Added alarm setpoints

Added alarm setpoint registers, adjusted individual fan speed --> RPM, ensured Fan Speed Feedback (40029) --> 0 in Standby/Fail mode.
This commit is contained in:
RobertJDavis
2025-12-01 16:08:34 -07:00
parent 5259754a66
commit 245d01ed61
5 changed files with 44 additions and 34 deletions

View File

@@ -138,8 +138,15 @@ modbusMap mb_map[] =
{IR_FLOAT, 79, 0, "Amps Fan 9"},
{IR_FLOAT, 99, 0, "CRAH Heartbeat"},
{HR_FLOAT, 1, 0, "High Return Air Temp Setpoint"}, // default: 100, set locally on unit
{HR_FLOAT, 3, 0, "Low Return Air Temp Setpoint"}, // default: 72, set locally on unit
{HR_FLOAT, 5, 0, "High Supply Air Temp Setpoint"}, // default: 78, set locally on unit
{HR_FLOAT, 7, 0, "Low Return Air Temp Setpoint"}, // default: 72, set locally on unit
{HR_FLOAT, 9, 0, "High Return Humidity Setpoint"}, // default: 60, set locally on unit
{HR_FLOAT, 11, 0, "Low Return Humidity Setpoint"}, // default: 20, set locally on unit
{HR_FLOAT, 13, 0, "Fan Speed Setpoint"}, // Receive signal from PLC
{HR_FLOAT, 17, 0, "Supply Air Temp Setpoint"}, // Receive signal from PLC
{HR_FLOAT, 19, 0, "Return Air Temp Setpoint"}, // set locally on unit
{HR_FLOAT, 21, 0, "Fan Min Speed"}, // Send to PLC
{HR_FLOAT, 23, 0, "Fan Max Speed"}, // Send to PLC
{HR, 25, 0, "BMS Control Source"}, // Receive signal from PLC 0:Speed, 1:Room Temp