Zach equipment added
This commit is contained in:
@@ -54,67 +54,18 @@
|
||||
*/
|
||||
modbusMap mb_map[] =
|
||||
{
|
||||
{HR, 100, 0, "State Control"}, //Internal to control from Modscan
|
||||
{HR, 101, 0, "Fault Code"},
|
||||
{HR_FLOAT, 102, 0, "Supply Temp"},
|
||||
{HR, 0, 0, "Chiller Local-Network"},
|
||||
{HR, 1, 0, "Chiller Enable Output"},
|
||||
{HR, 2, 0, "Run Enabled"},
|
||||
{HR, 3, 0, "Chiller Capacity Limited"},
|
||||
{HR, 4, 0, "Alm Digital Output"},
|
||||
{HR, 6, 0, "Evap Flow Switch Sts"},
|
||||
{HR, 7, 0, "Cond Flow Switch Sts"},
|
||||
{HR, 8, 0, "Chiller On-Off"},
|
||||
{HR, 9, 0, "Chiller Enable SP"},
|
||||
{HR, 10, 0, "Clear Alm"},
|
||||
{HR, 11, 0, "Chiller Mode Output"},
|
||||
{HR_10x, 12, 0, "Active SP"},
|
||||
{HR_10x, 13, 0, "Actual Capacity"},
|
||||
{HR_10x, 14, 0, "Active Capacity Limit"},
|
||||
{HR, 15, 0, "Chiller Sts"},
|
||||
{HR_10x, 16, 0, "Evap Entering Fluid Temp"},
|
||||
{HR_10x, 17, 0, "Evap Leaving Fluid Temp"},
|
||||
{HR, 18, 0, "Evap Fluid Flow Rate"},
|
||||
{HR_10x, 19, 0, "Cond Entering Fluid Temp"},
|
||||
{HR_10x, 20, 0, "Cond Leaving Fluid Temp"},
|
||||
{HR, 21, 0, "Cond Fluid Flow Rate"},
|
||||
{HR_10x, 24, 0, "Outdoor Air Temp"},
|
||||
{HR, 25, 0, "Chiller Current"},
|
||||
{HR, 27, 0, "Total Kw"},
|
||||
{HR, 28, 0, "Warning Alm Idx"},
|
||||
{HR, 29, 0, "Problem Alm Idx"},
|
||||
{HR, 30, 0, "Fault Alm Idx"},
|
||||
{HR, 31, 0, "Warning Alm Code"},
|
||||
{HR, 32, 0, "Problem Alm Code"},
|
||||
{HR, 33, 0, "Fault Alm Code"},
|
||||
{HR, 34, 0, "Chiller Mode SP"},
|
||||
{HR_10x, 35, 0, "Cool SP"},
|
||||
{HR_10x, 36, 0, "Ice SP"},
|
||||
{HR_10x, 38, 0, "Capacity Limit SP"},
|
||||
{HR_10x, 39, 0, "Cond Refrig Pressure"},
|
||||
{HR_10x, 40, 0, "Cond Saturated Refrig Temp"},
|
||||
{HR_10x, 41, 0, "Evap Refrig Pressure"},
|
||||
{HR_10x, 42, 0, "Evap Saturated Refrig Temp"},
|
||||
{HR, 65, 0, "Comp Suction Refrig Temp"},
|
||||
{HR_10x, 68, 0, "Comp Discharge Refrig Temp"},
|
||||
{HR, 69, 0, "Comp1 Percent RLA"},
|
||||
{HR, 70, 0, "Comp1 Current"},
|
||||
{HR, 71, 0, "Comp Voltage"},
|
||||
{HR, 72, 0, "Comp Power"},
|
||||
{HR, 73, 0, "Comp Starts"},
|
||||
{HR, 74, 0, "Comp Run Hours"},
|
||||
{HR, 75, 0, "Comp Run Hours"},
|
||||
{HR, 82, 0, "Comp2 Percent RLA"},
|
||||
{HR, 303, 0, "Evap Pump Run Hours"},
|
||||
{HR, 304, 0, "Evap Pump Run Hours"},
|
||||
{HR, 305, 0, "Evap Pump Sts"},
|
||||
{HR, 316, 0, "Units"},
|
||||
{HR, 317, 0, "Chiller Model"},
|
||||
{HR, 1849, 0, "Oil Feed Pessure"},
|
||||
{HR, 1854, 0, "Wtrside Econo State"},
|
||||
{HR, 1855, 0, "Wtrside Econo En SP"},
|
||||
|
||||
};
|
||||
{COIL, 0, 0, "Coil"},
|
||||
{DI, 1, 0, "Discrete input"},
|
||||
{IR, 2, 0, "Input Register 1 word"},
|
||||
{IR_10x, 3, 0, "Input Register scaled by 10"},
|
||||
{IR_FLOAT, 4, 0, "Input Register float"},
|
||||
{IR_LONG, 6, 0, "Input Register 2 word"},
|
||||
{HR, 8, 0, "Holding Register 1 word"},
|
||||
{HR_10x, 8, 0, "Holding Register scaled by 10"},
|
||||
{HR_FLOAT, 10, 0, "Holding Register float"},
|
||||
{HR_LONG, 12, 0, "Holding Register 2 word"},
|
||||
};
|
||||
|
||||
//Size of modbus map used in FOR cycles, automatically calculated.
|
||||
/**
|
||||
* @brief The total number of entries in the `mb_map` array.
|
||||
|
||||
Reference in New Issue
Block a user