Merge pull request #49 from emmanuelsrlok/rdavis/UMAS_CRAH_TCP

Rdavis/umas crah tcp
This commit is contained in:
Emmanuel HC
2026-05-21 09:19:56 -05:00
committed by GitHub
7 changed files with 244 additions and 169 deletions

View File

@@ -9,7 +9,8 @@
[platformio]
default_envs = RPP_Cortex_TCP ; Select here the name of the configuration you want to download
default_envs = CRAH_UMAS_TCP ; Select here the name of the configuration you want to download
[env]
upload_port = COM11
@@ -213,71 +214,9 @@ board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_src_filter = -<*> +<BMS/CHILLER/CH_York_YVAA_RTU>
[env:PHX3_VFD_ABB_ACH580_RTU]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_src_filter = -<*> +<BMS/VFD/PHX3_VFD_ABB_ACH580_RTU>
[env:PHX3_CRAH_LIEBERT_80_SLAB_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<BMS/CRAH/PHX3_CRAH_LIEBERT_80_SLAB_TCP>
[env:HUM_DriSteem_RTS_RX36_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<BMS/HUM/HUM_DriSteem_RTS_RX36_TCP>
[env:CRAH_UMAS_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<BMS/CRAH/CRAH_UMAS_TCP>
[env:GEN_HSE]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<EPMS/GEN/GEN_HSE>
[env:SEL_2440_MVG]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<Base_TCP>
[env:MVG_SC_EC_M505_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP,
build_src_filter = -<*> +<EPMS/MVG/MVG_SC_EC_M505_TCP>
[env:GEN_CAT_GCCP_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP,
build_src_filter = -<*> +<EPMS/GEN/GEN_CAT_GCCP_TCP>
[env:CDU_CoolIT_Oracle_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<BMS/CDU/CDU_CoolIT_Oracle_TCP>
[env:RPP_Cortex_TCP]
platform = espressif32
board = dfrobot_firebeetle2_esp32e
extends = common_env_options
build_flags = -D USE_MODBUS_IP
build_src_filter = -<*> +<EPMS/RPP/RPP_Cortex_TCP>

View File

@@ -53,6 +53,120 @@ void updateControlMode(Equipment<ModbusIP>* equipment){
equipment->setModbus_Point("Control Mode Selected", Control_Mode_Selected);
}
/** This function will set RA Temp, SA Temp, RA Humidity analog values to a LOW or HIGH range for testing alarms in Ignition.
* There is an associated COIL for performing each of those functions.
* There is also a NORMAL bit, which sends a one-shot to reset the associated analog value back into a normal range.
*/
void updateAnalogs(Equipment<ModbusIP>* equipment){
if (equipment->getModbus_Point("RA Temp NORMAL")->getValue()==1){
equipment->setModbus_Point("Return Air Temp", 84.0f);
equipment->setModbus_Point("RA Temp Low Alarm ON", 0);
equipment->setModbus_Point("RA Temp High Alarm ON", 0);
equipment->setModbus_Point("RA Temp NORMAL", 0);
}
else if (equipment->getModbus_Point("RA Temp Low Alarm ON")->getValue() ==1){
equipment->setModbus_Point("Return Air Temp", 60.0f);
equipment->setModbus_Point("RA Temp High Alarm ON", 0);
}
else if (equipment->getModbus_Point("RA Temp High Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Air Temp", 110.0f);
equipment->setModbus_Point("RA Temp Low Alarm ON", 0);
}
if (equipment->getModbus_Point("RA Humidity NORMAL")->getValue()==1){
equipment->setModbus_Point("Return Humidity", 25.0f);
equipment->setModbus_Point("RA Humidity Low Alarm ON", 0);
equipment->setModbus_Point("RA Humidity High Alarm ON", 0);
equipment->setModbus_Point("RA Humidity NORMAL", 0);
}
else if (equipment->getModbus_Point("RA Humidity Low Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Humidity", 5.0f);
equipment->setModbus_Point("RA Humidity High Alarm ON", 0);
}
else if (equipment->getModbus_Point("RA Humidity High Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Humidity", 80.0f);
equipment->setModbus_Point("RA Humidity Low Alarm ON", 0);
}
if (equipment->getModbus_Point("SA Temp NORMAL")->getValue()==1){
equipment->setModbus_Point("Supply Air Temp", 76.0f);
equipment->setModbus_Point("SA Temp Low Alarm ON", 0);
equipment->setModbus_Point("SA Temp High Alarm ON", 0);
equipment->setModbus_Point("SA Temp NORMAL", 0);
}
else if (equipment->getModbus_Point("SA Temp Low Alarm ON")->getValue() ==1){
equipment->setModbus_Point("Supply Air Temp", 60.0f);
equipment->setModbus_Point("SA Temp High Alarm ON", 0);
}
else if (equipment->getModbus_Point("SA Temp High Alarm ON")->getValue()==1){
equipment->setModbus_Point("Supply Air Temp", 90.0f);
equipment->setModbus_Point("SA Temp Low Alarm ON", 0);
}
}
// Updates the RA Temp Alarms
void updateReturnAirTempAlarms(Equipment<ModbusIP>* equipment){
Modbus_Point<ModbusIP>* returnAirTemp = equipment -> getModbus_Point("Return Air Temp");
Modbus_Point<ModbusIP>* returnTempHighAlarmSP = equipment->getModbus_Point("Return Air Temp Alarm High SP");
Modbus_Point<ModbusIP>* returnTempLowAlarmSP = equipment->getModbus_Point("Return Air Temp Alarm Low SP");
if (returnAirTemp->getValue() < returnTempLowAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm Low Return Air Temp", 1);
equipment->setModbus_Point("Alarm High Return Air Temp", 0);
}
else if (returnAirTemp->getValue() > returnTempHighAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm High Return Air Temp", 1);
equipment->setModbus_Point("Alarm Low Return Air Temp", 0);
}
else{
equipment->setModbus_Point("Alarm High Return Air Temp", 0);
equipment->setModbus_Point("Alarm Low Return Air Temp", 0);
}
}
// Updates the SA Temp Alarms
void updateSupplyAirTempAlarms(Equipment<ModbusIP>* equipment){
Modbus_Point<ModbusIP>* supplyAirTemp = equipment -> getModbus_Point("Supply Air Temp");
Modbus_Point<ModbusIP>* supplyTempHighAlarmSP = equipment->getModbus_Point("Supply Air Temp Alarm High SP");
Modbus_Point<ModbusIP>* supplyTempLowAlarmSP = equipment->getModbus_Point("Supply Air Temp Alarm Low SP");
if (supplyAirTemp->getValue() > supplyTempHighAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm High Supply Temp", 1);
equipment->setModbus_Point("Alarm Low Supply Temp", 0);
}
else if (supplyAirTemp->getValue() < supplyTempLowAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm Low Supply Temp", 1);
equipment->setModbus_Point("Alarm High Supply Temp", 0);
}
else{
equipment->setModbus_Point("Alarm High Supply Temp", 0);
equipment->setModbus_Point("Alarm Low Supply Temp", 0);
}
}
// Updates the RA Humidity Alarms
void updateReturnHumidityAlarms(Equipment<ModbusIP>* equipment){
Modbus_Point<ModbusIP>* returnHumidity = equipment -> getModbus_Point("Return Humidity");
Modbus_Point<ModbusIP>* returnHumHighAlarmSP = equipment->getModbus_Point("Return Humidity Alarm High SP");
Modbus_Point<ModbusIP>* returnHumLowAlarmSP = equipment->getModbus_Point("Return Humidity Alarm Low SP");
if (returnHumidity->getValue() > returnHumHighAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm High Return Humidity", 1);
equipment->setModbus_Point("Alarm Low Return Humidity", 0);
}
else if (returnHumidity->getValue() < returnHumLowAlarmSP->getValue()) {
equipment->setModbus_Point("Alarm Low Return Humidity", 1);
equipment->setModbus_Point("Alarm High Return Humidity", 0);
}
else{
equipment->setModbus_Point("Alarm High Return Humidity", 0);
equipment->setModbus_Point("Alarm Low Return Humidity", 0);
}
}
/**
* @brief This function will update the Alarm status DI bits according to the Alarm Commands from Coils (Modscan)
* It will also update the Common Alarm: if any alarm is active, the Common alarm will also be active.
@@ -75,6 +189,12 @@ void updateAlarms(Equipment<ModbusIP>* equipment){
"Alarm Condensate Pump ON", "Alarm Fire ON", "Alarm Smoke ON"
};
const std::vector<std::string> alarmAnalogs = {
"Alarm High Return Air Temp", "Alarm Low Return Air Temp", "Alarm High Return Humidity", "Alarm Low Return Humidity",
"Alarm High Supply Temp", "Alarm Low Supply Temp"
};
// NOTE: Per UMAS hardwire signals, alarm opened in case of normal operation, closed in case of alarm condition
// 0: no alarm, 1: alarm
int numAlarms = 0;
@@ -86,37 +206,15 @@ void updateAlarms(Equipment<ModbusIP>* equipment){
if (alarmPoint->getValue() == 1) numAlarms++;
}
}
// If any of the analog alarms = 1, increment counter for number of active alarms
for (int j = 0; j<alarmAnalogs.size(); ++j){
Modbus_Point<ModbusIP>* alarmAnalogPoint = equipment->getModbus_Point(alarmAnalogs[j]);
if (alarmAnalogPoint) {
if (alarmAnalogPoint->getValue() == 1) numAlarms++;
}
}
// If any alarms are active, set the Common Alarm = 1, else Common Alarm = 0.
if (numAlarms >= 1) equipment->setModbus_Point("Common Alarm", 1);
else equipment->setModbus_Point("Common Alarm", 0);
}
/**
* @brief The purpose of this function is for testing the RA Temp and RA Humidity alarms (Ignition HMI display)
* User will manually set Alarms through Modscan coils, which will change RA Temp or RA Humidity accordingly.
* The RA Temp alarm limits (reference Ignition UDT) are 72, 100.
* The SA Temp alarm limits (reference Ignition UDT) are 72, 78.
* The RA Humidity alarm limits (reference Ignition UDT) are 20, 60.
* If an associated alarm coil is not active, the analog values are set to a safe, un-alarmed value.
*
* NOTE: These analog alarms will not activate the Common Alarm in the Arduino test.
* Since these alarms will be set in Ignition, will not be sent over Modbus from CRAH to Ignition.
*
* This is a function used in the update() of the Running State.
*
*/
// Note: The Common Alarm is not configured to annunciate with these analog low/high alarms.
void updateAnalogs(Equipment<ModbusIP>* equipment){
if (equipment->getModbus_Point("RA Temp Low Alarm ON")->getValue() ==1){
equipment->setModbus_Point("Return Air Temp", 68.0f);
}
else if (equipment->getModbus_Point("RA Temp High Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Air Temp", 104.0f);
}
if (equipment->getModbus_Point("RA Humidity Low Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Air Humidity", 15.0f);
}
else if (equipment->getModbus_Point("RA Humidity High Alarm ON")->getValue()==1){
equipment->setModbus_Point("Return Air Humidity", 65.0f);
}
}

View File

@@ -34,6 +34,10 @@ class State;
* @return The selected control mode (int).
*/
void updateControlMode(Equipment<ModbusIP>* equipment);
void updateAnalogs(Equipment<ModbusIP>* equipment);
void updateReturnAirTempAlarms(Equipment<ModbusIP>* equipment);
void updateSupplyAirTempAlarms(Equipment<ModbusIP>* equipment);
void updateReturnHumidityAlarms(Equipment<ModbusIP>* equipment);
/**
* @brief Checks common alarms (non-fail alarms) and updates the Common Alarm Modbus point.
@@ -41,10 +45,3 @@ void updateControlMode(Equipment<ModbusIP>* equipment);
* @return true if any common alarm is active, false otherwise.
*/
void updateAlarms(Equipment<ModbusIP>* equipment);
/**
* @brief Checks common alarms (non-fail alarms) and updates the Common Alarm Modbus point.
* @param equipment Pointer to the Equipment instance.
* @return true if any common alarm is active, false otherwise.
*/
void updateAnalogs(Equipment<ModbusIP>* equipment);

View File

@@ -42,16 +42,17 @@ FailState<ModbusIP>::FailState(const std::vector<std::string>& activeAlarms) {
addStrategy("CW Valve Position", new RampStrategy(0.0f, 5.0f, 1000));
addStrategy("Supply Air Temp", new SingleValueStrategy(74.0f, 1.0f, 1000));
addStrategy("Return Air Temp", new SingleValueStrategy(86.0f, 1.0f, 1000));
addStrategy("Return Air Humidity", new SingleValueStrategy(35.0f, 2.0f, 1000));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Return Humidity", new SingleValueStrategy(30.0f, 1.0f, 3000));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Fan Speed Feedback", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Amps Fan 1", new RampStrategy(0.0f, 4.5f, 1000));
addStrategy("Amps Fan 2", new RampStrategy(0.0f, 4.5f, 1000));
addStrategy("Amps Fan 3", new RampStrategy(0.0f, 4.5f, 1000));
@@ -81,8 +82,11 @@ State<ModbusIP>* FailState<ModbusIP>::update(Equipment<ModbusIP>* equipment) {
// Still want Control Mode and Alarms to be updated while in Fail State
// Ensure BMS Command is set to Off: want operator to re-start from BMS once Leak Detect Alarm is cleared.
updateControlMode(equipment);
updateAlarms(equipment);
updateAnalogs(equipment);
updateReturnAirTempAlarms(equipment);
updateSupplyAirTempAlarms(equipment);
updateReturnHumidityAlarms(equipment);
updateAlarms(equipment);
setPointValue(equipment, "ON/OFF Command By BMS", 0);
// The only way to exit the Fail State is for Leak Detect Alarm to turn off, then enter Standby State.

View File

@@ -44,15 +44,15 @@ template<>
RunningState<ModbusIP>::RunningState() {
addStrategy("Fan Min Speed", new SingleValueStrategy(30.0f, 0.0f, 1000));
addStrategy("Fan Max Speed", new SingleValueStrategy(100.0f, 0.0f, 1000));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 100.0f, 1000));
addStrategy("Amps Fan 1", new RampStrategy(15.0f, 2.5f, 1000));
addStrategy("Amps Fan 2", new RampStrategy(15.0f, 2.5f, 1000));
addStrategy("Amps Fan 3", new RampStrategy(15.0f, 2.5f, 1000));
@@ -71,13 +71,13 @@ RunningState<ModbusIP>::RunningState() {
addStrategy("Operating Hours Fan 7", new TotalizerStrategy(1000));
addStrategy("Operating Hours Fan 8", new TotalizerStrategy(1000));
addStrategy("Operating Hours Fan 9", new TotalizerStrategy(1000));
addStrategy("Supply Air Temp", new SawStrategy(60.0f, 100.0f, 2.2f, 1000)); // Won't initialize at lower bound; always initializes at 0 b/c FLOAT; initialize manually via Modscan
addStrategy("Return Air Humidity", new SawStrategy(25.0f, 40.0f, 1.1f, 1000));
addStrategy("Return Air Temp", new SawStrategy(70.0f, 80.0f, 0.8f, 1000));
addStrategy("Filter Differential Pressure", new SawStrategy(0.0f, 5.0f, 0.2f, 1000));
addStrategy("Supply Air Temp", new SawStrategy(73.0f, 77.0f, 0.2f, 1000)); // Won't initialize at lower bound; always initializes at 0 b/c FLOAT; initialize manually via Modscan
addStrategy("Return Humidity", new SawStrategy(25.0f, 35.0f, 0.2f, 1000));
addStrategy("Return Air Temp", new SawStrategy(80.0f, 90.0f, 0.2f, 1000));
addStrategy("Filter Differential Pressure", new SawStrategy(0.1f, 5.1f, 0.2f, 1000));
addStrategy("CW Valve Position", new PIDStrategy("Supply Air Temp Setpoint", 1000, "Supply Air Temp")); // SAT must be greater than SAT Setpoint for this PID to work.
addStrategy("CRAH Heartbeat", new SawStrategy(0.0f, 60.0f, 1.0f, 1000));
addStrategy("Fan Speed Feedback", new RampStrategy(0.0f, 1.0f, 200));
addStrategy("Fan Speed Feedback", new RampStrategy(0.0f, 2.0f, 200));
}
/**
@@ -104,8 +104,11 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
int BMS_Enable_Source = getPointValue(equipment, "BMS Enable Source"); // Modscan HR 2
updateControlMode(equipment);
updateAlarms(equipment);
updateAnalogs(equipment);
updateReturnAirTempAlarms(equipment);
updateSupplyAirTempAlarms(equipment);
updateReturnHumidityAlarms(equipment);
updateAlarms(equipment);
// Check to see if Leak Detect alarm is active (only alarm which will make unit FAIL and turn off) --> Send to FailState
bool leakDetect = getPointValue(equipment, "Alarm Leak Detect");
@@ -121,11 +124,14 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
// This will update the Fan Speed Setpoint dynamically while in run mode. Fan Speed Setpoint changed through Modscan.
// This functioanlity matches the UMAS SOO specifically for how it calculates Speed Setpoint.
float BMS_Speed_Setpoint = getPointValue(equipment, "Fan Speed Setpoint");
float BMS_Speed_Setpoint_Pct = BMS_Speed_Setpoint / 100.0f;
float Fan_Min_Speed = getPointValue(equipment, "Fan Min Speed");
float Fan_Max_Speed = getPointValue(equipment, "Fan Max Speed");
float Fan_Nominal_Speed = 1900.0f;
float BMS_Speed_Setpoint = getPointValue(equipment, "Fan Speed Setpoint");
float BMS_Speed_Setpoint_Pct = BMS_Speed_Setpoint / 100.0f;
float Fan_Speed_Setpoint = BMS_Speed_Setpoint_Pct * (Fan_Max_Speed - Fan_Min_Speed) + Fan_Min_Speed;
float Fan_Speed_Setpoint_RPM = Fan_Speed_Setpoint / 100.0f * Fan_Nominal_Speed;
for (int i = 0; i < 10; i++){
std::string pointName = "Speed Fan " + std::to_string(i);
Strategy_Behavior* strat = getStrategy(pointName);
@@ -134,11 +140,13 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
if (ramp){
if (BMS_Speed_Setpoint > 100){
Fan_Speed_Setpoint = Fan_Max_Speed;
Fan_Speed_Setpoint_RPM = Fan_Max_Speed / 100.0f * Fan_Nominal_Speed;
}
else if (BMS_Speed_Setpoint < 0){
Fan_Speed_Setpoint = Fan_Min_Speed;
Fan_Speed_Setpoint_RPM = Fan_Min_Speed / 100.0f * Fan_Nominal_Speed;
}
ramp->setTarget(Fan_Speed_Setpoint);
ramp->setTarget(Fan_Speed_Setpoint_RPM);
}
}
}
@@ -146,7 +154,7 @@ State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
// Fan Speed Feedback dynamically ramp to Fan Speed Setpoint sent to Arduino
Strategy_Behavior* speedFeedback = getStrategy("Fan Speed Feedback");
if (speedFeedback){
static_cast<RampStrategy*>(speedFeedback)->setTarget(BMS_Speed_Setpoint);
static_cast<RampStrategy*>(speedFeedback)->setTarget(Fan_Speed_Setpoint);
}
// Apply any strategies defined for the standby state

View File

@@ -41,18 +41,19 @@ StandbyState<ModbusIP>::StandbyState() {
// You can add initialization code here if needed.
// These strategies are applied at the end of the update function.
addStrategy("CW Valve Position", new RampStrategy(0.0f, 5.0f, 1000));
addStrategy("Supply Air Temp", new SingleValueStrategy(74.0f, 1.0f, 1000));
addStrategy("Return Air Temp", new SingleValueStrategy(86.0f, 1.0f, 1000));
addStrategy("Return Air Humidity", new SingleValueStrategy(35.0f, 2.0f, 1000));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Supply Air Temp", new SingleValueStrategy(76.0f, 1.0f, 2000));
addStrategy("Return Air Temp", new SingleValueStrategy(86.0f, 1.0f, 3000));
addStrategy("Return Humidity", new SingleValueStrategy(25.0f, 1.0f, 4000));
addStrategy("Speed Fan 1", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 2", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 3", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 4", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 5", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 6", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 7", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 8", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Speed Fan 9", new RampStrategy(0.0f, 300.0f, 1000));
addStrategy("Fan Speed Feedback", new RampStrategy(0.0f, 10.0f, 1000));
addStrategy("Amps Fan 1", new RampStrategy(0.0f, 4.5f, 1000));
addStrategy("Amps Fan 2", new RampStrategy(0.0f, 4.5f, 1000));
addStrategy("Amps Fan 3", new RampStrategy(0.0f, 4.5f, 1000));
@@ -86,8 +87,11 @@ State<ModbusIP>* StandbyState<ModbusIP>::update(Equipment<ModbusIP>* equipment)
int BMS_Enable_Source = getPointValue(equipment, "BMS Enable Source"); // Modscan HR 2
updateControlMode(equipment);
updateAlarms(equipment);
updateAnalogs(equipment);
updateReturnAirTempAlarms(equipment);
updateSupplyAirTempAlarms(equipment);
updateReturnHumidityAlarms(equipment);
updateAlarms(equipment);
// Check to see if Leak Detect alarm is active (only alarm which will make unit FAIL and turn off) --> Send to FailState
bool leakDetect = getPointValue(equipment, "Alarm Leak Detect");

View File

@@ -23,7 +23,7 @@
#include <ModbusIP_ESP8266.h>
const char *ssid = "ArduinoWifiB"; /**< @brief The SSID of the WiFi network. */
const char *password = "123abc456"; /**< @brief The password for the WiFi network. */
IPAddress local_IP(172, 17, 32, 62); /**< @brief The static IP address for the device. */
IPAddress local_IP(172, 17, 32, 232); /**< @brief The static IP address for the device. */
IPAddress gateway(172, 17, 32, 1); /**< @brief The gateway IP address. */
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
@@ -56,37 +56,55 @@
* This array defines all the Modbus points available on the emulated device.
* The `description` field is crucial as it's used to look up points within the application logic.
*/
// "One-Based" Addressing for IR, HR registers
modbusMap mb_map[] =
{
{COIL, 0, 0, "ON/OFF Command By BMS"}, // Receive signal from PLC
{COIL, 1, 0, "Alarm Fan 1 ON"}, // Just for Arduino testing. Sets Alarm Fan 1 to 1.
{COIL, 2, 0, "Alarm Fan 2 ON"}, // Just for Arduino testing. Sets Alarm Fan 2 to 1.
{COIL, 3, 0, "Alarm Dirty Filter ON"}, // Just for Arduino testing. Sets Alarm Dirty Filter to 1.
{COIL, 4, 0, "Alarm Leak Detect ON"}, // Just for Arduino testing. Sets Alarm Fan 1 to 1.
{COIL, 5, 0, "RA Temp Low Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 6, 0, "RA Temp High Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 104F (high alarm)
{COIL, 7, 0, "RA Humidity Low Alarm ON"}, // Just for Arduino testing. Sets RA Humidity to 15% (low alarm)
{COIL, 8, 0, "RA Humidity High Alarm ON"}, // Just for Arduino testing. Sets RA Humidity to 65% (high alarm)
{COIL, 9, 0, "Alarm Fan 3 ON"}, // Just for Arduino testing. Sets Alarm Fan 3 to 1.
{COIL, 10, 0, "Alarm Fan 4 ON"}, // Just for Arduino testing. Sets Alarm Fan 4 to 1.
{COIL, 11, 0, "Alarm Fan 5 ON"}, // Just for Arduino testing. Sets Alarm Fan 5 to 1.
{COIL, 12, 0, "Alarm Fan 6 ON"}, // Just for Arduino testing. Sets Alarm Fan 6 to 1.
{COIL, 13, 0, "Alarm Fan 7 ON"}, // Just for Arduino testing. Sets Alarm Fan 7 to 1.
{COIL, 14, 0, "Alarm Fan 8 ON"}, // Just for Arduino testing. Sets Alarm Fan 8 to 1.
{COIL, 15, 0, "Alarm Fan 9 ON"}, // Just for Arduino testing. Sets Alarm Fan 9 to 1.
{COIL, 16, 0, "Alarm Condensate Pump ON"}, // Just for Arduino testing. Sets Alarm Condensate Pump to 1.
{COIL, 17, 0, "Alarm Fire ON"}, // Just for Arduino testing. Sets Alarm Fire to 1.
{COIL, 18, 0, "Alarm Smoke ON"}, // Just for Arduino testing. Sets Alarm Smoke to 1.
{COIL, 1, 0, "Alarm Dirty Filter ON"}, // Just for Arduino testing. Sets Alarm Dirty Filter to 1.
{COIL, 2, 0, "Alarm Leak Detect ON"}, // Just for Arduino testing. Sets Alarm Fan 1 to 1.
{COIL, 3, 0, "Alarm Fan 1 ON"}, // Just for Arduino testing. Sets Alarm Fan 1 to 1.
{COIL, 4, 0, "Alarm Fan 2 ON"}, // Just for Arduino testing. Sets Alarm Fan 2 to 1.
{COIL, 5, 0, "Alarm Fan 3 ON"}, // Just for Arduino testing. Sets Alarm Fan 3 to 1.
{COIL, 6, 0, "Alarm Fan 4 ON"}, // Just for Arduino testing. Sets Alarm Fan 4 to 1.
{COIL, 7, 0, "Alarm Fan 5 ON"}, // Just for Arduino testing. Sets Alarm Fan 5 to 1.
{COIL, 8, 0, "Alarm Fan 6 ON"}, // Just for Arduino testing. Sets Alarm Fan 6 to 1.
{COIL, 9, 0, "Alarm Fan 7 ON"}, // Just for Arduino testing. Sets Alarm Fan 7 to 1.
{COIL, 10, 0, "Alarm Fan 8 ON"}, // Just for Arduino testing. Sets Alarm Fan 8 to 1.
{COIL, 11, 0, "Alarm Fan 9 ON"}, // Just for Arduino testing. Sets Alarm Fan 9 to 1.
{COIL, 12, 0, "Alarm Condensate Pump ON"}, // Just for Arduino testing. Sets Alarm Condensate Pump to 1.
{COIL, 13, 0, "Alarm Fire ON"}, // Just for Arduino testing. Sets Alarm Fire to 1.
{COIL, 14, 0, "Alarm Smoke ON"}, // Just for Arduino testing. Sets Alarm Smoke to 1.
{COIL, 15, 0, "RA Temp Low Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 16, 0, "RA Temp NORMAL"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 17, 0, "RA Temp High Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 104F (high alarm)
{COIL, 18, 0, "SA Temp Low Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 19, 0, "SA Temp NORMAL"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 20, 0, "SA Temp High Alarm ON"}, // Just for Arduino testing. Sets RA Temp to 104F (high alarm)
{COIL, 21, 0, "RA Humidity Low Alarm ON"}, // Just for Arduino testing. Sets RA Humidity to 15% (low alarm)
{COIL, 22, 0, "RA Humidity NORMAL"}, // Just for Arduino testing. Sets RA Temp to 68F (low alarm)
{COIL, 23, 0, "RA Humidity High Alarm ON"}, // Just for Arduino testing. Sets RA Humidity to 65% (high alarm)
{DI, 4, 0, "Alarm Leak Detect"},
{DI, 5, 0, "Alarm Dirty Filter"},
{DI, 6, 0, "Alarm High Return Air Temp"}, // suggested default 100, operator inputs High RA Temp SP for alarm limit
{DI, 7, 0, "Alarm Low Return Air Temp"}, // suggested default 72, operator inputs Low RA Temp SP for alarm limit
{DI, 8, 0, "Alarm High Supply Temp"}, // suggested default 78, operator inputs High SA Temp SP for alarm limit
{DI, 9, 0, "Alarm Low Supply Temp"}, // suggested default 72, operator inputs Low SA Temp SP for alarm limit
{DI, 10, 0, "Alarm High Return Humidity"}, // suggested default 60, operator inputs High Return Humidity SP for alarm limit
{DI, 11, 0, "Alarm Low Return Humidity"}, // suggested default 20, operator inputs Low Return Humidity SP for alarm limit
{DI, 12, 0, "Common Alarm"}, // Send to PLC
{DI, 14, 0, "Alarm Condensate Pump"},
{DI, 15, 0, "Alarm Smoke"},
{DI, 16, 0, "Alarm Fire"},
{IR_FLOAT, 1, 0, "Supply Air Temp"},
{IR_FLOAT, 3, 0, "Return Air Humidity"}, // Ignition visual only
{IR_FLOAT, 3, 0, "Return Humidity"}, // Ignition visual only
{IR_FLOAT, 5, 0, "Return Air Temp"}, // Send to PLC
{IR_FLOAT, 7, 0, "Filter Differential Pressure"}, // sawStrategy between 0 and 5
{IR_FLOAT, 9, 0, "CW Valve Position"},
@@ -136,16 +154,23 @@ modbusMap mb_map[] =
{IR_FLOAT, 75, 0, "Amps Fan 7"},
{IR_FLOAT, 77, 0, "Amps Fan 8"},
{IR_FLOAT, 79, 0, "Amps Fan 9"},
{IR_FLOAT, 99, 0, "CRAH Heartbeat"},
{HR_FLOAT, 1, 0, "Return Air Temp Alarm High SP"}, // default: 100, set locally on unit
{HR_FLOAT, 3, 0, "Return Air Temp Alarm Low SP"}, // default: 72, set locally on unit
{HR_FLOAT, 5, 0, "Supply Air Temp Alarm High SP"}, // default: 78, set locally on unit
{HR_FLOAT, 7, 0, "Supply Air Temp Alarm Low SP"}, // default: 72, set locally on unit
{HR_FLOAT, 9, 0, "Return Humidity Alarm High SP"}, // default: 60, set locally on unit
{HR_FLOAT, 11, 0, "Return Humidity Alarm Low SP"}, // default: 20, set locally on unit
{HR_FLOAT, 13, 0, "Fan Speed Setpoint"}, // Receive signal from PLC
{HR_FLOAT, 17, 0, "Supply Air Temp Setpoint"}, // Receive signal from PLC
{HR_FLOAT, 19, 0, "Return Air Temp Setpoint"}, // set locally on unit
{HR_FLOAT, 21, 0, "Fan Min Speed"}, // Send to PLC
{HR_FLOAT, 23, 0, "Fan Max Speed"}, // Send to PLC
{HR, 25, 0, "BMS Control Source"}, // Receive signal from PLC 0:Speed, 1:Room Temp
{HR, 26, 2, "BMS Enable Source"}, // Receive signal from PLC 0:Keypad, 1:DI, 2:BMS
{HR_FLOAT, 28, 0, "Fan Speed Feedback"},
{HR_FLOAT, 99, 0, "PLC Heartbeat"}, // This will be seconds from PLC - if doesn't change for 15 seconds set BMS Enable Source to Local (0)
{HR, 95, 0, "CRAH Heartbeat"},
{HR, 96, 0, "BMS Heartbeat"}, // This will be seconds from PLC - if doesn't change for 15 seconds set BMS Enable Source to Local (0)
};
//Size of modbus map used in FOR cycles, automatically calculated.