template<>
|
||||
RunningState<ModbusIP>::RunningState() {
|
||||
addStrategy("CW Valve Position", new PIDStrategy("RAT Setpoint", 1000, "RAT"));
|
||||
addStrategy("Operating Hours EC Fan #1", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #2", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #3", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #4", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #5", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #6", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #7", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #8", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #9", new TotalizerStrategy(10000));
|
||||
addStrategy("CW Valve Position", new PIDStrategy("SAT Setpoint", 2000, "SAT Reading"));
|
||||
addStrategy("SAT Reading", new SingleValueStrategy(0.0f, 3.0f, 1000));
|
||||
addStrategy("Speed EC Fan #1", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #2", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #3", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #4", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #5", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #6", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #7", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #8", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #9", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Operating Hours EC Fan #1", new TotalizerStrategy(1100));
|
||||
addStrategy("Operating Hours EC Fan #2", new TotalizerStrategy(1200));
|
||||
addStrategy("Operating Hours EC Fan #3", new TotalizerStrategy(1300));
|
||||
addStrategy("Operating Hours EC Fan #4", new TotalizerStrategy(1250));
|
||||
addStrategy("Operating Hours EC Fan #5", new TotalizerStrategy(1350));
|
||||
addStrategy("Operating Hours EC Fan #6", new TotalizerStrategy(1450));
|
||||
addStrategy("Operating Hours EC Fan #7", new TotalizerStrategy(1150));
|
||||
addStrategy("Operating Hours EC Fan #8", new TotalizerStrategy(1180));
|
||||
addStrategy("Operating Hours EC Fan #9", new TotalizerStrategy(1340));
|
||||
}
|
||||
|
||||
/**
|
||||
@@ -74,63 +84,36 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
|
||||
return new StandbyState<ModbusIP>();
|
||||
}
|
||||
|
||||
Modbus_Point<ModbusIP>* faultCode = equipment->getModbus_Point("Fault Code");
|
||||
int faultCodeValue = faultCode ? faultCode->getValue() : 0;
|
||||
switch (faultCodeValue){
|
||||
case 1:
|
||||
return new FailState<ModbusIP>({"Alarm SAT Sensor Fault"});
|
||||
case 2:
|
||||
return new FailState<ModbusIP>({"Alarm RAH Sensor Fault"});
|
||||
case 3:
|
||||
return new FailState<ModbusIP>({"Alarm RAT Sensor Fault"});
|
||||
case 4:
|
||||
return new FailState<ModbusIP>({"Alarm Filter DP Sensor Fault"});
|
||||
case 5:
|
||||
return new FailState<ModbusIP>({"Alarm Flooding"});
|
||||
case 6:
|
||||
return new FailState<ModbusIP>({"Alarm Dirty Filter"});
|
||||
case 7:
|
||||
return new FailState<ModbusIP>({"Alarm High RAT"});
|
||||
case 8:
|
||||
return new FailState<ModbusIP>({"Alarm Low RAT"});
|
||||
case 9:
|
||||
return new FailState<ModbusIP>({"Alarm High SAT"});
|
||||
case 10:
|
||||
return new FailState<ModbusIP>({"Alarm Low SAT"});
|
||||
case 11:
|
||||
return new FailState<ModbusIP>({"Alarm High RAH"});
|
||||
case 12:
|
||||
return new FailState<ModbusIP>({"Alarm Low RAH"});
|
||||
case 13:
|
||||
return new FailState<ModbusIP>({"Alarm Phase Failure"});
|
||||
case 14:
|
||||
return new FailState<ModbusIP>({"Alarm Condensate Pump"});
|
||||
case 15:
|
||||
return new FailState<ModbusIP>({"Alarm Smoke"});
|
||||
case 16:
|
||||
return new FailState<ModbusIP>({"Alarm Fire"});
|
||||
case 17:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #1"});
|
||||
case 18:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #2"});
|
||||
case 19:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #3"});
|
||||
case 20:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #4"});
|
||||
case 21:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #5"});
|
||||
case 22:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #6"});
|
||||
case 23:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #7"});
|
||||
case 24:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #8"});
|
||||
case 25:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #9"});
|
||||
default:
|
||||
break;
|
||||
}
|
||||
|
||||
float rat = getPointValue(equipment, "RAT");
|
||||
setPointValue(equipment, "RAT Reading", rat);
|
||||
float speed = getPointValue(equipment, "Setting EC Fan Speed");
|
||||
Strategy_Behavior* fan1_rs = getStrategy("Speed EC Fan #1");
|
||||
static_cast<RampStrategy*>(fan1_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan2_rs = getStrategy("Speed EC Fan #2");
|
||||
static_cast<RampStrategy*>(fan2_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan3_rs = getStrategy("Speed EC Fan #3");
|
||||
static_cast<RampStrategy*>(fan3_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan4_rs = getStrategy("Speed EC Fan #4");
|
||||
static_cast<RampStrategy*>(fan4_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan5_rs = getStrategy("Speed EC Fan #5");
|
||||
static_cast<RampStrategy*>(fan5_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan6_rs = getStrategy("Speed EC Fan #6");
|
||||
static_cast<RampStrategy*>(fan6_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan7_rs = getStrategy("Speed EC Fan #7");
|
||||
static_cast<RampStrategy*>(fan7_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan8_rs = getStrategy("Speed EC Fan #8");
|
||||
static_cast<RampStrategy*>(fan8_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan9_rs = getStrategy("Speed EC Fan #9");
|
||||
static_cast<RampStrategy*>(fan9_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
|
||||
|
||||
|
||||
float value = getPointValue(equipment, "CW Valve Position");
|
||||
Serial.printf("CW Valve Position: %0.2f\n", value);
|
||||
float sat_setpoint = getPointValue(equipment, "SAT Setpoint");
|
||||
Strategy_Behavior* sat_svs = getStrategy("SAT Reading");
|
||||
static_cast<SingleValueStrategy*>(sat_svs)->setSetpoint(sat_setpoint);
|
||||
// Apply any strategies defined for the standby state
|
||||
_applyStrategies(equipment);
|
||||
return nullptr;
|
||||
|
||||
@@ -21,10 +21,10 @@
|
||||
* @{
|
||||
*/
|
||||
#include <ModbusIP_ESP8266.h>
|
||||
const char *ssid = "wifi_name"; /**< @brief The SSID of the WiFi network. */
|
||||
const char *password = "wifi_password"; /**< @brief The password for the WiFi network. */
|
||||
IPAddress local_IP(192, 168, 1, 234); /**< @brief The static IP address for the device. */
|
||||
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
|
||||
const char *ssid = "QTS_CDR_Arduino"; /**< @brief The SSID of the WiFi network. */
|
||||
const char *password = "123abc456"; /**< @brief The password for the WiFi network. */
|
||||
IPAddress local_IP(172, 17, 33, 11); /**< @brief The static IP address for the device. */
|
||||
IPAddress gateway(172, 17, 33, 1); /**< @brief The gateway IP address. */
|
||||
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
|
||||
|
||||
ModbusIP mb;
|
||||
@@ -60,81 +60,82 @@
|
||||
*/
|
||||
modbusMap mb_map[] =
|
||||
{
|
||||
{HR, 15, 0, "State Control"}, //Internal to control from Modscan
|
||||
{HR, 16, 0, "Fault Code"},
|
||||
{HR_FLOAT, 18, 0, "RAT"}, //Internal Fault code from Modscan
|
||||
{HR_FLOAT, 1, 0, "SAT Setpoint"},
|
||||
{HR_FLOAT, 681, 0, "RAT Setpoint"},
|
||||
{HR_FLOAT, 111, 0, "High RAT Limit"},
|
||||
{HR_FLOAT, 114, 0, "Low RAT Limit"},
|
||||
{HR_FLOAT, 118, 0, "High SAT Limit"},
|
||||
{HR_FLOAT, 122, 0, "Low SAT Limit"},
|
||||
{HR_FLOAT, 685, 0, "High RAH Limit"},
|
||||
{HR_FLOAT, 689, 0, "Low RAH Limit"},
|
||||
{HR, 5, 0, "Setting the EC Fan Max Speed"},
|
||||
{HR, 695, 0, "Setting the EC Fan Min Speed"},
|
||||
{HR_FLOAT, 693, 0, "Setting Room Temp"},
|
||||
{HR, 691, 0, "Setting EC Fan Speed "},
|
||||
{DI, 146, 0, "Alarm SAT Sensor Fault"},
|
||||
{DI, 1246, 0, "Alarm RAH Sensor Fault"},
|
||||
{DI, 1245, 0, "Alarm RAT Sensor Fault"},
|
||||
{DI, 1250, 0, "Alarm Filter DP Sensor Fault"},
|
||||
{DI, 51, 0, "Alarm Flooding"},
|
||||
{DI, 1096, 0, "Alarm Dirty Filter"},
|
||||
{DI, 1367, 0, "Alarm High RAT"},
|
||||
{DI, 1099, 0, "Alarm Low RAT"},
|
||||
{DI, 118, 0, "Alarm High SAT"},
|
||||
{DI, 122, 0, "Alarm Low SAT"},
|
||||
{DI, 1307, 0, "Alarm High RAH"},
|
||||
{DI, 1308, 0, "Alarm Low RAH"},
|
||||
{DI, 1342, 0, "Alarm Common"},
|
||||
{DI, 148, 0, "Alarm Phase Failure"},
|
||||
{DI, 1370, 0, "Alarm Condensate Pump"},
|
||||
{DI, 1368, 0, "Alarm Smoke"},
|
||||
{DI, 1369, 0, "Alarm Fire"},
|
||||
{DI, 131, 0, "Alarm EC Fan #1"},
|
||||
{DI, 132, 0, "Alarm EC Fan #2"},
|
||||
{DI, 133, 0, "Alarm EC Fan #3"},
|
||||
{DI, 134, 0, "Alarm EC Fan #4"},
|
||||
{DI, 135, 0, "Alarm EC Fan #5"},
|
||||
{DI, 136, 0, "Alarm EC Fan #6"},
|
||||
{DI, 1360, 0, "Alarm EC Fan #7"},
|
||||
{DI, 1361, 0, "Alarm EC Fan #8"},
|
||||
{DI, 1362, 0, "Alarm EC Fan #9"},
|
||||
{DI, 138, 0, "Run Status EC Fan #1"},
|
||||
{DI, 139, 0, "Run Status EC Fan #2"},
|
||||
{DI, 140, 0, "Run Status EC Fan #3"},
|
||||
{DI, 141, 0, "Run Status EC Fan #4"},
|
||||
{DI, 142, 0, "Run Status EC Fan #5"},
|
||||
{DI, 143, 0, "Run Status EC Fan #6"},
|
||||
{DI, 1363, 0, "Run Status EC Fan #7"},
|
||||
{DI, 1364, 0, "Run Status EC Fan #8"},
|
||||
{DI, 1365, 0, "Run Status EC Fan #9"},
|
||||
{IR_FLOAT, 99, 0, "SAT Reading"},
|
||||
{IR_FLOAT, 70, 0, "RAH Reading"},
|
||||
{IR_FLOAT, 101, 0, "RAT Reading"},
|
||||
{IR_FLOAT, 106, 0, "Filter DP Reading"},
|
||||
{IR_FLOAT, 496, 0, "CW Valve Position"},
|
||||
{IR, 53, 0, "Speed EC Fan #1"},
|
||||
{IR, 228, 0, "Speed EC Fan #2"},
|
||||
{IR, 229, 0, "Speed EC Fan #3"},
|
||||
{IR, 230, 0, "Speed EC Fan #4"},
|
||||
{IR, 231, 0, "Speed EC Fan #5"},
|
||||
{IR, 232, 0, "Speed EC Fan #6"},
|
||||
{IR, 678, 0, "Speed EC Fan #7"},
|
||||
{IR, 679, 0, "Speed EC Fan #8"},
|
||||
{IR, 680, 0, "Speed EC Fan #9"},
|
||||
{IR, 274, 0, "Operating Hours EC Fan #1"},
|
||||
{IR, 233, 0, "Operating Hours EC Fan #2"},
|
||||
{IR, 244, 0, "Operating Hours EC Fan #3"},
|
||||
{IR, 235, 0, "Operating Hours EC Fan #4"},
|
||||
{IR, 236, 0, "Operating Hours EC Fan #5"},
|
||||
{IR, 245, 0, "Operating Hours EC Fan #6"},
|
||||
{IR, 486, 0, "Operating Hours EC Fan #7"},
|
||||
{IR, 487, 0, "Operating Hours EC Fan #8"},
|
||||
{IR, 488, 0, "Operating Hours EC Fan #9"},
|
||||
{COIL, 301, 0, "ON/OFF Command By BMS"},
|
||||
{COIL, 302, 0, "Enable Off By Supervisory"},
|
||||
{HR, 13, 0, "Delta"},
|
||||
{HR, 14, 0, "State Control"}, //Internal to control from Modscan
|
||||
{HR, 15, 0, "Fault Code"},
|
||||
{HR_FLOAT, 17, 0, "RAT"}, //Internal Fault code from Modscan
|
||||
{HR_FLOAT, 0, 0, "SAT Setpoint"},
|
||||
{HR_FLOAT, 680, 0, "RAT Setpoint"},
|
||||
{HR_FLOAT, 110, 0, "High RAT Limit"},
|
||||
{HR_FLOAT, 113, 0, "Low RAT Limit"},
|
||||
{HR_FLOAT, 117, 0, "High SAT Limit"},
|
||||
{HR_FLOAT, 121, 0, "Low SAT Limit"},
|
||||
{HR_FLOAT, 684, 0, "High RAH Limit"},
|
||||
{HR_FLOAT, 688, 0, "Low RAH Limit"},
|
||||
{HR, 4, 0, "Setting the EC Fan Max Speed"},
|
||||
{HR, 694, 0, "Setting the EC Fan Min Speed"},
|
||||
{HR_FLOAT, 692, 0, "Setting Room Temp"},
|
||||
{HR_FLOAT, 690, 0, "Setting EC Fan Speed"},
|
||||
{DI, 145, 0, "Alarm SAT Sensor Fault"},
|
||||
{DI, 1245, 0, "Alarm RAH Sensor Fault"},
|
||||
{DI, 1244, 0, "Alarm RAT Sensor Fault"},
|
||||
{DI, 1249, 0, "Alarm Filter DP Sensor Fault"},
|
||||
{DI, 50, 0, "Alarm Flooding"},
|
||||
{DI, 1095, 0, "Alarm Dirty Filter"},
|
||||
{DI, 1366, 0, "Alarm High RAT"},
|
||||
{DI, 1098, 0, "Alarm Low RAT"},
|
||||
{DI, 117, 0, "Alarm High SAT"},
|
||||
{DI, 121, 0, "Alarm Low SAT"},
|
||||
{DI, 1306, 0, "Alarm High RAH"},
|
||||
{DI, 1307, 0, "Alarm Low RAH"},
|
||||
{DI, 1341, 0, "Alarm Common"},
|
||||
{DI, 147, 0, "Alarm Phase Failure"},
|
||||
{DI, 1369, 0, "Alarm Condensate Pump"},
|
||||
{DI, 1367, 0, "Alarm Smoke"},
|
||||
{DI, 1368, 0, "Alarm Fire"},
|
||||
{DI, 130, 0, "Alarm EC Fan #1"},
|
||||
{DI, 131, 0, "Alarm EC Fan #2"},
|
||||
{DI, 132, 0, "Alarm EC Fan #3"},
|
||||
{DI, 133, 0, "Alarm EC Fan #4"},
|
||||
{DI, 134, 0, "Alarm EC Fan #5"},
|
||||
{DI, 135, 0, "Alarm EC Fan #6"},
|
||||
{DI, 1359, 0, "Alarm EC Fan #7"},
|
||||
{DI, 1360, 0, "Alarm EC Fan #8"},
|
||||
{DI, 1361, 0, "Alarm EC Fan #9"},
|
||||
{DI, 137, 0, "Run Status EC Fan #1"},
|
||||
{DI, 138, 0, "Run Status EC Fan #2"},
|
||||
{DI, 139, 0, "Run Status EC Fan #3"},
|
||||
{DI, 140, 0, "Run Status EC Fan #4"},
|
||||
{DI, 141, 0, "Run Status EC Fan #5"},
|
||||
{DI, 142, 0, "Run Status EC Fan #6"},
|
||||
{DI, 1362, 0, "Run Status EC Fan #7"},
|
||||
{DI, 1363, 0, "Run Status EC Fan #8"},
|
||||
{DI, 1364, 0, "Run Status EC Fan #9"},
|
||||
{IR_FLOAT, 98, 0, "SAT Reading"},
|
||||
{IR_FLOAT, 69, 0, "RAH Reading"},
|
||||
{IR_FLOAT, 100, 0, "RAT Reading"},
|
||||
{IR_FLOAT, 105, 0, "Filter DP Reading"},
|
||||
{IR_FLOAT, 495, 0, "CW Valve Position"},
|
||||
{IR, 52, 0, "Speed EC Fan #1"},
|
||||
{IR, 227, 0, "Speed EC Fan #2"},
|
||||
{IR, 228, 0, "Speed EC Fan #3"},
|
||||
{IR, 229, 0, "Speed EC Fan #4"},
|
||||
{IR, 230, 0, "Speed EC Fan #5"},
|
||||
{IR, 231, 0, "Speed EC Fan #6"},
|
||||
{IR, 677, 0, "Speed EC Fan #7"},
|
||||
{IR, 678, 0, "Speed EC Fan #8"},
|
||||
{IR, 679, 0, "Speed EC Fan #9"},
|
||||
{IR, 273, 0, "Operating Hours EC Fan #1"},
|
||||
{IR, 232, 0, "Operating Hours EC Fan #2"},
|
||||
{IR, 243, 0, "Operating Hours EC Fan #3"},
|
||||
{IR, 234, 0, "Operating Hours EC Fan #4"},
|
||||
{IR, 235, 0, "Operating Hours EC Fan #5"},
|
||||
{IR, 244, 0, "Operating Hours EC Fan #6"},
|
||||
{IR, 485, 0, "Operating Hours EC Fan #7"},
|
||||
{IR, 486, 0, "Operating Hours EC Fan #8"},
|
||||
{IR, 487, 0, "Operating Hours EC Fan #9"},
|
||||
{COIL, 300, 0, "ON/OFF Command By BMS"},
|
||||
{COIL, 301, 0, "Enable Off By Supervisory"},
|
||||
{COIL, 264, 0, "Alarm Reset"}
|
||||
};
|
||||