First Set of Devices

This commit is contained in:
2026-06-12 11:55:32 -05:00
commit e8fcc6995e
17 changed files with 1376 additions and 0 deletions

37
ABB_XT_Modbus_v3.csv Normal file
View File

@@ -0,0 +1,37 @@
type,address,name,data_type,control_address,pics_address,pics_data_type,notes
,,,,,,,
Input_Register,300101,Amps_A,uint32,400101,,,
Holding_Register,400101,Amps_A_Ovr,uint32,,410001,Integer,
,,,,,,,
Input_Register,300103,Amps_B,uint32,400103,,,
Holding_Register,400103,Amps_B_Ovr,uint32,,410003,Integer,
,,,,,,,
Input_Register,300105,Amps_C,uint32,400105,,,
Holding_Register,400105,Amps_C_Ovr,uint32,,410005,Integer,
,,,,,,,
Input_Register,300109,Amps_G,uint32,400109,,,
Holding_Register,400109,Amps_G_Ovr,uint32,,410007,Integer,
,,,,,,,
Input_Register,300107,Amps_N,uint32,400107,,,
Holding_Register,400107,Amps_N_Ovr,uint32,,410009,Integer,
,,,,,,,
Input_Register,300041,Breaker_Status,uint16,400041,,,
Holding_Register,400041,Breaker_Status_Ovr,uint16,,410011,Integer,1 = Open/Close : 4096 = Tripped
,,,,,,,
Input_Register,300155,Volts_AB,uint16,400155,,,
Holding_Register,400155,Volts_AB_Ovr,uint16,,410013,Integer,
,,,,,,,
Input_Register,300151,Volts_AN,uint16,400151,,,
Holding_Register,400151,Volts_AN_Ovr,uint16,,410015,Integer,
,,,,,,,
Input_Register,300156,Volts_BC,uint16,400156,,,
Holding_Register,400156,Volts_BC_Ovr,uint16,,410017,Integer,
,,,,,,,
Input_Register,300152,Volts_BN,uint16,400152,,,
Holding_Register,400152,Volts_BN_Ovr,uint16,,410019,Integer,
,,,,,,,
Input_Register,300157,Volts_CA,uint16,400157,,,
Holding_Register,400157,Volts_CA_Ovr,uint16,,410021,Integer,
,,,,,,,
Input_Register,300153,Volts_CN,uint16,400153,,,
Holding_Register,400153,Volts_CN_Ovr,uint16,,410023,Integer,
1 type address name data_type control_address pics_address pics_data_type notes
2
3 Input_Register 300101 Amps_A uint32 400101
4 Holding_Register 400101 Amps_A_Ovr uint32 410001 Integer
5
6 Input_Register 300103 Amps_B uint32 400103
7 Holding_Register 400103 Amps_B_Ovr uint32 410003 Integer
8
9 Input_Register 300105 Amps_C uint32 400105
10 Holding_Register 400105 Amps_C_Ovr uint32 410005 Integer
11
12 Input_Register 300109 Amps_G uint32 400109
13 Holding_Register 400109 Amps_G_Ovr uint32 410007 Integer
14
15 Input_Register 300107 Amps_N uint32 400107
16 Holding_Register 400107 Amps_N_Ovr uint32 410009 Integer
17
18 Input_Register 300041 Breaker_Status uint16 400041
19 Holding_Register 400041 Breaker_Status_Ovr uint16 410011 Integer 1 = Open/Close : 4096 = Tripped
20
21 Input_Register 300155 Volts_AB uint16 400155
22 Holding_Register 400155 Volts_AB_Ovr uint16 410013 Integer
23
24 Input_Register 300151 Volts_AN uint16 400151
25 Holding_Register 400151 Volts_AN_Ovr uint16 410015 Integer
26
27 Input_Register 300156 Volts_BC uint16 400156
28 Holding_Register 400156 Volts_BC_Ovr uint16 410017 Integer
29
30 Input_Register 300152 Volts_BN uint16 400152
31 Holding_Register 400152 Volts_BN_Ovr uint16 410019 Integer
32
33 Input_Register 300157 Volts_CA uint16 400157
34 Holding_Register 400157 Volts_CA_Ovr uint16 410021 Integer
35
36 Input_Register 300153 Volts_CN uint16 400153
37 Holding_Register 400153 Volts_CN_Ovr uint16 410023 Integer