type,address,name,data_type,control_address,pics_address,pics_data_type,notes
|
||||
Discrete_Input,100051,Water_Detected_Alarm,bool,000051,,,Unit flooding detector alarm
|
||||
Coil,000051,_Water_Detected_Alarm,bool,,,,Unit flooding detector alarm
|
||||
Discrete_Input,100118,High_Temperature_Supply_Air,bool,000118,,,High supply air temperature alarm
|
||||
Coil,000118,_High_Temperature_Supply_Air,bool,,,,High supply air temperature alarm
|
||||
Discrete_Input,100122,Low_Temperature_Supply_Air,bool,000122,,,Low supply air temperature alarm
|
||||
Coil,000122,_Low_Temperature_Supply_Air,bool,,,,Low supply air temperature alarm
|
||||
Discrete_Input,100131,Fan_Alarm1,bool,000131,,,Fan Alarm 1
|
||||
Coil,000131,_Fan_Alarm1,bool,,,,Fan Alarm 1
|
||||
Discrete_Input,100132,Fan_Alarm2,bool,000132,,,Fan Alarm 2
|
||||
Coil,000132,_Fan_Alarm2,bool,,,,Fan Alarm 2
|
||||
Discrete_Input,100133,Fan_Alarm3,bool,000133,,,Fan Alarm 3
|
||||
Coil,000133,_Fan_Alarm3,bool,,,,Fan Alarm 3
|
||||
Discrete_Input,100134,Fan_Alarm4,bool,000134,,,Fan Alarm 4
|
||||
Coil,000134,_Fan_Alarm4,bool,,,,Fan Alarm 4
|
||||
Discrete_Input,100135,Fan_Alarm5,bool,000135,,,Fan Alarm 5
|
||||
Coil,000135,_Fan_Alarm5,bool,,,,Fan Alarm 5
|
||||
Discrete_Input,100136,Fan_Alarm6,bool,000136,,,Fan Alarm 6
|
||||
Coil,000136,_Fan_Alarm6,bool,,,,Fan Alarm 6
|
||||
Discrete_Input,100146,Supply_Sensor_Failure_Alarm,bool,000146,,,Supply air temperature sensor fault
|
||||
Coil,000146,_Supply_Sensor_Failure_Alarm,bool,,,,Supply air temperature sensor fault
|
||||
Discrete_Input,101096,Filter_Alarm,bool,001096,,,Dirty filter alarm
|
||||
Coil,001096,_Filter_Alarm,bool,,,,Dirty filter alarm
|
||||
Discrete_Input,101099,Low_Temperature_Return_Air,bool,001099,,,Low return air temperature alarm
|
||||
Coil,001099,_Low_Temperature_Return_Air,bool,,,,Low return air temperature alarm
|
||||
Discrete_Input,101245,Return_Sensor_Failure_Alarm,bool,001245,,,Return air temperature sensor fault
|
||||
Coil,001245,_Return_Sensor_Failure_Alarm,bool,,,,Return air temperature sensor fault
|
||||
Discrete_Input,101246,Humidity_Sensor_Failure_Alarm,bool,001246,,,Return air humidity sensor fault
|
||||
Coil,001246,_Humidity_Sensor_Failure_Alarm,bool,,,,Return air humidity sensor fault
|
||||
Discrete_Input,101250,Filter_Diff_Press_Sensor_Failure,bool,001250,,,Filter differential pressure sensor fault
|
||||
Coil,001250,_Filter_Diff_Press_Sensor_Failure,bool,,,,Filter differential pressure sensor fault
|
||||
Discrete_Input,101307,High_Humidity_Return_Air,bool,001307,,,High return air humidity alarm
|
||||
Coil,001307,_High_Humidity_Return_Air,bool,,,,High return air humidity alarm
|
||||
Discrete_Input,101308,Low_Humidity_Return_Air,bool,001308,,,Low return air humidity alarm
|
||||
Coil,001308,_Low_Humidity_Return_Air,bool,,,,Low return air humidity alarm
|
||||
Discrete_Input,101342,Common_Alarm,bool,001342,,,Common alarm status
|
||||
Coil,001342,_Common_Alarm,bool,,,,Common alarm status
|
||||
Discrete_Input,101360,Fan_Alarm7,bool,001360,,,Fan Alarm 7
|
||||
Coil,001360,_Fan_Alarm7,bool,,,,Fan Alarm 7
|
||||
Discrete_Input,101361,Fan_Alarm8,bool,001361,,,Fan Alarm 8
|
||||
Coil,001361,_Fan_Alarm8,bool,,,,Fan Alarm 8
|
||||
Discrete_Input,101362,Fan_Alarm9,bool,001362,,,Fan Alarm 9
|
||||
Coil,001362,_Fan_Alarm9,bool,,,,Fan Alarm 9
|
||||
Discrete_Input,101367,High_Temperature_Return_Air,bool,001367,,,High return air temperature alarm
|
||||
Coil,001367,_High_Temperature_Return_Air,bool,,,,High return air temperature alarm
|
||||
Discrete_Input,101368,Smoke_Detected,bool,001368,,,Smoke alarm status
|
||||
Coil,001368,_Smoke_Detected,bool,,,,Smoke alarm status
|
||||
Discrete_Input,101369,Fire_SD_Alarm,bool,001369,,,Fire alarm status
|
||||
Coil,001369,_Fire_SD_Alarm,bool,,,,Fire alarm status
|
||||
Discrete_Input,101370,Cond_Pump_Fail,bool,001370,,,Condensate pump alarm status
|
||||
Coil,001370,_Cond_Pump_Fail,bool,,,,Condensate pump alarm status
|
||||
,,,,,,,
|
||||
,,,,,,,
|
||||
Input_Register,300053,Fan1_Speed,uint16,430053,,,Speed-EC FAN#1
|
||||
Holding_Register,430053,_Fan1_Speed,uint16,,410001,Integer,Speed-EC FAN#1
|
||||
Input_Register,300070,Return_Humidity,float,430070,,,Return air humidity reading
|
||||
Holding_Register,430070,_Return_Humidity,float,,410005,Float,Return air humidity reading
|
||||
Input_Register,300099,Air_Supply_Temp,uint32,430099,,,Supply air temperature reading
|
||||
Holding_Register,430099,_Air_Supply_Temp,uint32,,410009,Float,Supply air temperature reading
|
||||
Input_Register,300101,Air_Return_Temp,float,430101,,,Return air temperature
|
||||
Holding_Register,430101,_Air_Return_Temp,float,,410013,Float,Return air temperature
|
||||
Input_Register,300106,Supply_Filter_Diff_Press,float,430106,,,
|
||||
Holding_Register,430106,_Supply_Filter_Diff_Press,float,,410017,Float,
|
||||
Input_Register,300228,Fan2_Speed,uint16,430228,,,Speed-EC FAN#2
|
||||
Holding_Register,430228,_Fan2_Speed,uint16,,410021,Integer,Speed-EC FAN#2
|
||||
Input_Register,300229,Fan3_Speed,uint16,430229,,,Speed-EC FAN#3
|
||||
Holding_Register,430229,_Fan3_Speed,uint16,,410025,Integer,Speed-EC FAN#3
|
||||
Input_Register,300230,Fan4_Speed,uint16,430243,,,Speed-EC FAN#4
|
||||
Holding_Register,430243,_Fan4_Speed,uint16,,410029,Integer,Speed-EC FAN#4
|
||||
Input_Register,300231,Fan5_Speed,uint16,430231,,,Speed-EC FAN#5
|
||||
Holding_Register,430231,_Fan5_Speed,uint16,,410033,Integer,Speed-EC FAN#5
|
||||
Input_Register,300232,Fan6_Speed,uint16,430232,,,Speed-EC FAN#6
|
||||
Holding_Register,430232,_Fan6_Speed,uint16,,410037,Integer,Speed-EC FAN#6
|
||||
Input_Register,300233,Fan2_Hrs,uint16,430233,,,Operating hours-EC FAN#2
|
||||
Holding_Register,430233,_Fan2_Hrs,uint16,,410041,Integer,Operating hours-EC FAN#2
|
||||
Input_Register,300235,Fan4_Hrs,uint16,430235,,,Operating hours-EC FAN#4
|
||||
Holding_Register,430235,_Fan4_Hrs,uint16,,410045,Integer,Operating hours-EC FAN#4
|
||||
Input_Register,300236,Fan5_Hrs,uint16,430236,,,Operating hours-EC FAN#5
|
||||
Holding_Register,430236,_Fan5_Hrs,uint16,,410049,Integer,Operating hours-EC FAN#5
|
||||
Input_Register,300244,Fan3_Hrs,uint16,430244,,,Operating hours-EC FAN#3
|
||||
Holding_Register,430244,_Fan3_Hrs,uint16,,410053,Integer,Operating hours-EC FAN#3
|
||||
Input_Register,300245,Fan6_Hrs,uint16,430245,,,Operating hours-EC FAN#6
|
||||
Holding_Register,430245,_Fan6_Hrs,uint16,,410057,Integer,Operating hours-EC FAN#6
|
||||
Input_Register,300274,Fan1_Hrs,uint16,430274,,,Operating hours-EC FAN#1
|
||||
Holding_Register,430274,_Fan1_Hrs,uint16,,410061,Integer,Operating hours-EC FAN#1
|
||||
Input_Register,300486,Fan7_Hrs,uint16,430486,,,Operating hours-EC FAN#7
|
||||
Holding_Register,430486,_Fan7_Hrs,uint16,,410065,Integer,Operating hours-EC FAN#7
|
||||
Input_Register,300487,Fan8_Hrs,uint16,430487,,,Operating hours-EC FAN#8
|
||||
Holding_Register,430487,_Fan8_Hrs,uint16,,410069,Integer,Operating hours-EC FAN#8
|
||||
Input_Register,300488,Fan9_Hrs,uint16,430488,,,Operating hours-EC FAN#9
|
||||
Holding_Register,430488,_Fan9_Hrs,uint16,,410073,Integer,Operating hours-EC FAN#9
|
||||
Input_Register,300496,Cooling_Valve_Output,float,430496,,,Chilled water valve feedback signal
|
||||
Holding_Register,430496,_Cooling_Valve_Output,float,,410077,Float,Chilled water valve feedback signal
|
||||
Input_Register,300678,Fan7_Speed,uint16,430678,,,Speed-EC FAN#7
|
||||
Holding_Register,430678,_Fan7_Speed,uint16,,410081,Integer,Speed-EC FAN#7
|
||||
Input_Register,300679,Fan8_Speed,uint16,430679,,,Speed-EC FAN#8
|
||||
Holding_Register,430679,_Fan8_Speed,uint16,,410085,Integer,Speed-EC FAN#8
|
||||
Input_Register,300680,Fan9_Speed,uint16,430680,,,Speed-EC FAN#9
|
||||
Holding_Register,430680,_Fan9_Speed,uint16,,410089,Integer,Speed-EC FAN#9
|
||||
,,,,,,,
|
||||
,,,,,,,
|
||||
Holding_Register,400005,Fan_Speed_Max_SP,float,,410097,Float,Setting the EC fan maximum speed
|
||||
,,,,,,,
|
||||
Holding_Register,40029,Fan_Speed,float,,410101,Float,Fan Speed Feedback
|
||||
,,,,,,,
|
||||
Holding_Register,400111,Air_Return_Temp_Alm_Hi_SP,float,,410105,Float,High return air temperature alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400114,Air_Return_Temp_Alm_Lo_SP,float,,410109,Float,Low return air temperature alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400118,Air_Supply_Temp_Alm_Hi_SP,float,,410113,Float,High supply air temperature alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400122,Air_Supply_Temp_Alm_Lo_SP,float,,410117,Float,Low supply air temperature alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400681,Air_Return_Temp_SP,float,,410121,Float,Return air temperature setpoint
|
||||
,,,,,,,
|
||||
Holding_Register,400685,Return_Humidity_Alm_Hi_SP,float,,410125,Float,High return air humidity alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400689,Return_Humidity_Alm_Lo_SP,float,,410129,Float,Low return air humidity alarm limit
|
||||
,,,,,,,
|
||||
Holding_Register,400693,Space_Temp_SP,float,,410133,Float,Setting the room temperature
|
||||
,,,,,,,
|
||||
Holding_Register,400695,Fan_Speed_Min_SP,float,,410137,Float,Setting the EC fan minimum speed
|
||||
,,,,,,,
|
||||
Coil,000301,BMS_StartStop,bool,,,,
|
||||
|