1typeaddressnamedata_typecontrol_addresspics_addresspics_data_typenotes
2Input_Register30215Amps_Afloat40215
3Holding_Register40215Amps_A_Ovrfloat410001Integer
4Input_Register30217Amps_Bfloat40217
5Holding_Register40217Amps_B_Ovrfloat410003Integer
6Input_Register30219Amps_Cfloat40219
7Holding_Register40219Amps_C_Ovrfloat410005Integer
8Input_Register30223Amps_Gfloat40223
9Holding_Register40223Amps_G_Ovrfloat410007Integer
10Input_Register30221Amps_Nfloat40221
11Holding_Register40221Amps_N_Ovrfloat410009Integer
12Input_Register30255kVAfloat40255
13Holding_Register40255kVA_Ovrfloat410011Integer
14Input_Register30251kWfloat40251
15Input_Register30265kWh_Reg1float40265
16Holding_Register40265kWh_Reg1_Ovrfloat410013Integer
17Input_Register30267kWh_Reg2float40267
18Holding_Register40267kWh_Reg2_Ovrfloat410015Integer
19Holding_Register40251kW_Ovrfloat410017Integer
20Input_Register30249PFfloat40249
21Holding_Register40249PF_Ovrfloat410019Integer
22Input_Register30207Register_30207_Bitsuint1640207bit 9=512: Tripped; bit 12=4096: CB_Position
23Holding_Register40207Register_30207_Bits_Ovruint16410021Integer
24Input_Register30237Volts_ABfloat40237
25Holding_Register40237Volts_AB_Ovrfloat410023Integer
26Input_Register30231Volts_ANfloat40231
27Holding_Register40231Volts_AN_Ovrfloat410025Integer
28Input_Register30239Volts_BCfloat40239
29Holding_Register40239Volts_BC_Ovrfloat410027Integer
30Input_Register30233Volts_BNfloat40233
31Holding_Register40233Volts_BN_Ovrfloat410029Integer
32Input_Register30241Volts_CAfloat40241
33Holding_Register40241Volts_CA_Ovrfloat410031Integer
34Input_Register30235Volts_CNfloat40235
35Holding_Register40235Volts_CN_Ovrfloat410033Integer