps
|
|
|
|
|
Holding_Register,420048,CT14_kW,uint16,,430117,Integer,CT14_kW
|
|
|
|
|
Holding_Register,420917,CT14_kWH,uint32,,430119,Float,CT14_kWH
|
|
|
|
|
Holding_Register,420664,CT15_Amps,uint16,,430123,Integer,CT15_Amps
|
|
|
|
|
Holding_Register,420008,CT15_kW,uint16,,430125,Integer,CT15_kW
|
|
|
|
|
Holding_Register,420835,CT15_kWH,uint32,,430127,Float,CT15_kWH
|
|
|
|
|
Holding_Register,420705,CT16_Amps,uint16,,430131,Integer,CT16_Amps
|
|
|
|
|
Holding_Register,420049,CT16_kW,uint16,,430133,Integer,CT16_kW
|
|
|
|
|
Holding_Register,420919,CT16_kWH,uint32,,430135,Float,CT16_kWH
|
|
|
|
|
Holding_Register,420665,CT17_Amps,uint16,,430139,Integer,CT17_Amps
|
|
|
|
|
Holding_Register,420009,CT17_kW,uint16,,430141,Integer,CT17_kW
|
|
|
|
|
Holding_Register,420837,CT17_kWH,uint32,,430143,Float,CT17_kWH
|
|
|
|
|
Holding_Register,420706,CT18_Amps,uint16,,430147,Integer,CT18_Amps
|
|
|
|
|
Holding_Register,420050,CT18_kW,uint16,,430149,Integer,CT18_kW
|
|
|
|
|
Holding_Register,420921,CT18_kWH,uint32,,430151,Float,CT18_kWH
|
|
|
|
|
Holding_Register,420666,CT19_Amps,uint16,,430155,Integer,CT19_Amps
|
|
|
|
|
Holding_Register,420010,CT19_kW,uint16,,430157,Integer,CT19_kW
|
|
|
|
|
Holding_Register,420839,CT19_kWH,uint32,,430159,Float,CT19_kWH
|
|
|
|
|
Holding_Register,420707,CT20_Amps,uint16,,430163,Integer,CT20_Amps
|
|
|
|
|
Holding_Register,420051,CT20_kW,uint16,,430165,Integer,CT20_kW
|
|
|
|
|
Holding_Register,420923,CT20_kWH,uint32,,430167,Float,CT20_kWH
|
|
|
|
|
Holding_Register,420667,CT21_Amps,uint16,,430171,Integer,CT21_Amps
|
|
|
|
|
Holding_Register,420011,CT21_kW,uint16,,430173,Integer,CT21_kW
|
|
|
|
|
Holding_Register,420841,CT21_kWH,uint32,,430175,Float,CT21_kWH
|
|
|
|
|
Holding_Register,420708,CT22_Amps,uint16,,430179,Integer,CT22_Amps
|
|
|
|
|
Holding_Register,420052,CT22_kW,uint16,,430181,Integer,CT22_kW
|
|
|
|
|
Holding_Register,420925,CT22_kWH,uint32,,430183,Float,CT22_kWH
|
|
|
|
|
Holding_Register,420668,CT23_Amps,uint16,,430187,Integer,CT23_Amps
|
|
|
|
|
Holding_Register,420012,CT23_kW,uint16,,430189,Integer,CT23_kW
|
|
|
|
|
Holding_Register,420843,CT23_kWH,uint32,,430191,Float,CT23_kWH
|
|
|
|
|
Holding_Register,420709,CT24_Amps,uint16,,430195,Integer,CT24_Amps
|
|
|
|
|
Holding_Register,420053,CT24_kW,uint16,,430197,Integer,CT24_kW
|
|
|
|
|
Holding_Register,420927,CT24_kWH,uint32,,430199,Float,CT24_kWH
|
|
|
|
|
Holding_Register,420669,CT25_Amps,uint16,,430203,Integer,CT25_Amps
|
|
|
|
|
Holding_Register,420013,CT25_kW,uint16,,430205,Integer,CT25_kW
|
|
|
|
|
Holding_Register,420845,CT25_kWH,uint32,,430207,Float,CT25_kWH
|
|
|
|
|
Holding_Register,420710,CT26_Amps,uint16,,430211,Integer,CT26_Amps
|
|
|
|
|
Holding_Register,420054,CT26_kW,uint16,,430213,Integer,CT26_kW
|
|
|
|
|
Holding_Register,420929,CT26_kWH,uint32,,430215,Float,CT26_kWH
|
|
|
|
|
Holding_Register,420670,CT27_Amps,uint16,,430219,Integer,CT27_Amps
|
|
|
|
|
Holding_Register,420014,CT27_kW,uint16,,430221,Integer,CT27_kW
|
|
|
|
|
Holding_Register,420847,CT27_kWH,uint32,,430223,Float,CT27_kWH
|
|
|
|
|
Holding_Register,420711,CT28_Amps,uint16,,430227,Integer,CT28_Amps
|
|
|
|
|
Holding_Register,420055,CT28_kW,uint16,,430229,Integer,CT28_kW
|
|
|
|
|
Holding_Register,420931,CT28_kWH,uint32,,430231,Float,CT28_kWH
|
|
|
|
|
Holding_Register,420671,CT29_Amps,uint16,,430235,Integer,CT29_Amps
|
|
|
|
|
Holding_Register,420015,CT29_kW,uint16,,430237,Integer,CT29_kW
|
|
|
|
|
Holding_Register,420849,CT29_kWH,uint32,,430239,Float,CT29_kWH
|
|
|
|
|
Holding_Register,420712,CT30_Amps,uint16,,430243,Integer,CT30_Amps
|
|
|
|
|
Holding_Register,420056,CT30_kW,uint16,,430245,Integer,CT30_kW
|
|
|
|
|
Holding_Register,420933,CT30_kWH,uint32,,430247,Float,CT30_kWH
|
|
|
|
|
Holding_Register,420672,CT31_Amps,uint16,,430251,Integer,CT31_Amps
|
|
|
|
|
Holding_Register,420016,CT31_kW,uint16,,430253,Integer,CT31_kW
|
|
|
|
|
Holding_Register,420851,CT31_kWH,uint32,,430255,Float,CT31_kWH
|
|
|
|
|
Holding_Register,420713,CT32_Amps,uint16,,430259,Integer,CT32_Amps
|
|
|
|
|
Holding_Register,420057,CT32_kW,uint16,,430261,Integer,CT32_kW
|
|
|
|
|
Holding_Register,420935,CT32_kWH,uint32,,430263,Float,CT32_kWH
|
|
|
|
|
Holding_Register,420673,CT33_Amps,uint16,,430267,Integer,CT33_Amps
|
|
|
|
|
Holding_Register,420017,CT33_kW,uint16,,430269,Integer,CT33_kW
|
|
|
|
|
Holding_Register,420853,CT33_kWH,uint32,,430271,Float,CT33_kWH
|
|
|
|
|
Holding_Register,420714,CT34_Amps,uint16,,430275,Integer,CT34_Amps
|
|
|
|
|
Holding_Register,420058,CT34_kW,uint16,,430277,Integer,CT34_kW
|
|
|
|
|
Holding_Register,420937,CT34_kWH,uint32,,430279,Float,CT34_kWH
|
|
|
|
|
Holding_Register,420674,CT35_Amps,uint16,,430283,Integer,CT35_Amps
|
|
|
|
|
Holding_Register,420018,CT35_kW,uint16,,430285,Integer,CT35_kW
|
|
|
|
|
Holding_Register,420855,CT35_kWH,uint32,,430287,Float,CT35_kWH
|
|
|
|
|
Holding_Register,420715,CT36_Amps,uint16,,430291,Integer,CT36_Amps
|
|
|
|
|
Holding_Register,420059,CT36_kW,uint16,,430293,Integer,CT36_kW
|
|
|
|
|
Holding_Register,420939,CT36_kWH,uint32,,430295,Float,CT36_kWH
|
|
|
|
|
Holding_Register,420675,CT37_Amps,uint16,,430299,Integer,CT37_Amps
|
|
|
|
|
Holding_Register,420019,CT37_kW,uint16,,430301,Integer,CT37_kW
|
|
|
|
|
Holding_Register,420857,CT37_kWH,uint32,,430303,Float,CT37_kWH
|
|
|
|
|
Holding_Register,420716,CT38_Amps,uint16,,430307,Integer,CT38_Amps
|
|
|
|
|
Holding_Register,420060,CT38_kW,uint16,,430309,Integer,CT38_kW
|
|
|
|
|
Holding_Register,420941,CT38_kWH,uint32,,430311,Float,CT38_kWH
|
|
|
|
|
Holding_Register,420676,CT39_Amps,uint16,,430315,Integer,CT39_Amps
|
|
|
|
|
Holding_Register,420020,CT39_kW,uint16,,430317,Integer,CT39_kW
|
|
|
|
|
Holding_Register,420859,CT39_kWH,uint32,,430319,Float,CT39_kWH
|
|
|
|
|
Holding_Register,420717,CT40_Amps,uint16,,430323,Integer,CT40_Amps
|
|
|
|
|
Holding_Register,420061,CT40_kW,uint16,,430325,Integer,CT40_kW
|
|
|
|
|
Holding_Register,420943,CT40_kWH,uint32,,430327,Float,CT40_kWH
|
|
|
|
|
Holding_Register,420677,CT41_Amps,uint16,,430331,Integer,CT41_Amps
|
|
|
|
|
Holding_Register,420021,CT41_kW,uint16,,430333,Integer,CT41_kW
|
|
|
|
|
Holding_Register,420861,CT41_kWH,uint32,,430335,Float,CT41_kWH
|
|
|
|
|
Holding_Register,420718,CT42_Amps,uint16,,430339,Integer,CT42_Amps
|
|
|
|
|
Holding_Register,420062,CT42_kW,uint16,,430341,Integer,CT42_kW
|
|
|
|
|
Holding_Register,420945,CT42_kWH,uint32,,430343,Float,CT42_kWH
|
|
|
|
|
Holding_Register,420739,CT43_Amps,uint16,,430347,Integer,CT43_Amps
|
|
|
|
|
Holding_Register,420083,CT43_kW,uint16,,430349,Integer,CT43_kW
|
|
|
|
|
Holding_Register,420985,CT43_kWH,uint32,,430351,Float,CT43_kWH
|
|
|
|
|
Holding_Register,420780,CT44_Amps,uint16,,430355,Integer,CT44_Amps
|
|
|
|
|
Holding_Register,420124,CT44_kW,uint16,,430357,Integer,CT44_kW
|
|
|
|
|
Holding_Register,421067,CT44_kWH,uint32,,430359,Float,CT44_kWH
|
|
|
|
|
Holding_Register,420740,CT45_Amps,uint16,,430363,Integer,CT45_Amps
|
|
|
|
|
Holding_Register,420084,CT45_kW,uint16,,430365,Integer,CT45_kW
|
|
|
|
|
Holding_Register,420987,CT45_kWH,uint32,,430367,Float,CT45_kWH
|
|
|
|
|
Holding_Register,420781,CT46_Amps,uint16,,430371,Integer,CT46_Amps
|
|
|
|
|
Holding_Register,420125,CT46_kW,uint16,,430373,Integer,CT46_kW
|
|
|
|
|
Holding_Register,421069,CT46_kWH,uint32,,430375,Float,CT46_kWH
|
|
|
|
|
Holding_Register,420741,CT47_Amps,uint16,,430379,Integer,CT47_Amps
|
|
|
|
|
Holding_Register,420085,CT47_kW,uint16,,430381,Integer,CT47_kW
|
|
|
|
|
Holding_Register,420989,CT47_kWH,uint32,,430383,Float,CT47_kWH
|
|
|
|
|
Holding_Register,420782,CT48_Amps,uint16,,430387,Integer,CT48_Amps
|
|
|
|
|
Holding_Register,420126,CT48_kW,uint16,,430389,Integer,CT48_kW
|
|
|
|
|
Holding_Register,421071,CT48_kWH,uint32,,430391,Float,CT48_kWH
|
|
|
|
|
Holding_Register,420742,CT49_Amps,uint16,,430395,Integer,CT49_Amps
|
|
|
|
|
Holding_Register,420086,CT49_kW,uint16,,430397,Integer,CT49_kW
|
|
|
|
|
Holding_Register,420991,CT49_kWH,uint32,,430399,Float,CT49_kWH
|
|
|
|
|
Holding_Register,420783,CT50_Amps,uint16,,430403,Integer,CT50_Amps
|
|
|
|
|
Holding_Register,420127,CT50_kW,uint16,,430405,Integer,CT50_kW
|
|
|
|
|
Holding_Register,421073,CT50_kWH,uint32,,430407,Float,CT50_kWH
|
|
|
|
|
Holding_Register,420743,CT51_Amps,uint16,,430411,Integer,CT51_Amps
|
|
|
|
|
Holding_Register,420087,CT51_kW,uint16,,430413,Integer,CT51_kW
|
|
|
|
|
Holding_Register,420993,CT51_kWH,uint32,,430415,Float,CT51_kWH
|
|
|
|
|
Holding_Register,420784,CT52_Amps,uint16,,430419,Integer,CT52_Amps
|
|
|
|
|
Holding_Register,420128,CT52_kW,uint16,,430421,Integer,CT52_kW
|
|
|
|
|
Holding_Register,421075,CT52_kWH,uint32,,430423,Float,CT52_kWH
|
|
|
|
|
Holding_Register,420744,CT53_Amps,uint16,,430427,Integer,CT53_Amps
|
|
|
|
|
Holding_Register,420088,CT53_kW,uint16,,430429,Integer,CT53_kW
|
|
|
|
|
Holding_Register,420995,CT53_kWH,uint32,,430431,Float,CT53_kWH
|
|
|
|
|
Holding_Register,420785,CT54_Amps,uint16,,430435,Integer,CT54_Amps
|
|
|
|
|
Holding_Register,420129,CT54_kW,uint16,,430437,Integer,CT54_kW
|
|
|
|
|
Holding_Register,421077,CT54_kWH,uint32,,430439,Float,CT54_kWH
|
|
|
|
|
Holding_Register,420745,CT55_Amps,uint16,,430443,Integer,CT55_Amps
|
|
|
|
|
Holding_Register,420089,CT55_kW,uint16,,430445,Integer,CT55_kW
|
|
|
|
|
Holding_Register,420997,CT55_kWH,uint32,,430447,Float,CT55_kWH
|
|
|
|
|
Holding_Register,420786,CT56_Amps,uint16,,430451,Integer,CT56_Amps
|
|
|
|
|
Holding_Register,420130,CT56_kW,uint16,,430453,Integer,CT56_kW
|
|
|
|
|
Holding_Register,421079,CT56_kWH,uint32,,430455,Float,CT56_kWH
|
|
|
|
|
Holding_Register,420746,CT57_Amps,uint16,,430459,Integer,CT57_Amps
|
|
|
|
|
Holding_Register,420090,CT57_kW,uint16,,430461,Integer,CT57_kW
|
|
|
|
|
Holding_Register,420999,CT57_kWH,uint32,,430463,Float,CT57_kWH
|
|
|
|
|
Holding_Register,420787,CT58_Amps,uint16,,430467,Integer,CT58_Amps
|
|
|
|
|
Holding_Register,420131,CT58_kW,uint16,,430469,Integer,CT58_kW
|
|
|
|
|
Holding_Register,421081,CT58_kWH,uint32,,430471,Float,CT58_kWH
|
|
|
|
|
Holding_Register,420747,CT59_Amps,uint16,,430475,Integer,CT59_Amps
|
|
|
|
|
Holding_Register,420091,CT59_kW,uint16,,430477,Integer,CT59_kW
|
|
|
|
|
Holding_Register,421001,CT59_kWH,uint32,,430479,Float,CT59_kWH
|
|
|
|
|
Holding_Register,420788,CT60_Amps,uint16,,430483,Integer,CT60_Amps
|
|
|
|
|
Holding_Register,420132,CT60_kW,uint16,,430485,Integer,CT60_kW
|
|
|
|
|
Holding_Register,421083,CT60_kWH,uint32,,430487,Float,CT60_kWH
|
|
|
|
|
Holding_Register,420748,CT61_Amps,uint16,,430491,Integer,CT61_Amps
|
|
|
|
|
Holding_Register,420092,CT61_kW,uint16,,430493,Integer,CT61_kW
|
|
|
|
|
Holding_Register,421003,CT61_kWH,uint32,,430495,Float,CT61_kWH
|
|
|
|
|
Holding_Register,420789,CT62_Amps,uint16,,430499,Integer,CT62_Amps
|
|
|
|
|
Holding_Register,420133,CT62_kW,uint16,,430501,Integer,CT62_kW
|
|
|
|
|
Holding_Register,421085,CT62_kWH,uint32,,430503,Float,CT62_kWH
|
|
|
|
|
Holding_Register,420749,CT63_Amps,uint16,,430507,Integer,CT63_Amps
|
|
|
|
|
Holding_Register,420093,CT63_kW,uint16,,430509,Integer,CT63_kW
|
|
|
|
|
Holding_Register,421005,CT63_kWH,uint32,,430511,Float,CT63_kWH
|
|
|
|
|
Holding_Register,420790,CT64_Amps,uint16,,430515,Integer,CT64_Amps
|
|
|
|
|
Holding_Register,420134,CT64_kW,uint16,,430517,Integer,CT64_kW
|
|
|
|
|
Holding_Register,421087,CT64_kWH,uint32,,430519,Float,CT64_kWH
|
|
|
|
|
Holding_Register,420750,CT65_Amps,uint16,,430523,Integer,CT65_Amps
|
|
|
|
|
Holding_Register,420094,CT65_kW,uint16,,430525,Integer,CT65_kW
|
|
|
|
|
Holding_Register,421007,CT65_kWH,uint32,,430527,Float,CT65_kWH
|
|
|
|
|
Holding_Register,420791,CT66_Amps,uint16,,430531,Integer,CT66_Amps
|
|
|
|
|
Holding_Register,420135,CT66_kW,uint16,,430533,Integer,CT66_kW
|
|
|
|
|
Holding_Register,421089,CT66_kWH,uint32,,430535,Float,CT66_kWH
|
|
|
|
|
Holding_Register,420751,CT67_Amps,uint16,,430539,Integer,CT67_Amps
|
|
|
|
|
Holding_Register,420095,CT67_kW,uint16,,430541,Integer,CT67_kW
|
|
|
|
|
Holding_Register,421009,CT67_kWH,uint32,,430543,Float,CT67_kWH
|
|
|
|
|
Holding_Register,420792,CT68_Amps,uint16,,430547,Integer,CT68_Amps
|
|
|
|
|
Holding_Register,420136,CT68_kW,uint16,,430549,Integer,CT68_kW
|
|
|
|
|
Holding_Register,421091,CT68_kWH,uint32,,430551,Float,CT68_kWH
|
|
|
|
|
Holding_Register,420752,CT69_Amps,uint16,,430555,Integer,CT69_Amps
|
|
|
|
|
Holding_Register,420096,CT69_kW,uint16,,430557,Integer,CT69_kW
|
|
|
|
|
Holding_Register,421011,CT69_kWH,uint32,,430559,Float,CT69_kWH
|
|
|
|
|
Holding_Register,420793,CT70_Amps,uint16,,430563,Integer,CT70_Amps
|
|
|
|
|
Holding_Register,420137,CT70_kW,uint16,,430565,Integer,CT70_kW
|
|
|
|
|
Holding_Register,421093,CT70_kWH,uint32,,430567,Float,CT70_kWH
|
|
|
|
|
Holding_Register,420753,CT71_Amps,uint16,,430571,Integer,CT71_Amps
|
|
|
|
|
Holding_Register,420097,CT71_kW,uint16,,430573,Integer,CT71_kW
|
|
|
|
|
Holding_Register,421013,CT71_kWH,uint32,,430575,Float,CT71_kWH
|
|
|
|
|
Holding_Register,420794,CT72_Amps,uint16,,430579,Integer,CT72_Amps
|
|
|
|
|
Holding_Register,420138,CT72_kW,uint16,,430581,Integer,CT72_kW
|
|
|
|
|
Holding_Register,421095,CT72_kWH,uint32,,430583,Float,CT72_kWH
|
|
|
|
|
Holding_Register,420754,CT73_Amps,uint16,,430587,Integer,CT73_Amps
|
|
|
|
|
Holding_Register,420098,CT73_kW,uint16,,430589,Integer,CT73_kW
|
|
|
|
|
Holding_Register,421015,CT73_kWH,uint32,,430591,Float,CT73_kWH
|
|
|
|
|
Holding_Register,420795,CT74_Amps,uint16,,430595,Integer,CT74_Amps
|
|
|
|
|
Holding_Register,420139,CT74_kW,uint16,,430597,Integer,CT74_kW
|
|
|
|
|
Holding_Register,421097,CT74_kWH,uint32,,430599,Float,CT74_kWH
|
|
|
|
|
Holding_Register,420755,CT75_Amps,uint16,,430603,Integer,CT75_Amps
|
|
|
|
|
Holding_Register,420099,CT75_kW,uint16,,430605,Integer,CT75_kW
|
|
|
|
|
Holding_Register,421017,CT75_kWH,uint32,,430607,Float,CT75_kWH
|
|
|
|
|
Holding_Register,420796,CT76_Amps,uint16,,430611,Integer,CT76_Amps
|
|
|
|
|
Holding_Register,420140,CT76_kW,uint16,,430613,Integer,CT76_kW
|
|
|
|
|
Holding_Register,421099,CT76_kWH,uint32,,430615,Float,CT76_kWH
|
|
|
|
|
Holding_Register,420756,CT77_Amps,uint16,,430619,Integer,CT77_Amps
|
|
|
|
|
Holding_Register,420100,CT77_kW,uint16,,430621,Integer,CT77_kW
|
|
|
|
|
Holding_Register,421019,CT77_kWH,uint32,,430623,Float,CT77_kWH
|
|
|
|
|
Holding_Register,420797,CT78_Amps,uint16,,430627,Integer,CT78_Amps
|
|
|
|
|
Holding_Register,420141,CT78_kW,uint16,,430629,Integer,CT78_kW
|
|
|
|
|
Holding_Register,421101,CT78_kWH,uint32,,430631,Float,CT78_kWH
|
|
|
|
|
Holding_Register,420757,CT79_Amps,uint16,,430635,Integer,CT79_Amps
|
|
|
|
|
Holding_Register,420101,CT79_kW,uint16,,430637,Integer,CT79_kW
|
|
|
|
|
Holding_Register,421021,CT79_kWH,uint32,,430639,Float,CT79_kWH
|
|
|
|
|
Holding_Register,420798,CT80_Amps,uint16,,430643,Integer,CT80_Amps
|
|
|
|
|
Holding_Register,420142,CT80_kW,uint16,,430645,Integer,CT80_kW
|
|
|
|
|
Holding_Register,421103,CT80_kWH,uint32,,430647,Float,CT80_kWH
|
|
|
|
|
Holding_Register,420758,CT81_Amps,uint16,,430651,Integer,CT81_Amps
|
|
|
|
|
Holding_Register,420102,CT81_kW,uint16,,430653,Integer,CT81_kW
|
|
|
|
|
Holding_Register,421023,CT81_kWH,uint32,,430655,Float,CT81_kWH
|
|
|
|
|
Holding_Register,420799,CT82_Amps,uint16,,430659,Integer,CT82_Amps
|
|
|
|
|
Holding_Register,420143,CT82_kW,uint16,,430661,Integer,CT82_kW
|
|
|
|
|
Holding_Register,421105,CT82_kWH,uint32,,430663,Float,CT82_kWH
|
|
|
|
|
Holding_Register,420759,CT83_Amps,uint16,,430667,Integer,CT83_Amps
|
|
|
|
|
Holding_Register,420103,CT83_kW,uint16,,430669,Integer,CT83_kW
|
|
|
|
|
Holding_Register,421025,CT83_kWH,uint32,,430671,Float,CT83_kWH
|
|
|
|
|
Holding_Register,420800,CT84_Amps,uint16,,430675,Integer,CT84_Amps
|
|
|
|
|
Holding_Register,420144,CT84_kW,uint16,,430677,Integer,CT84_kW
|
|
|
|
|
Holding_Register,421107,CT84_kWH,uint32,,430679,Float,CT84_kWH
|
|
|
|
|
,,,,,,,
|
|
|
|
|
Holding_Register,422060,Freq,float,,430683,Float,Freq
|
|
|
|
|
Holding_Register,41127,kVA,uint16,,430687,Integer,kVA
|
|
|
|
|
Holding_Register,41119,kW,uint16,,430689,Integer,kW
|
|
|
|
|
Holding_Register,41151,kWH,uint32,,430691,Float,kWH
|
|
|
|
|
Holding_Register,41131,PF,uint16,,430695,Integer,PF
|
|
|
|
|
Holding_Register,41102,Volts_AB,uint16,,430697,Integer,Volts_AB
|
|
|
|
|
Holding_Register,41106,Volts_AN,uint16,,430699,Integer,Volts_AN
|
|
|
|
|
Holding_Register,41103,Volts_BC,uint16,,430701,Integer,Volts_BC
|
|
|
|
|
Holding_Register,41107,Volts_BN,uint16,,430703,Integer,Volts_BN
|
|
|
|
|
Holding_Register,41104,Volts_CA,uint16,,430705,Integer,Volts_CA
|
|
|
|
|
Holding_Register,41108,Volts_CN,uint16,,430707,Integer,Volts_CN
|
|
|
|
|
Holding_Register,41105,Volts_LL_Avg,uint16,,430709,Integer,Volts_LL_Avg
|
|
|
|
|
Holding_Register,41109,Volts_LN_Avg,uint16,,430711,Integer,Volts_LN_Avg
|