Merge branch 'develop' into rdavis/HUM_DriSteem_RTS_RX36_TCP
This commit is contained in:
@@ -1,16 +1,12 @@
|
||||
# CHILLER YORK YVAA 0428IOK46BAVTXX TCP
|
||||
|
||||
## Brief Introduction
|
||||
|
||||
*** NOTE! ***
|
||||
This code has not been verified with Chiller and Chiller Manager PLC program.
|
||||
It is a best-guess based on a preliminary review of Chiller PLC program, but
|
||||
has yet to be fully vetted and local tested with PLC programs.
|
||||
|
||||
Chiller receives Temp SP and Enable from PLC (Modscan)
|
||||
Alarms are also simulated via Modscan, though those signals will be internal to Chiller
|
||||
Many hard IO points are simulated using Modscan.
|
||||
Assumes all Modbus points are for monitoring only and go to Ignition - not sent to PLC
|
||||
Chiller receives Chiller Temp SP and Enable from PLC. The Supply Temp will ramp to Chiller Temp SP in Run Mode.
|
||||
Alarms are also simulated via Modscan, though those signals will be internal to Chiller.
|
||||
Hard IO points simulated with Modscan: Sys 1 Alarm, Sys 2 Alarm.
|
||||
Chiller Status is sent back to PLC.
|
||||
In practice, all Modbus points are for monitoring only and go to Ignition - not sent to PLC.
|
||||
For the sake of simulation, some hard IO points (simulated as Modbus points) will go back to PLC for feedback or will be sent from PLC to Arduino.
|
||||
|
||||
## List of Equipment
|
||||
This cofiguration has been used for these models:
|
||||
@@ -24,20 +20,51 @@ The code is written for an ESP8266/ESP32-style microcontroller with WiFi capabil
|
||||
---
|
||||
|
||||
## States and Strategies
|
||||
Updates Alarms States. If any active alarms --> FailState
|
||||
Updates Alarms States. Only the Sys 1 Fan Fault or Sys 2 Fan Fault will send unit --> FailState
|
||||
Sys 1 Alarm, Sys 2 Alarm, and General Alarm will annunciate only, will not stop the unit (this is an assumption the program follows, may differ in field).
|
||||
Updates Free Cooling Mode: Free Cooling Mode is activated using a coil, for simulation purposes only.
|
||||
Modbus points are simulated, mostly with a SingleValue strategy for image verification in Ignition.
|
||||
While in RunningState, the Supply Temp dynamically ramps to the Supply Temp SP sent from PLC (Modscan)
|
||||
While in RunningState, the Supply Temp dynamically ramps to the Supply Temp SP sent from PLC (or Modscan)
|
||||
The CHW In and CHW Out temperature values also dynamically ramp to match the Return and Supply Temps.
|
||||
|
||||
### Standby State
|
||||
* **Chiller Status**: set to 0
|
||||
* **Operational Code**: set to 77
|
||||
* **Chiller Start Command**: set to 0
|
||||
Supply Temp = 80 +/- 1
|
||||
Return Temp = 80 +/- 1
|
||||
System CHW Out = 80 +/- 1
|
||||
System CHW In = 80 +/- 1
|
||||
Ambient Temp = 1-- +/- 1
|
||||
Sys 1, 2 Oil Pressure = 420 +/- 1
|
||||
Sys 1, 2 Suction Pressure = 70 +/- 1
|
||||
Sys 1, 2 Discharge Pressure = 70 +/- 1
|
||||
Sys 1, 2 Condenser Temp = 124 +/- 1
|
||||
|
||||
### Running State
|
||||
* **Chiller status**: set to 1
|
||||
* **Supply Temperature**: **Ramp Strategy** ramps to Temp Setpoint from PLC (Modscan)
|
||||
* **Operational Code**: set to 78 (running)
|
||||
* **Supply Temperature**: **Ramp Strategy** ramps to Chiller Temp Setpoint from PLC (Modscan)
|
||||
Supply Temp dynamically ramps to Chiller Temp Setpoint as sent from PLC (or Modscan)
|
||||
Return Temp sawStrategy (79-83)
|
||||
System CHW Out dynamically ramps to follow Supply Temp
|
||||
System CHW In dynamically ramps to follow Return Temp
|
||||
Ambient Temp = 1-- +/- 1
|
||||
Sys 1, 2 Oil Pressure = 450 +/- 5
|
||||
Sys 1, 2 Suction Pressure = 70 +/- 2
|
||||
Sys 1, 2 Discharge Pressure = 375 +/- 4
|
||||
Sys 1, 2 Compressor Pct FLA = 93 +/- 2
|
||||
Sys 1, 2 Condenser Temp = 125 +/- 5
|
||||
Sys 1 Fan kW = 35 +/- 2
|
||||
Sys 2 Fan kW = 23 +/- 2
|
||||
Sys 1 Compressor kW = 304 +/- 5
|
||||
Sys 2 Compressor kW = 198 +/- 5
|
||||
|
||||
### Fail State
|
||||
* **Chiller Status**: set to 0
|
||||
All values match that of Standby State.
|
||||
The difference is in Fail State, if a Start Command is sent it will not start the Chiller.
|
||||
All faults must be cleared, then unit transitions to Standby State.
|
||||
* **Chiller Status**: set to 0
|
||||
* **Operational Code**: set to 77
|
||||
* **Chiller Start Command**: set to 0
|
||||
All analog values same as in Standby State
|
||||
@@ -32,13 +32,15 @@
|
||||
* @brief Updates Alarms states
|
||||
*
|
||||
* This function will update the Alarm status DI bits according to the Alarm Commands from Coils (Modscan)
|
||||
* The appropriate Fault Code will also be set to 56 (Condenser Fan VSD Warning)
|
||||
* The appropriate Fault Code will also be set to 56 (Condenser Fan VSD Warning).
|
||||
* Also updates the General Alarm bit. If any alarms are active, General Alarm --> 1, else 0.
|
||||
*
|
||||
* This is a function used in the update() of the Standby, Running, and Fail States.
|
||||
*
|
||||
*/
|
||||
|
||||
void updateAlarms(Equipment<ModbusRTU>* equipment){
|
||||
// Updates Sys 1, 2 Fan Fault Alarms with associated Fault Code
|
||||
Modbus_Point<ModbusRTU>* Sys1FanAlarmCommand = equipment->getModbus_Point("Sys 1 Fan Fault ON");
|
||||
Modbus_Point<ModbusRTU>* Sys2FanAlarmCommand = equipment->getModbus_Point("Sys 2 Fan Fault ON");
|
||||
Modbus_Point<ModbusRTU>* Sys1FanAlarm = equipment->getModbus_Point("Sys 1 Fan Fault Alarm");
|
||||
@@ -57,6 +59,20 @@ void updateAlarms(Equipment<ModbusRTU>* equipment){
|
||||
}
|
||||
else equipment->setModbus_Point("Sys 2 Fault Code", 0);
|
||||
}
|
||||
|
||||
// Update General Alarm (if any Alarm is active, make general alarm active)
|
||||
const std::vector<std::string> alarmDescriptions = {
|
||||
"Sys 1 Alarm", "Sys 2 Alarm", "Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm"
|
||||
};
|
||||
int numAlarms = 0;
|
||||
for (int i =0; i < alarmDescriptions.size(); ++i) {
|
||||
Modbus_Point<ModbusRTU>* alarmPoint = equipment->getModbus_Point(alarmDescriptions[i]);
|
||||
if (alarmPoint) {
|
||||
if (alarmPoint->getValue() == 1) numAlarms++;
|
||||
}
|
||||
}
|
||||
if (numAlarms >= 1) equipment->setModbus_Point("General Alarm", 1);
|
||||
else equipment->setModbus_Point("General Alarm", 0);
|
||||
}
|
||||
|
||||
/**
|
||||
@@ -74,12 +90,6 @@ void updateFreeCooling(Equipment<ModbusRTU>* equipment){
|
||||
Modbus_Point<ModbusRTU>* FreeCoolingCommand = equipment->getModbus_Point("Free Cooling Mode ON");
|
||||
Modbus_Point<ModbusRTU>* FreeCoolingMode = equipment->getModbus_Point("Free Cooling Mode");
|
||||
Modbus_Point<ModbusRTU>* FreeCoolingValve = equipment->getModbus_Point("Free Cooling Valve");
|
||||
if (FreeCoolingCommand->getValue() == 1) {
|
||||
FreeCoolingMode->setValue(1);
|
||||
FreeCoolingValve->setValue(1);
|
||||
}
|
||||
else {
|
||||
FreeCoolingMode->setValue(0);
|
||||
FreeCoolingValve->setValue(0);
|
||||
}
|
||||
FreeCoolingMode->setValue(FreeCoolingCommand->getValue());
|
||||
FreeCoolingValve->setValue(FreeCoolingCommand->getValue());
|
||||
}
|
||||
@@ -6,6 +6,7 @@
|
||||
*
|
||||
* This file contains the implementation for the FailState, which defines
|
||||
* the behavior of the equipment when it has entered a fault condition.
|
||||
* The unit enters Fail State if Sys 1 Fan Fault Alarm or Sys 2 Fan Fault Alarm is active.
|
||||
*/
|
||||
#include "ModbusPoints/Modbus_Point.h"
|
||||
#include "Equipment/Equipment.h"
|
||||
@@ -29,15 +30,31 @@
|
||||
* @brief Constructs a new FailState object.
|
||||
*
|
||||
* This constructor receives a list of alarm descriptions and creates strategies
|
||||
* to set the Compressor and Fan kW to 0.
|
||||
* to set the unit back into an idle, de-energized state.
|
||||
*
|
||||
* @param activeAlarms A vector of strings, where each string is the
|
||||
* description of a Modbus point to be set as an active alarm.
|
||||
* @param activeFaults A vector of strings, where each string is the
|
||||
* description of the currently active faults.
|
||||
*/
|
||||
template<>
|
||||
FailState<ModbusRTU>::FailState(const std::vector<std::string>& activeAlarms) {
|
||||
FailState<ModbusRTU>::FailState(const std::vector<std::string>& activeFaults) {
|
||||
addStrategy("Supply Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("Return Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("Ambient Temp", new SingleValueStrategy(100.0f, 1.0f, 1000));
|
||||
|
||||
addStrategy("System CHW Out", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("System CHW In", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Condenser Temp", new SingleValueStrategy(124.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 2 Condenser Temp", new SingleValueStrategy(124.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Oil Pressure", new SingleValueStrategy(420.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 2 Oil Pressure", new SingleValueStrategy(420.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Suction Pressure", new SingleValueStrategy(70.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 2 Suction Pressure", new SingleValueStrategy(70.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Discharge Pressure", new SingleValueStrategy(70.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 2 Discharge Pressure", new SingleValueStrategy(70.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Compressor Pct FLA", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 2 Compressor Pct FLA", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Local Leaving Temp Setpoint", new SingleValueStrategy(70.0f, 0.0f, 1000));
|
||||
addStrategy("VSD Output Frequency", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 1 Fan KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 2 Fan KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 1 Compressor KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
@@ -48,33 +65,44 @@ FailState<ModbusRTU>::FailState(const std::vector<std::string>& activeAlarms) {
|
||||
* @brief Executes the fail state's logic for one update cycle.
|
||||
*
|
||||
* This method first updates all alarms states and Free Cooling Mode (for ease of testing).
|
||||
* If all alarms have been cleared --> StandbyState.
|
||||
* If alarms are still active, ensures the Chiller Start Command remains at 0.
|
||||
* If all faults have been cleared --> StandbyState.
|
||||
* If faults are still active, ensures the Chiller Start Command remains at 0.
|
||||
*
|
||||
* @param equipment Pointer to the Equipment instance.
|
||||
* @return A pointer to a new State if a transition should occur, otherwise nullptr.
|
||||
*/
|
||||
template<>
|
||||
State<ModbusRTU>* FailState<ModbusRTU>::update(Equipment<ModbusRTU>* equipment) {
|
||||
// Update alarms states, Free Cooling mode, Freeze Protection Mode
|
||||
// Update alarms states, Free Cooling mode
|
||||
updateAlarms(equipment);
|
||||
updateFreeCooling(equipment);
|
||||
|
||||
const std::vector<std::string> alarmDescriptions = {
|
||||
"Sys 1 Alarm", "Sys 2 Alarm", "Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm",
|
||||
const std::vector<std::string> FaultDescriptions = {
|
||||
"Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm",
|
||||
};
|
||||
|
||||
// If no alarms active --> send to StandbyState()
|
||||
bool alarms_active = false;
|
||||
for (const auto& desc : alarmDescriptions) {
|
||||
// If no faults active --> send to StandbyState()
|
||||
bool faults_active = false;
|
||||
for (const auto& desc : FaultDescriptions) {
|
||||
Modbus_Point<ModbusRTU>* point = equipment->getModbus_Point(desc);
|
||||
if (point->getValue() == 1) {
|
||||
alarms_active = true;
|
||||
faults_active = true;
|
||||
}
|
||||
}
|
||||
if (!alarms_active) return new StandbyState<ModbusRTU>();
|
||||
if (!faults_active) return new StandbyState<ModbusRTU>();
|
||||
|
||||
setPointValue(equipment, "Chiller Start Command", 0);
|
||||
|
||||
// Update Operational Code depending on Free Cooling Mode
|
||||
int freeCoolingState = getPointValue(equipment, "Free Cooling Mode ON");
|
||||
if (freeCoolingState == 1){
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 82);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 82);
|
||||
}
|
||||
else{
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 77);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 77);
|
||||
}
|
||||
|
||||
_applyStrategies(equipment);
|
||||
return nullptr;
|
||||
|
||||
@@ -60,11 +60,11 @@ RunningState<ModbusRTU>::RunningState() {
|
||||
addStrategy("Sys 1 Run Hours", new TotalizerStrategy(1000));
|
||||
addStrategy("Sys 2 Run Hours", new TotalizerStrategy(1000));
|
||||
addStrategy("Local Leaving Temp Setpoint", new SingleValueStrategy(70.0f, 0.0f, 1000));
|
||||
addStrategy("VSD Output Frequency", new SingleValueStrategy(59.0f, 1.0f, 1000));
|
||||
addStrategy("Sys 1 Fan KW", new SingleValueStrategy(35.0f, 2.0f, 1000));
|
||||
addStrategy("Sys 2 Fan KW", new SingleValueStrategy(23.0f, 2.0f, 1000));
|
||||
addStrategy("Sys 1 Compressor KW", new SingleValueStrategy(304.0f, 5.0f, 1000));
|
||||
addStrategy("Sys 2 Compressor KW", new SingleValueStrategy(198.0f, 5.0f, 1000));
|
||||
|
||||
}
|
||||
|
||||
/**
|
||||
@@ -88,23 +88,23 @@ State<ModbusRTU>* RunningState<ModbusRTU>::update(Equipment<ModbusRTU>* equipmen
|
||||
updateAlarms(equipment);
|
||||
updateFreeCooling(equipment);
|
||||
|
||||
std::vector<std::string> activeAlarmsDescriptions = {};
|
||||
const std::vector<std::string> alarmDescriptions = {
|
||||
"Sys 1 Alarm", "Sys 2 Alarm", "Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm",
|
||||
std::vector<std::string> activeFaultDescriptions = {};
|
||||
const std::vector<std::string> FaultDescriptions = {
|
||||
"Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm"
|
||||
};
|
||||
|
||||
// Loop through alarms, create array of active alarms and send to FailState if any alarms are active
|
||||
bool alarms_active = false;
|
||||
for (const auto& desc : alarmDescriptions) {
|
||||
// Loop through faults, create array of active faults and send to FailState if any faults are active
|
||||
bool faults_active = false;
|
||||
for (const auto& desc : FaultDescriptions) {
|
||||
Modbus_Point<ModbusRTU>* point = equipment->getModbus_Point(desc);
|
||||
if (point->getValue() == 1) {
|
||||
activeAlarmsDescriptions.push_back(desc);
|
||||
alarms_active = true;
|
||||
activeFaultDescriptions.push_back(desc);
|
||||
faults_active = true;
|
||||
}
|
||||
}
|
||||
if (alarms_active) return new FailState<ModbusRTU>(activeAlarmsDescriptions);
|
||||
if (faults_active) return new FailState<ModbusRTU>(activeFaultDescriptions);
|
||||
|
||||
// If no alarms active and Start Command = 0--> send to StandbyState()
|
||||
// If no faults active and Start Command = 0--> send to StandbyState()
|
||||
int Chiller_Enable = getPointValue(equipment, "Chiller Start Command"); // Modscan COIL 1
|
||||
if (Chiller_Enable == 0){
|
||||
return new StandbyState<ModbusRTU>();
|
||||
@@ -124,6 +124,17 @@ State<ModbusRTU>* RunningState<ModbusRTU>::update(Equipment<ModbusRTU>* equipmen
|
||||
static_cast<RampStrategy*>(CHW_In_strat)->setTarget(returnTemp);
|
||||
}
|
||||
|
||||
// Update Operational Code depending on Free Cooling Mode
|
||||
int freeCoolingState = getPointValue(equipment, "Free Cooling Mode ON");
|
||||
if (freeCoolingState == 1){
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 82);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 82);
|
||||
}
|
||||
else{
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 78);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 78);
|
||||
}
|
||||
|
||||
// Apply any strategies defined for the standby state
|
||||
_applyStrategies(equipment);
|
||||
return nullptr;
|
||||
|
||||
@@ -55,6 +55,7 @@ StandbyState<ModbusRTU>::StandbyState() {
|
||||
addStrategy("Sys 1 Compressor Pct FLA", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 2 Compressor Pct FLA", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Local Leaving Temp Setpoint", new SingleValueStrategy(70.0f, 0.0f, 1000));
|
||||
addStrategy("VSD Output Frequency", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 1 Fan KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 2 Fan KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
addStrategy("Sys 1 Compressor KW", new SingleValueStrategy(0.0f, 0.0f, 1000));
|
||||
@@ -82,7 +83,7 @@ State<ModbusRTU>* StandbyState<ModbusRTU>::update(Equipment<ModbusRTU>* equipmen
|
||||
|
||||
std::vector<std::string> activeAlarmsDescriptions = {};
|
||||
const std::vector<std::string> alarmDescriptions = {
|
||||
"Sys 1 Alarm", "Sys 2 Alarm", "Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm",
|
||||
"Sys 1 Fan Fault Alarm", "Sys 2 Fan Fault Alarm"
|
||||
};
|
||||
|
||||
// Loop through alarms, create array of active alarms and send to FailState if any alarms are active
|
||||
@@ -102,6 +103,17 @@ State<ModbusRTU>* StandbyState<ModbusRTU>::update(Equipment<ModbusRTU>* equipmen
|
||||
return new RunningState<ModbusRTU>();
|
||||
}
|
||||
|
||||
// Update Operational Code depending on Free Cooling Mode
|
||||
int freeCoolingState = getPointValue(equipment, "Free Cooling Mode ON");
|
||||
if (freeCoolingState == 1){
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 82);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 82);
|
||||
}
|
||||
else{
|
||||
setPointValue(equipment, "Sys 1 Operational Code", 77);
|
||||
setPointValue(equipment, "Sys 2 Operational Code", 77);
|
||||
}
|
||||
|
||||
// Apply any strategies defined for the standby state
|
||||
_applyStrategies(equipment);
|
||||
return nullptr;
|
||||
|
||||
@@ -54,54 +54,58 @@
|
||||
*/
|
||||
modbusMap mb_map[] =
|
||||
{
|
||||
{COIL, 0, 0, "Chiller Start Command"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{COIL, 1, 0, "Sys 1 Alarm"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{COIL, 2, 0, "Sys 2 Alarm"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{COIL, 3, 0, "Sys 1 Fan Fault ON"}, // Use in Modscan - Used for Arduino simulation only
|
||||
{COIL, 4, 0, "Sys 2 Fan Fault ON"}, // Use in Modscan - Used for Arduino simulation only
|
||||
{COIL, 5, 0, "Free Cooling Mode ON"}, // Use in Modscan - Used for Arduino simulation only
|
||||
{COIL, 0, 0, "Chiller Start Command"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only. Signal should come from PLC.
|
||||
{COIL, 1, 0, "Sys 1 Alarm"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only --> INDICATION ONLY (assumption)
|
||||
{COIL, 2, 0, "Sys 2 Alarm"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only --> INDICATION ONLY (assumption)
|
||||
{COIL, 3, 0, "Sys 1 Fan Fault ON"}, // Use in Modscan - Used for Arduino simulation only --> FAILSTATE (assumption)
|
||||
{COIL, 4, 0, "Sys 2 Fan Fault ON"}, // Use in Modscan - Used for Arduino simulation only --> FAILSTATE (assumption)
|
||||
{COIL, 5, 0, "Free Cooling Mode ON"}, // Use in Modscan - Used for Arduino simulation only
|
||||
|
||||
{DI, 0, 0, "Sys 1 Fan Fault Alarm"},
|
||||
{DI, 1, 0, "Sys 2 Fan Fault Alarm"},
|
||||
{DI, 65, 0, "General Alarm"}, // if any alarm is active, General Alarm = 1 --> used for INDICATION ONLY (assumption)
|
||||
{DI, 174, 0, "Sys 1 Fan Fault Alarm"},
|
||||
{DI, 175, 0, "Sys 2 Fan Fault Alarm"},
|
||||
|
||||
{HR, 0, 0, "Chiller Status"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{HR, 1, 0, "Chiller Temp Setpoint"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{HR, 2, 0, "Supply Temp"}, // Use in Modscan - Hard IO in SCP (PICS?), Used for Arduino simulation only
|
||||
{HR, 3, 0, "Return Temp"}, // Use in Modscan - Hard IO in SCP (PICS?), Used for Arduino simulation only
|
||||
{IR, 130, 0, "Free Cooling Mode"},
|
||||
{IR, 165, 0, "Free Cooling Valve"},
|
||||
|
||||
{HR, 4, 70, "System CHW Out"},
|
||||
{HR, 5, 70, "System CHW In"},
|
||||
{HR, 7, 0, "Sys 1 Condenser Temp"},
|
||||
{HR, 9, 0, "Ambient Temp"},
|
||||
{HR, 0, 0, "Chiller Status"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{HR, 1, 0, "Chiller Temp Setpoint"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{HR, 2, 0, "Supply Temp"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
{HR, 3, 0, "Return Temp"}, // Use in Modscan - Hard IO in SCP, Used for Arduino simulation only
|
||||
|
||||
{HR, 11, 0, "Sys 1 Oil Pressure"},
|
||||
{HR, 12, 0, "Sys 1 Suction Pressure"},
|
||||
{HR, 13, 0, "Sys 1 Discharge Pressure"},
|
||||
{HR, 14, 0, "Sys 1 Compressor Pct FLA"},
|
||||
{HR, 15, 0, "Sys 1 Run Hours"},
|
||||
{HR, 16, 0, "Sys 1 Starts"},
|
||||
{HR, 4, 70, "System CHW Out"},
|
||||
{HR, 5, 70, "System CHW In"},
|
||||
{HR_10x, 7, 0, "Sys 1 Condenser Temp"},
|
||||
{HR_10x, 9, 0, "Ambient Temp"},
|
||||
|
||||
{HR_10x, 11, 0, "Sys 1 Oil Pressure"},
|
||||
{HR_10x, 12, 0, "Sys 1 Suction Pressure"},
|
||||
{HR_10x, 13, 0, "Sys 1 Discharge Pressure"},
|
||||
{HR_10x, 14, 0, "Sys 1 Compressor Pct FLA"},
|
||||
{HR, 15, 0, "Sys 1 Run Hours"},
|
||||
{HR, 16, 0, "Sys 1 Starts"},
|
||||
|
||||
{HR, 20, 0, "Sys 2 Oil Pressure"},
|
||||
{HR, 21, 0, "Sys 2 Suction Pressure"},
|
||||
{HR, 22, 0, "Sys 2 Discharge Pressure"},
|
||||
{HR, 23, 0, "Sys 2 Compressor Pct FLA"},
|
||||
{HR, 24, 0, "Sys 2 Run Hours"},
|
||||
{HR, 25, 0, "Sys 2 Starts"},
|
||||
{HR_10x, 20, 0, "Sys 2 Oil Pressure"},
|
||||
{HR_10x, 21, 0, "Sys 2 Suction Pressure"},
|
||||
{HR_10x, 22, 0, "Sys 2 Discharge Pressure"},
|
||||
{HR_10x, 23, 0, "Sys 2 Compressor Pct FLA"},
|
||||
{HR, 24, 0, "Sys 2 Run Hours"},
|
||||
{HR, 25, 0, "Sys 2 Starts"},
|
||||
|
||||
{HR, 29, 77, "Sys 1 Operational Code"},
|
||||
{HR, 30, 0, "Sys 1 Fault Code"},
|
||||
{HR, 31, 77, "Sys 2 Operational Code"},
|
||||
{HR, 32, 0, "Sys 2 Fault Code"},
|
||||
{HR_10x, 26, 0, "VSD Output Frequency"},
|
||||
|
||||
{HR, 39, 0, "Local Leaving Temp Setpoint"},
|
||||
{HR, 29, 77, "Sys 1 Operational Code"}, // 77:not running, 78:running, 82:free cooling
|
||||
{HR, 30, 0, "Sys 1 Fault Code"}, // 56:condenser fan VSD warning
|
||||
{HR, 31, 77, "Sys 2 Operational Code"}, // 77:not running, 78:running, 82:free cooling
|
||||
{HR, 32, 0, "Sys 2 Fault Code"}, // 56:condenser fan VSD warning
|
||||
|
||||
{HR, 40, 0, "Sys 1 Fan KW"},
|
||||
{HR, 41, 0, "Sys 1 Compressor KW"},
|
||||
{HR, 42, 0, "Sys 2 Fan KW"},
|
||||
{HR, 43, 0, "Sys 2 Compressor KW"},
|
||||
{HR, 49, 0, "Sys 2 Condenser Temp"},
|
||||
{HR, 50, 0, "Free Cooling Mode"},
|
||||
{HR, 51, 0, "Free Cooling Valve"},
|
||||
{HR, 39, 0, "Local Leaving Temp Setpoint"},
|
||||
|
||||
{HR_10x, 49, 0, "Sys 2 Condenser Temp"},
|
||||
{HR_10x, 140, 0, "Sys 1 Fan KW"},
|
||||
{HR_10x, 141, 0, "Sys 1 Compressor KW"},
|
||||
{HR_10x, 142, 0, "Sys 2 Fan KW"},
|
||||
{HR_10x, 143, 0, "Sys 2 Compressor KW"},
|
||||
|
||||
};
|
||||
//Size of modbus map used in FOR cycles, automatically calculated.
|
||||
|
||||
@@ -1,11 +1,11 @@
|
||||
/**
|
||||
* @file main.cpp
|
||||
* @brief Main execution program for the Daikin Chiller (RTU) Emulator.
|
||||
* @author Emmanuel Hernandez Cruz
|
||||
* @brief Main execution program for the York YVAA Chiller (RTU) Emulator.
|
||||
* @author Emmanuel Hernandez Cruz, Robert J. Davis
|
||||
* @date 2025-09-02
|
||||
*
|
||||
* @details This file contains the main execution program for an Arduino-based
|
||||
* emulator of a Daikin Chiller unit. The program communicates via the
|
||||
* emulator of a York YVAA Chiller unit. The program communicates via the
|
||||
* Modbus RTU protocol over a serial connection.
|
||||
*
|
||||
* The setup() function initializes the following:
|
||||
|
||||
@@ -38,16 +38,26 @@
|
||||
*/
|
||||
template<>
|
||||
RunningState<ModbusIP>::RunningState() {
|
||||
addStrategy("CW Valve Position", new PIDStrategy("RAT Setpoint", 1000, "RAT"));
|
||||
addStrategy("Operating Hours EC Fan #1", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #2", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #3", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #4", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #5", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #6", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #7", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #8", new TotalizerStrategy(10000));
|
||||
addStrategy("Operating Hours EC Fan #9", new TotalizerStrategy(10000));
|
||||
addStrategy("CW Valve Position", new PIDStrategy("SAT Setpoint", 2000, "SAT Reading"));
|
||||
addStrategy("SAT Reading", new SingleValueStrategy(0.0f, 3.0f, 1000));
|
||||
addStrategy("Speed EC Fan #1", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #2", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #3", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #4", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #5", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #6", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #7", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #8", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Speed EC Fan #9", new RampStrategy(0.0f, 500.0f, 1000));
|
||||
addStrategy("Operating Hours EC Fan #1", new TotalizerStrategy(1100));
|
||||
addStrategy("Operating Hours EC Fan #2", new TotalizerStrategy(1200));
|
||||
addStrategy("Operating Hours EC Fan #3", new TotalizerStrategy(1300));
|
||||
addStrategy("Operating Hours EC Fan #4", new TotalizerStrategy(1250));
|
||||
addStrategy("Operating Hours EC Fan #5", new TotalizerStrategy(1350));
|
||||
addStrategy("Operating Hours EC Fan #6", new TotalizerStrategy(1450));
|
||||
addStrategy("Operating Hours EC Fan #7", new TotalizerStrategy(1150));
|
||||
addStrategy("Operating Hours EC Fan #8", new TotalizerStrategy(1180));
|
||||
addStrategy("Operating Hours EC Fan #9", new TotalizerStrategy(1340));
|
||||
}
|
||||
|
||||
/**
|
||||
@@ -74,63 +84,36 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
|
||||
return new StandbyState<ModbusIP>();
|
||||
}
|
||||
|
||||
Modbus_Point<ModbusIP>* faultCode = equipment->getModbus_Point("Fault Code");
|
||||
int faultCodeValue = faultCode ? faultCode->getValue() : 0;
|
||||
switch (faultCodeValue){
|
||||
case 1:
|
||||
return new FailState<ModbusIP>({"Alarm SAT Sensor Fault"});
|
||||
case 2:
|
||||
return new FailState<ModbusIP>({"Alarm RAH Sensor Fault"});
|
||||
case 3:
|
||||
return new FailState<ModbusIP>({"Alarm RAT Sensor Fault"});
|
||||
case 4:
|
||||
return new FailState<ModbusIP>({"Alarm Filter DP Sensor Fault"});
|
||||
case 5:
|
||||
return new FailState<ModbusIP>({"Alarm Flooding"});
|
||||
case 6:
|
||||
return new FailState<ModbusIP>({"Alarm Dirty Filter"});
|
||||
case 7:
|
||||
return new FailState<ModbusIP>({"Alarm High RAT"});
|
||||
case 8:
|
||||
return new FailState<ModbusIP>({"Alarm Low RAT"});
|
||||
case 9:
|
||||
return new FailState<ModbusIP>({"Alarm High SAT"});
|
||||
case 10:
|
||||
return new FailState<ModbusIP>({"Alarm Low SAT"});
|
||||
case 11:
|
||||
return new FailState<ModbusIP>({"Alarm High RAH"});
|
||||
case 12:
|
||||
return new FailState<ModbusIP>({"Alarm Low RAH"});
|
||||
case 13:
|
||||
return new FailState<ModbusIP>({"Alarm Phase Failure"});
|
||||
case 14:
|
||||
return new FailState<ModbusIP>({"Alarm Condensate Pump"});
|
||||
case 15:
|
||||
return new FailState<ModbusIP>({"Alarm Smoke"});
|
||||
case 16:
|
||||
return new FailState<ModbusIP>({"Alarm Fire"});
|
||||
case 17:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #1"});
|
||||
case 18:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #2"});
|
||||
case 19:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #3"});
|
||||
case 20:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #4"});
|
||||
case 21:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #5"});
|
||||
case 22:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #6"});
|
||||
case 23:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #7"});
|
||||
case 24:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #8"});
|
||||
case 25:
|
||||
return new FailState<ModbusIP>({"Alarm EC Fan #9"});
|
||||
default:
|
||||
break;
|
||||
}
|
||||
|
||||
float rat = getPointValue(equipment, "RAT");
|
||||
setPointValue(equipment, "RAT Reading", rat);
|
||||
float speed = getPointValue(equipment, "Setting EC Fan Speed");
|
||||
Strategy_Behavior* fan1_rs = getStrategy("Speed EC Fan #1");
|
||||
static_cast<RampStrategy*>(fan1_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan2_rs = getStrategy("Speed EC Fan #2");
|
||||
static_cast<RampStrategy*>(fan2_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan3_rs = getStrategy("Speed EC Fan #3");
|
||||
static_cast<RampStrategy*>(fan3_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan4_rs = getStrategy("Speed EC Fan #4");
|
||||
static_cast<RampStrategy*>(fan4_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan5_rs = getStrategy("Speed EC Fan #5");
|
||||
static_cast<RampStrategy*>(fan5_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan6_rs = getStrategy("Speed EC Fan #6");
|
||||
static_cast<RampStrategy*>(fan6_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan7_rs = getStrategy("Speed EC Fan #7");
|
||||
static_cast<RampStrategy*>(fan7_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan8_rs = getStrategy("Speed EC Fan #8");
|
||||
static_cast<RampStrategy*>(fan8_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
Strategy_Behavior* fan9_rs = getStrategy("Speed EC Fan #9");
|
||||
static_cast<RampStrategy*>(fan9_rs)->setTarget(4200.0f * (speed /100.0f));
|
||||
|
||||
|
||||
|
||||
float value = getPointValue(equipment, "CW Valve Position");
|
||||
Serial.printf("CW Valve Position: %0.2f\n", value);
|
||||
float sat_setpoint = getPointValue(equipment, "SAT Setpoint");
|
||||
Strategy_Behavior* sat_svs = getStrategy("SAT Reading");
|
||||
static_cast<SingleValueStrategy*>(sat_svs)->setSetpoint(sat_setpoint);
|
||||
// Apply any strategies defined for the standby state
|
||||
_applyStrategies(equipment);
|
||||
return nullptr;
|
||||
|
||||
@@ -21,10 +21,10 @@
|
||||
* @{
|
||||
*/
|
||||
#include <ModbusIP_ESP8266.h>
|
||||
const char *ssid = "wifi_name"; /**< @brief The SSID of the WiFi network. */
|
||||
const char *password = "wifi_password"; /**< @brief The password for the WiFi network. */
|
||||
IPAddress local_IP(192, 168, 1, 234); /**< @brief The static IP address for the device. */
|
||||
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
|
||||
const char *ssid = "QTS_CDR_Arduino"; /**< @brief The SSID of the WiFi network. */
|
||||
const char *password = "123abc456"; /**< @brief The password for the WiFi network. */
|
||||
IPAddress local_IP(172, 17, 33, 11); /**< @brief The static IP address for the device. */
|
||||
IPAddress gateway(172, 17, 33, 1); /**< @brief The gateway IP address. */
|
||||
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
|
||||
|
||||
ModbusIP mb;
|
||||
@@ -60,81 +60,82 @@
|
||||
*/
|
||||
modbusMap mb_map[] =
|
||||
{
|
||||
{HR, 15, 0, "State Control"}, //Internal to control from Modscan
|
||||
{HR, 16, 0, "Fault Code"},
|
||||
{HR_FLOAT, 18, 0, "RAT"}, //Internal Fault code from Modscan
|
||||
{HR_FLOAT, 1, 0, "SAT Setpoint"},
|
||||
{HR_FLOAT, 681, 0, "RAT Setpoint"},
|
||||
{HR_FLOAT, 111, 0, "High RAT Limit"},
|
||||
{HR_FLOAT, 114, 0, "Low RAT Limit"},
|
||||
{HR_FLOAT, 118, 0, "High SAT Limit"},
|
||||
{HR_FLOAT, 122, 0, "Low SAT Limit"},
|
||||
{HR_FLOAT, 685, 0, "High RAH Limit"},
|
||||
{HR_FLOAT, 689, 0, "Low RAH Limit"},
|
||||
{HR, 5, 0, "Setting the EC Fan Max Speed"},
|
||||
{HR, 695, 0, "Setting the EC Fan Min Speed"},
|
||||
{HR_FLOAT, 693, 0, "Setting Room Temp"},
|
||||
{HR, 691, 0, "Setting EC Fan Speed "},
|
||||
{DI, 146, 0, "Alarm SAT Sensor Fault"},
|
||||
{DI, 1246, 0, "Alarm RAH Sensor Fault"},
|
||||
{DI, 1245, 0, "Alarm RAT Sensor Fault"},
|
||||
{DI, 1250, 0, "Alarm Filter DP Sensor Fault"},
|
||||
{DI, 51, 0, "Alarm Flooding"},
|
||||
{DI, 1096, 0, "Alarm Dirty Filter"},
|
||||
{DI, 1367, 0, "Alarm High RAT"},
|
||||
{DI, 1099, 0, "Alarm Low RAT"},
|
||||
{DI, 118, 0, "Alarm High SAT"},
|
||||
{DI, 122, 0, "Alarm Low SAT"},
|
||||
{DI, 1307, 0, "Alarm High RAH"},
|
||||
{DI, 1308, 0, "Alarm Low RAH"},
|
||||
{DI, 1342, 0, "Alarm Common"},
|
||||
{DI, 148, 0, "Alarm Phase Failure"},
|
||||
{DI, 1370, 0, "Alarm Condensate Pump"},
|
||||
{DI, 1368, 0, "Alarm Smoke"},
|
||||
{DI, 1369, 0, "Alarm Fire"},
|
||||
{DI, 131, 0, "Alarm EC Fan #1"},
|
||||
{DI, 132, 0, "Alarm EC Fan #2"},
|
||||
{DI, 133, 0, "Alarm EC Fan #3"},
|
||||
{DI, 134, 0, "Alarm EC Fan #4"},
|
||||
{DI, 135, 0, "Alarm EC Fan #5"},
|
||||
{DI, 136, 0, "Alarm EC Fan #6"},
|
||||
{DI, 1360, 0, "Alarm EC Fan #7"},
|
||||
{DI, 1361, 0, "Alarm EC Fan #8"},
|
||||
{DI, 1362, 0, "Alarm EC Fan #9"},
|
||||
{DI, 138, 0, "Run Status EC Fan #1"},
|
||||
{DI, 139, 0, "Run Status EC Fan #2"},
|
||||
{DI, 140, 0, "Run Status EC Fan #3"},
|
||||
{DI, 141, 0, "Run Status EC Fan #4"},
|
||||
{DI, 142, 0, "Run Status EC Fan #5"},
|
||||
{DI, 143, 0, "Run Status EC Fan #6"},
|
||||
{DI, 1363, 0, "Run Status EC Fan #7"},
|
||||
{DI, 1364, 0, "Run Status EC Fan #8"},
|
||||
{DI, 1365, 0, "Run Status EC Fan #9"},
|
||||
{IR_FLOAT, 99, 0, "SAT Reading"},
|
||||
{IR_FLOAT, 70, 0, "RAH Reading"},
|
||||
{IR_FLOAT, 101, 0, "RAT Reading"},
|
||||
{IR_FLOAT, 106, 0, "Filter DP Reading"},
|
||||
{IR_FLOAT, 496, 0, "CW Valve Position"},
|
||||
{IR, 53, 0, "Speed EC Fan #1"},
|
||||
{IR, 228, 0, "Speed EC Fan #2"},
|
||||
{IR, 229, 0, "Speed EC Fan #3"},
|
||||
{IR, 230, 0, "Speed EC Fan #4"},
|
||||
{IR, 231, 0, "Speed EC Fan #5"},
|
||||
{IR, 232, 0, "Speed EC Fan #6"},
|
||||
{IR, 678, 0, "Speed EC Fan #7"},
|
||||
{IR, 679, 0, "Speed EC Fan #8"},
|
||||
{IR, 680, 0, "Speed EC Fan #9"},
|
||||
{IR, 274, 0, "Operating Hours EC Fan #1"},
|
||||
{IR, 233, 0, "Operating Hours EC Fan #2"},
|
||||
{IR, 244, 0, "Operating Hours EC Fan #3"},
|
||||
{IR, 235, 0, "Operating Hours EC Fan #4"},
|
||||
{IR, 236, 0, "Operating Hours EC Fan #5"},
|
||||
{IR, 245, 0, "Operating Hours EC Fan #6"},
|
||||
{IR, 486, 0, "Operating Hours EC Fan #7"},
|
||||
{IR, 487, 0, "Operating Hours EC Fan #8"},
|
||||
{IR, 488, 0, "Operating Hours EC Fan #9"},
|
||||
{COIL, 301, 0, "ON/OFF Command By BMS"},
|
||||
{COIL, 302, 0, "Enable Off By Supervisory"},
|
||||
{HR, 13, 0, "Delta"},
|
||||
{HR, 14, 0, "State Control"}, //Internal to control from Modscan
|
||||
{HR, 15, 0, "Fault Code"},
|
||||
{HR_FLOAT, 17, 0, "RAT"}, //Internal Fault code from Modscan
|
||||
{HR_FLOAT, 0, 0, "SAT Setpoint"},
|
||||
{HR_FLOAT, 680, 0, "RAT Setpoint"},
|
||||
{HR_FLOAT, 110, 0, "High RAT Limit"},
|
||||
{HR_FLOAT, 113, 0, "Low RAT Limit"},
|
||||
{HR_FLOAT, 117, 0, "High SAT Limit"},
|
||||
{HR_FLOAT, 121, 0, "Low SAT Limit"},
|
||||
{HR_FLOAT, 684, 0, "High RAH Limit"},
|
||||
{HR_FLOAT, 688, 0, "Low RAH Limit"},
|
||||
{HR, 4, 0, "Setting the EC Fan Max Speed"},
|
||||
{HR, 694, 0, "Setting the EC Fan Min Speed"},
|
||||
{HR_FLOAT, 692, 0, "Setting Room Temp"},
|
||||
{HR_FLOAT, 690, 0, "Setting EC Fan Speed"},
|
||||
{DI, 145, 0, "Alarm SAT Sensor Fault"},
|
||||
{DI, 1245, 0, "Alarm RAH Sensor Fault"},
|
||||
{DI, 1244, 0, "Alarm RAT Sensor Fault"},
|
||||
{DI, 1249, 0, "Alarm Filter DP Sensor Fault"},
|
||||
{DI, 50, 0, "Alarm Flooding"},
|
||||
{DI, 1095, 0, "Alarm Dirty Filter"},
|
||||
{DI, 1366, 0, "Alarm High RAT"},
|
||||
{DI, 1098, 0, "Alarm Low RAT"},
|
||||
{DI, 117, 0, "Alarm High SAT"},
|
||||
{DI, 121, 0, "Alarm Low SAT"},
|
||||
{DI, 1306, 0, "Alarm High RAH"},
|
||||
{DI, 1307, 0, "Alarm Low RAH"},
|
||||
{DI, 1341, 0, "Alarm Common"},
|
||||
{DI, 147, 0, "Alarm Phase Failure"},
|
||||
{DI, 1369, 0, "Alarm Condensate Pump"},
|
||||
{DI, 1367, 0, "Alarm Smoke"},
|
||||
{DI, 1368, 0, "Alarm Fire"},
|
||||
{DI, 130, 0, "Alarm EC Fan #1"},
|
||||
{DI, 131, 0, "Alarm EC Fan #2"},
|
||||
{DI, 132, 0, "Alarm EC Fan #3"},
|
||||
{DI, 133, 0, "Alarm EC Fan #4"},
|
||||
{DI, 134, 0, "Alarm EC Fan #5"},
|
||||
{DI, 135, 0, "Alarm EC Fan #6"},
|
||||
{DI, 1359, 0, "Alarm EC Fan #7"},
|
||||
{DI, 1360, 0, "Alarm EC Fan #8"},
|
||||
{DI, 1361, 0, "Alarm EC Fan #9"},
|
||||
{DI, 137, 0, "Run Status EC Fan #1"},
|
||||
{DI, 138, 0, "Run Status EC Fan #2"},
|
||||
{DI, 139, 0, "Run Status EC Fan #3"},
|
||||
{DI, 140, 0, "Run Status EC Fan #4"},
|
||||
{DI, 141, 0, "Run Status EC Fan #5"},
|
||||
{DI, 142, 0, "Run Status EC Fan #6"},
|
||||
{DI, 1362, 0, "Run Status EC Fan #7"},
|
||||
{DI, 1363, 0, "Run Status EC Fan #8"},
|
||||
{DI, 1364, 0, "Run Status EC Fan #9"},
|
||||
{IR_FLOAT, 98, 0, "SAT Reading"},
|
||||
{IR_FLOAT, 69, 0, "RAH Reading"},
|
||||
{IR_FLOAT, 100, 0, "RAT Reading"},
|
||||
{IR_FLOAT, 105, 0, "Filter DP Reading"},
|
||||
{IR_FLOAT, 495, 0, "CW Valve Position"},
|
||||
{IR, 52, 0, "Speed EC Fan #1"},
|
||||
{IR, 227, 0, "Speed EC Fan #2"},
|
||||
{IR, 228, 0, "Speed EC Fan #3"},
|
||||
{IR, 229, 0, "Speed EC Fan #4"},
|
||||
{IR, 230, 0, "Speed EC Fan #5"},
|
||||
{IR, 231, 0, "Speed EC Fan #6"},
|
||||
{IR, 677, 0, "Speed EC Fan #7"},
|
||||
{IR, 678, 0, "Speed EC Fan #8"},
|
||||
{IR, 679, 0, "Speed EC Fan #9"},
|
||||
{IR, 273, 0, "Operating Hours EC Fan #1"},
|
||||
{IR, 232, 0, "Operating Hours EC Fan #2"},
|
||||
{IR, 243, 0, "Operating Hours EC Fan #3"},
|
||||
{IR, 234, 0, "Operating Hours EC Fan #4"},
|
||||
{IR, 235, 0, "Operating Hours EC Fan #5"},
|
||||
{IR, 244, 0, "Operating Hours EC Fan #6"},
|
||||
{IR, 485, 0, "Operating Hours EC Fan #7"},
|
||||
{IR, 486, 0, "Operating Hours EC Fan #8"},
|
||||
{IR, 487, 0, "Operating Hours EC Fan #9"},
|
||||
{COIL, 300, 0, "ON/OFF Command By BMS"},
|
||||
{COIL, 301, 0, "Enable Off By Supervisory"},
|
||||
{COIL, 264, 0, "Alarm Reset"}
|
||||
};
|
||||
//Size of modbus map used in FOR cycles, automatically calculated.
|
||||
|
||||
Reference in New Issue
Block a user