com
change com
This commit is contained in:
@@ -13,7 +13,7 @@
|
|||||||
default_envs = PHX3_CRAH_LIEBERT_80_SLAB_TCP ; Select here the name of the configuration you want to download
|
default_envs = PHX3_CRAH_LIEBERT_80_SLAB_TCP ; Select here the name of the configuration you want to download
|
||||||
|
|
||||||
[env]
|
[env]
|
||||||
upload_port = COM9
|
upload_port = COM11
|
||||||
|
|
||||||
[common_env_options]
|
[common_env_options]
|
||||||
framework = arduino
|
framework = arduino
|
||||||
|
|||||||
@@ -63,6 +63,48 @@ void updateAlarms(Equipment<ModbusIP>* equipment){
|
|||||||
"Alarm Compressor 1B Overload ON", "Alarm Compressor 2B Overload ON"
|
"Alarm Compressor 1B Overload ON", "Alarm Compressor 2B Overload ON"
|
||||||
};
|
};
|
||||||
|
|
||||||
|
Modbus_Point<ModbusIP>* returnAirTemp = equipment -> getModbus_Point("Return Air Temp");
|
||||||
|
Modbus_Point<ModbusIP>* supplyAirTemp = equipment -> getModbus_Point("Supply Air Temp");
|
||||||
|
Modbus_Point<ModbusIP>* returnHumidity = equipment -> getModbus_Point("Return Humidity");
|
||||||
|
//int supplyAirTemp = getPointValue(equipment, "Supply Air Temp");
|
||||||
|
//int returnHumidity = getPointValue(equipment, "Return Humidity");
|
||||||
|
|
||||||
|
// Update Return Air Temp Alarms
|
||||||
|
if (returnAirTemp > equipment->getModbus_Point("Return Air Temp Alarm High SP")) {
|
||||||
|
equipment->setModbus_Point("Alarm High Return Air Temp", 1);
|
||||||
|
}
|
||||||
|
else if (returnAirTemp < equipment->getModbus_Point("Return Air Temp Alarm Low SP")) {
|
||||||
|
equipment->setModbus_Point("Alarm Low Return Air Temp", 1);
|
||||||
|
}
|
||||||
|
else{
|
||||||
|
equipment->setModbus_Point("Alarm High Return Air Temp", 0);
|
||||||
|
equipment->setModbus_Point("Alarm Low Return Air Temp", 0);
|
||||||
|
}
|
||||||
|
|
||||||
|
// Update Supply Air Temp Alarms
|
||||||
|
if (supplyAirTemp > equipment->getModbus_Point("Supply Air Temp Alarm High SP")) {
|
||||||
|
equipment->setModbus_Point("Alarm High Supply Temp", 1);
|
||||||
|
}
|
||||||
|
else if (supplyAirTemp < equipment->getModbus_Point("Supply Air Temp Alarm Low SP")) {
|
||||||
|
equipment->setModbus_Point("Alarm Low Supply Temp", 1);
|
||||||
|
}
|
||||||
|
else{
|
||||||
|
equipment->setModbus_Point("Alarm High Supply Temp", 0);
|
||||||
|
equipment->setModbus_Point("Alarm Low Supply Temp", 0);
|
||||||
|
}
|
||||||
|
|
||||||
|
// Update Return Humidity Alarms
|
||||||
|
if (returnHumidity > equipment->getModbus_Point("Return Humidity Alarm High SP")) {
|
||||||
|
equipment->setModbus_Point("Alarm High Return Humidity", 1);
|
||||||
|
}
|
||||||
|
else if (returnHumidity < equipment->getModbus_Point("Return Humidity Alarm Low SP")) {
|
||||||
|
equipment->setModbus_Point("AAlarm Low Return Humidity", 1);
|
||||||
|
}
|
||||||
|
else{
|
||||||
|
equipment->setModbus_Point("Alarm High Return Humidity", 0);
|
||||||
|
equipment->setModbus_Point("Alarm Low Return Humidity", 0);
|
||||||
|
}
|
||||||
|
|
||||||
int numAlarms = 0;
|
int numAlarms = 0;
|
||||||
for (int i =0; i< alarmCommands.size() && i < alarmDescriptions.size(); ++i) {
|
for (int i =0; i< alarmCommands.size() && i < alarmDescriptions.size(); ++i) {
|
||||||
Modbus_Point<ModbusIP>* commandPoint = equipment->getModbus_Point(alarmCommands[i]);
|
Modbus_Point<ModbusIP>* commandPoint = equipment->getModbus_Point(alarmCommands[i]);
|
||||||
|
|||||||
@@ -44,7 +44,7 @@
|
|||||||
*/
|
*/
|
||||||
template<>
|
template<>
|
||||||
RunningState<ModbusIP>::RunningState() {
|
RunningState<ModbusIP>::RunningState() {
|
||||||
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 5.0f, 1000));
|
addStrategy("Return Humidity", new SawStrategy(2.0f, 80.0f, 2.0f, 1000));
|
||||||
addStrategy("Return Air Temp", new SawStrategy(66.0f, 110.0f, 2.0f, 1000));
|
addStrategy("Return Air Temp", new SawStrategy(66.0f, 110.0f, 2.0f, 1000));
|
||||||
addStrategy("Supply Air Temp", new SawStrategy(68.0f, 86.0f, 1.0f, 1000));
|
addStrategy("Supply Air Temp", new SawStrategy(68.0f, 86.0f, 1.0f, 1000));
|
||||||
addStrategy("Supply Air Flow", new SawStrategy(7.0f, 10.0f, 1.0f, 1000));
|
addStrategy("Supply Air Flow", new SawStrategy(7.0f, 10.0f, 1.0f, 1000));
|
||||||
|
|||||||
@@ -40,7 +40,7 @@
|
|||||||
template<>
|
template<>
|
||||||
StandbyState<ModbusIP>::StandbyState() {
|
StandbyState<ModbusIP>::StandbyState() {
|
||||||
addStrategy("Fan Speed", new RampStrategy(0.0f, 10.0f, 1000));
|
addStrategy("Fan Speed", new RampStrategy(0.0f, 10.0f, 1000));
|
||||||
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 5.0f, 1000));
|
addStrategy("Return Humidity", new SawStrategy(0.0f, 80.0f, 2.0f, 1000));
|
||||||
addStrategy("Return Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
addStrategy("Return Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||||
addStrategy("Supply Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
addStrategy("Supply Air Temp", new SingleValueStrategy(80.0f, 1.0f, 1000));
|
||||||
addStrategy("Supply Air Flow", new RampStrategy(0.0f, 1.0f, 1000));
|
addStrategy("Supply Air Flow", new RampStrategy(0.0f, 1.0f, 1000));
|
||||||
|
|||||||
@@ -23,7 +23,7 @@
|
|||||||
#include <ModbusIP_ESP8266.h>
|
#include <ModbusIP_ESP8266.h>
|
||||||
const char *ssid = "TP-Link_D91A"; /**< @brief The SSID of the WiFi network. */
|
const char *ssid = "TP-Link_D91A"; /**< @brief The SSID of the WiFi network. */
|
||||||
const char *password = "52761492"; /**< @brief The password for the WiFi network. */
|
const char *password = "52761492"; /**< @brief The password for the WiFi network. */
|
||||||
IPAddress local_IP(192, 168, 1, 234); /**< @brief The static IP address for the device. */
|
IPAddress local_IP(192, 168, 0, 234); /**< @brief The static IP address for the device. */
|
||||||
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
|
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
|
||||||
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
|
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
|
||||||
|
|
||||||
@@ -68,7 +68,7 @@ modbusMap mb_map[] =
|
|||||||
{COIL, 6, 0, "Alarm Compressor 2A Overload ON"}, // For Arduino testing only
|
{COIL, 6, 0, "Alarm Compressor 2A Overload ON"}, // For Arduino testing only
|
||||||
{COIL, 7, 0, "Alarm Water Detected ON"}, // For Arduino testing only
|
{COIL, 7, 0, "Alarm Water Detected ON"}, // For Arduino testing only
|
||||||
{COIL, 8, 0, "Alarm Standby Unit On ON"}, // For Arduino testing only
|
{COIL, 8, 0, "Alarm Standby Unit On ON"}, // For Arduino testing only
|
||||||
{COIL, 9, 0, "Alarm Room Sensor Failure ON"}, // For Arduino testing only
|
{COIL, 9, 0, "Alarm Room Sensor Failure ON"}, // For Arduino testing only
|
||||||
{COIL, 10, 0, "Alarm Power Loss ON"}, // For Arduino testing only
|
{COIL, 10, 0, "Alarm Power Loss ON"}, // For Arduino testing only
|
||||||
{COIL, 11, 0, "Alarm Clogged Filter ON"}, // For Arduino testing only
|
{COIL, 11, 0, "Alarm Clogged Filter ON"}, // For Arduino testing only
|
||||||
{COIL, 12, 0, "Alarm Supply Sensor Failure ON"}, // For Arduino testing only
|
{COIL, 12, 0, "Alarm Supply Sensor Failure ON"}, // For Arduino testing only
|
||||||
@@ -144,8 +144,15 @@ modbusMap mb_map[] =
|
|||||||
{IR, 2050, 0, "Fluid Control Valve Position 1"},
|
{IR, 2050, 0, "Fluid Control Valve Position 1"},
|
||||||
{IR, 2051, 0, "Fluid Control Valve Position 2"},
|
{IR, 2051, 0, "Fluid Control Valve Position 2"},
|
||||||
|
|
||||||
|
{HR_10x, 53, 60, "Return Humidity Alarm High SP"},
|
||||||
|
{HR_10x, 54, 20, "Return Humidity Alarm Low SP"},
|
||||||
{HR, 732, 73, "Supply Air Temp Setpoint"},
|
{HR, 732, 73, "Supply Air Temp Setpoint"},
|
||||||
|
{HR_10x, 738, 100, "Return Air Temp Alarm High SP"},
|
||||||
|
{HR_10x, 739, 72, "Return Air Temp Alarm Low SP"},
|
||||||
{HR, 753, 80, "Return Air Temp Setpoint"},
|
{HR, 753, 80, "Return Air Temp Setpoint"},
|
||||||
|
{HR_10x, 754, 78, "Supply Air Temp Alarm High SP"},
|
||||||
|
{HR_10x, 755, 72, "Supply Air Temp Alarm Low SP"},
|
||||||
|
|
||||||
};
|
};
|
||||||
//Size of modbus map used in FOR cycles, automatically calculated.
|
//Size of modbus map used in FOR cycles, automatically calculated.
|
||||||
|
|
||||||
|
|||||||
Reference in New Issue
Block a user