com
change com
This commit is contained in:
@@ -63,6 +63,48 @@ void updateAlarms(Equipment<ModbusIP>* equipment){
|
||||
"Alarm Compressor 1B Overload ON", "Alarm Compressor 2B Overload ON"
|
||||
};
|
||||
|
||||
Modbus_Point<ModbusIP>* returnAirTemp = equipment -> getModbus_Point("Return Air Temp");
|
||||
Modbus_Point<ModbusIP>* supplyAirTemp = equipment -> getModbus_Point("Supply Air Temp");
|
||||
Modbus_Point<ModbusIP>* returnHumidity = equipment -> getModbus_Point("Return Humidity");
|
||||
//int supplyAirTemp = getPointValue(equipment, "Supply Air Temp");
|
||||
//int returnHumidity = getPointValue(equipment, "Return Humidity");
|
||||
|
||||
// Update Return Air Temp Alarms
|
||||
if (returnAirTemp > equipment->getModbus_Point("Return Air Temp Alarm High SP")) {
|
||||
equipment->setModbus_Point("Alarm High Return Air Temp", 1);
|
||||
}
|
||||
else if (returnAirTemp < equipment->getModbus_Point("Return Air Temp Alarm Low SP")) {
|
||||
equipment->setModbus_Point("Alarm Low Return Air Temp", 1);
|
||||
}
|
||||
else{
|
||||
equipment->setModbus_Point("Alarm High Return Air Temp", 0);
|
||||
equipment->setModbus_Point("Alarm Low Return Air Temp", 0);
|
||||
}
|
||||
|
||||
// Update Supply Air Temp Alarms
|
||||
if (supplyAirTemp > equipment->getModbus_Point("Supply Air Temp Alarm High SP")) {
|
||||
equipment->setModbus_Point("Alarm High Supply Temp", 1);
|
||||
}
|
||||
else if (supplyAirTemp < equipment->getModbus_Point("Supply Air Temp Alarm Low SP")) {
|
||||
equipment->setModbus_Point("Alarm Low Supply Temp", 1);
|
||||
}
|
||||
else{
|
||||
equipment->setModbus_Point("Alarm High Supply Temp", 0);
|
||||
equipment->setModbus_Point("Alarm Low Supply Temp", 0);
|
||||
}
|
||||
|
||||
// Update Return Humidity Alarms
|
||||
if (returnHumidity > equipment->getModbus_Point("Return Humidity Alarm High SP")) {
|
||||
equipment->setModbus_Point("Alarm High Return Humidity", 1);
|
||||
}
|
||||
else if (returnHumidity < equipment->getModbus_Point("Return Humidity Alarm Low SP")) {
|
||||
equipment->setModbus_Point("AAlarm Low Return Humidity", 1);
|
||||
}
|
||||
else{
|
||||
equipment->setModbus_Point("Alarm High Return Humidity", 0);
|
||||
equipment->setModbus_Point("Alarm Low Return Humidity", 0);
|
||||
}
|
||||
|
||||
int numAlarms = 0;
|
||||
for (int i =0; i< alarmCommands.size() && i < alarmDescriptions.size(); ++i) {
|
||||
Modbus_Point<ModbusIP>* commandPoint = equipment->getModbus_Point(alarmCommands[i]);
|
||||
|
||||
@@ -44,7 +44,7 @@
|
||||
*/
|
||||
template<>
|
||||
RunningState<ModbusIP>::RunningState() {
|
||||
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 5.0f, 1000));
|
||||
addStrategy("Return Humidity", new SawStrategy(2.0f, 80.0f, 2.0f, 1000));
|
||||
addStrategy("Return Air Temp", new SawStrategy(66.0f, 110.0f, 2.0f, 1000));
|
||||
addStrategy("Supply Air Temp", new SawStrategy(68.0f, 86.0f, 1.0f, 1000));
|
||||
addStrategy("Supply Air Flow", new SawStrategy(7.0f, 10.0f, 1.0f, 1000));
|
||||
|
||||
@@ -40,7 +40,7 @@
|
||||
template<>
|
||||
StandbyState<ModbusIP>::StandbyState() {
|
||||
addStrategy("Fan Speed", new RampStrategy(0.0f, 10.0f, 1000));
|
||||
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 5.0f, 1000));
|
||||
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 2.0f, 1000));
|
||||
addStrategy("Return Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("Supply Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||
addStrategy("Supply Air Flow", new RampStrategy(0.0f, 1.0f, 1000));
|
||||
|
||||
@@ -23,7 +23,7 @@
|
||||
#include <ModbusIP_ESP8266.h>
|
||||
const char *ssid = "TP-Link_D91A"; /**< @brief The SSID of the WiFi network. */
|
||||
const char *password = "52761492"; /**< @brief The password for the WiFi network. */
|
||||
IPAddress local_IP(192, 168, 1, 234); /**< @brief The static IP address for the device. */
|
||||
IPAddress local_IP(192, 168, 0, 234); /**< @brief The static IP address for the device. */
|
||||
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
|
||||
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
|
||||
|
||||
@@ -68,7 +68,7 @@ modbusMap mb_map[] =
|
||||
{COIL, 6, 0, "Alarm Compressor 2A Overload ON"}, // For Arduino testing only
|
||||
{COIL, 7, 0, "Alarm Water Detected ON"}, // For Arduino testing only
|
||||
{COIL, 8, 0, "Alarm Standby Unit On ON"}, // For Arduino testing only
|
||||
{COIL, 9, 0, "Alarm Room Sensor Failure ON"}, // For Arduino testing only
|
||||
{COIL, 9, 0, "Alarm Room Sensor Failure ON"}, // For Arduino testing only
|
||||
{COIL, 10, 0, "Alarm Power Loss ON"}, // For Arduino testing only
|
||||
{COIL, 11, 0, "Alarm Clogged Filter ON"}, // For Arduino testing only
|
||||
{COIL, 12, 0, "Alarm Supply Sensor Failure ON"}, // For Arduino testing only
|
||||
@@ -144,8 +144,15 @@ modbusMap mb_map[] =
|
||||
{IR, 2050, 0, "Fluid Control Valve Position 1"},
|
||||
{IR, 2051, 0, "Fluid Control Valve Position 2"},
|
||||
|
||||
{HR_10x, 53, 60, "Return Humidity Alarm High SP"},
|
||||
{HR_10x, 54, 20, "Return Humidity Alarm Low SP"},
|
||||
{HR, 732, 73, "Supply Air Temp Setpoint"},
|
||||
{HR_10x, 738, 100, "Return Air Temp Alarm High SP"},
|
||||
{HR_10x, 739, 72, "Return Air Temp Alarm Low SP"},
|
||||
{HR, 753, 80, "Return Air Temp Setpoint"},
|
||||
{HR_10x, 754, 78, "Supply Air Temp Alarm High SP"},
|
||||
{HR_10x, 755, 72, "Supply Air Temp Alarm Low SP"},
|
||||
|
||||
};
|
||||
//Size of modbus map used in FOR cycles, automatically calculated.
|
||||
|
||||
|
||||
Reference in New Issue
Block a user