| 1 | type | address | name | data_type | control_address | pics_address | pics_data_type | notes |
|---|---|---|---|---|---|---|---|---|
| 2 | Discrete_Input | 100051 | Water_Detected_Alarm | bool | 000051 | Unit flooding detector alarm | ||
| 3 | Coil | 000051 | _Water_Detected_Alarm | bool | Unit flooding detector alarm | |||
| 4 | Discrete_Input | 100118 | High_Temperature_Supply_Air | bool | 000118 | High supply air temperature alarm | ||
| 5 | Coil | 000118 | _High_Temperature_Supply_Air | bool | High supply air temperature alarm | |||
| 6 | Discrete_Input | 100122 | Low_Temperature_Supply_Air | bool | 000122 | Low supply air temperature alarm | ||
| 7 | Coil | 000122 | _Low_Temperature_Supply_Air | bool | Low supply air temperature alarm | |||
| 8 | Discrete_Input | 100131 | Fan_Alarm1 | bool | 000131 | Fan Alarm 1 | ||
| 9 | Coil | 000131 | _Fan_Alarm1 | bool | Fan Alarm 1 | |||
| 10 | Discrete_Input | 100132 | Fan_Alarm2 | bool | 000132 | Fan Alarm 2 | ||
| 11 | Coil | 000132 | _Fan_Alarm2 | bool | Fan Alarm 2 | |||
| 12 | Discrete_Input | 100133 | Fan_Alarm3 | bool | 000133 | Fan Alarm 3 | ||
| 13 | Coil | 000133 | _Fan_Alarm3 | bool | Fan Alarm 3 | |||
| 14 | Discrete_Input | 100134 | Fan_Alarm4 | bool | 000134 | Fan Alarm 4 | ||
| 15 | Coil | 000134 | _Fan_Alarm4 | bool | Fan Alarm 4 | |||
| 16 | Discrete_Input | 100135 | Fan_Alarm5 | bool | 000135 | Fan Alarm 5 | ||
| 17 | Coil | 000135 | _Fan_Alarm5 | bool | Fan Alarm 5 | |||
| 18 | Discrete_Input | 100136 | Fan_Alarm6 | bool | 000136 | Fan Alarm 6 | ||
| 19 | Coil | 000136 | _Fan_Alarm6 | bool | Fan Alarm 6 | |||
| 20 | Discrete_Input | 100146 | Supply_Sensor_Failure_Alarm | bool | 000146 | Supply air temperature sensor fault | ||
| 21 | Coil | 000146 | _Supply_Sensor_Failure_Alarm | bool | Supply air temperature sensor fault | |||
| 22 | Discrete_Input | 101096 | Filter_Alarm | bool | 001096 | Dirty filter alarm | ||
| 23 | Coil | 001096 | _Filter_Alarm | bool | Dirty filter alarm | |||
| 24 | Discrete_Input | 101099 | Low_Temperature_Return_Air | bool | 001099 | Low return air temperature alarm | ||
| 25 | Coil | 001099 | _Low_Temperature_Return_Air | bool | Low return air temperature alarm | |||
| 26 | Discrete_Input | 101245 | Return_Sensor_Failure_Alarm | bool | 001245 | Return air temperature sensor fault | ||
| 27 | Coil | 001245 | _Return_Sensor_Failure_Alarm | bool | Return air temperature sensor fault | |||
| 28 | Discrete_Input | 101246 | Humidity_Sensor_Failure_Alarm | bool | 001246 | Return air humidity sensor fault | ||
| 29 | Coil | 001246 | _Humidity_Sensor_Failure_Alarm | bool | Return air humidity sensor fault | |||
| 30 | Discrete_Input | 101250 | Filter_Diff_Press_Sensor_Failure | bool | 001250 | Filter differential pressure sensor fault | ||
| 31 | Coil | 001250 | _Filter_Diff_Press_Sensor_Failure | bool | Filter differential pressure sensor fault | |||
| 32 | Discrete_Input | 101307 | High_Humidity_Return_Air | bool | 001307 | High return air humidity alarm | ||
| 33 | Coil | 001307 | _High_Humidity_Return_Air | bool | High return air humidity alarm | |||
| 34 | Discrete_Input | 101308 | Low_Humidity_Return_Air | bool | 001308 | Low return air humidity alarm | ||
| 35 | Coil | 001308 | _Low_Humidity_Return_Air | bool | Low return air humidity alarm | |||
| 36 | Discrete_Input | 101342 | Common_Alarm | bool | 001342 | Common alarm status | ||
| 37 | Coil | 001342 | _Common_Alarm | bool | Common alarm status | |||
| 38 | Discrete_Input | 101360 | Fan_Alarm7 | bool | 001360 | Fan Alarm 7 | ||
| 39 | Coil | 001360 | _Fan_Alarm7 | bool | Fan Alarm 7 | |||
| 40 | Discrete_Input | 101361 | Fan_Alarm8 | bool | 001361 | Fan Alarm 8 | ||
| 41 | Coil | 001361 | _Fan_Alarm8 | bool | Fan Alarm 8 | |||
| 42 | Discrete_Input | 101362 | Fan_Alarm9 | bool | 001362 | Fan Alarm 9 | ||
| 43 | Coil | 001362 | _Fan_Alarm9 | bool | Fan Alarm 9 | |||
| 44 | Discrete_Input | 101367 | High_Temperature_Return_Air | bool | 001367 | High return air temperature alarm | ||
| 45 | Coil | 001367 | _High_Temperature_Return_Air | bool | High return air temperature alarm | |||
| 46 | Discrete_Input | 101368 | Smoke_Detected | bool | 001368 | Smoke alarm status | ||
| 47 | Coil | 001368 | _Smoke_Detected | bool | Smoke alarm status | |||
| 48 | Discrete_Input | 101369 | Fire_SD_Alarm | bool | 001369 | Fire alarm status | ||
| 49 | Coil | 001369 | _Fire_SD_Alarm | bool | Fire alarm status | |||
| 50 | Discrete_Input | 101370 | Cond_Pump_Fail | bool | 001370 | Condensate pump alarm status | ||
| 51 | Coil | 001370 | _Cond_Pump_Fail | bool | Condensate pump alarm status | |||
| 52 | ||||||||
| 53 | ||||||||
| 54 | Input_Register | 300053 | Fan1_Speed | uint16 | 430053 | Speed-EC FAN#1 | ||
| 55 | Holding_Register | 430053 | _Fan1_Speed | uint16 | 410001 | Integer | Speed-EC FAN#1 | |
| 56 | Input_Register | 300070 | Return_Humidity | float | 430070 | Return air humidity reading | ||
| 57 | Holding_Register | 430070 | _Return_Humidity | float | 410005 | Float | Return air humidity reading | |
| 58 | Input_Register | 300099 | Air_Supply_Temp | uint32 | 430099 | Supply air temperature reading | ||
| 59 | Holding_Register | 430099 | _Air_Supply_Temp | uint32 | 410009 | Float | Supply air temperature reading | |
| 60 | Input_Register | 300101 | Air_Return_Temp | float | 430101 | Return air temperature | ||
| 61 | Holding_Register | 430101 | _Air_Return_Temp | float | 410013 | Float | Return air temperature | |
| 62 | Input_Register | 300106 | Supply_Filter_Diff_Press | float | 430106 | |||
| 63 | Holding_Register | 430106 | _Supply_Filter_Diff_Press | float | 410017 | Float | ||
| 64 | Input_Register | 300228 | Fan2_Speed | uint16 | 430228 | Speed-EC FAN#2 | ||
| 65 | Holding_Register | 430228 | _Fan2_Speed | uint16 | 410021 | Integer | Speed-EC FAN#2 | |
| 66 | Input_Register | 300229 | Fan3_Speed | uint16 | 430229 | Speed-EC FAN#3 | ||
| 67 | Holding_Register | 430229 | _Fan3_Speed | uint16 | 410025 | Integer | Speed-EC FAN#3 | |
| 68 | Input_Register | 300230 | Fan4_Speed | uint16 | 430243 | Speed-EC FAN#4 | ||
| 69 | Holding_Register | 430243 | _Fan4_Speed | uint16 | 410029 | Integer | Speed-EC FAN#4 | |
| 70 | Input_Register | 300231 | Fan5_Speed | uint16 | 430231 | Speed-EC FAN#5 | ||
| 71 | Holding_Register | 430231 | _Fan5_Speed | uint16 | 410033 | Integer | Speed-EC FAN#5 | |
| 72 | Input_Register | 300232 | Fan6_Speed | uint16 | 430232 | Speed-EC FAN#6 | ||
| 73 | Holding_Register | 430232 | _Fan6_Speed | uint16 | 410037 | Integer | Speed-EC FAN#6 | |
| 74 | Input_Register | 300233 | Fan2_Hrs | uint16 | 430233 | Operating hours-EC FAN#2 | ||
| 75 | Holding_Register | 430233 | _Fan2_Hrs | uint16 | 410041 | Integer | Operating hours-EC FAN#2 | |
| 76 | Input_Register | 300235 | Fan4_Hrs | uint16 | 430235 | Operating hours-EC FAN#4 | ||
| 77 | Holding_Register | 430235 | _Fan4_Hrs | uint16 | 410045 | Integer | Operating hours-EC FAN#4 | |
| 78 | Input_Register | 300236 | Fan5_Hrs | uint16 | 430236 | Operating hours-EC FAN#5 | ||
| 79 | Holding_Register | 430236 | _Fan5_Hrs | uint16 | 410049 | Integer | Operating hours-EC FAN#5 | |
| 80 | Input_Register | 300244 | Fan3_Hrs | uint16 | 430244 | Operating hours-EC FAN#3 | ||
| 81 | Holding_Register | 430244 | _Fan3_Hrs | uint16 | 410053 | Integer | Operating hours-EC FAN#3 | |
| 82 | Input_Register | 300245 | Fan6_Hrs | uint16 | 430245 | Operating hours-EC FAN#6 | ||
| 83 | Holding_Register | 430245 | _Fan6_Hrs | uint16 | 410057 | Integer | Operating hours-EC FAN#6 | |
| 84 | Input_Register | 300274 | Fan1_Hrs | uint16 | 430274 | Operating hours-EC FAN#1 | ||
| 85 | Holding_Register | 430274 | _Fan1_Hrs | uint16 | 410061 | Integer | Operating hours-EC FAN#1 | |
| 86 | Input_Register | 300486 | Fan7_Hrs | uint16 | 430486 | Operating hours-EC FAN#7 | ||
| 87 | Holding_Register | 430486 | _Fan7_Hrs | uint16 | 410065 | Integer | Operating hours-EC FAN#7 | |
| 88 | Input_Register | 300487 | Fan8_Hrs | uint16 | 430487 | Operating hours-EC FAN#8 | ||
| 89 | Holding_Register | 430487 | _Fan8_Hrs | uint16 | 410069 | Integer | Operating hours-EC FAN#8 | |
| 90 | Input_Register | 300488 | Fan9_Hrs | uint16 | 430488 | Operating hours-EC FAN#9 | ||
| 91 | Holding_Register | 430488 | _Fan9_Hrs | uint16 | 410073 | Integer | Operating hours-EC FAN#9 | |
| 92 | Input_Register | 300496 | Cooling_Valve_Output | float | 430496 | Chilled water valve feedback signal | ||
| 93 | Holding_Register | 430496 | _Cooling_Valve_Output | float | 410077 | Float | Chilled water valve feedback signal | |
| 94 | Input_Register | 300678 | Fan7_Speed | uint16 | 430678 | Speed-EC FAN#7 | ||
| 95 | Holding_Register | 430678 | _Fan7_Speed | uint16 | 410081 | Integer | Speed-EC FAN#7 | |
| 96 | Input_Register | 300679 | Fan8_Speed | uint16 | 430679 | Speed-EC FAN#8 | ||
| 97 | Holding_Register | 430679 | _Fan8_Speed | uint16 | 410085 | Integer | Speed-EC FAN#8 | |
| 98 | Input_Register | 300680 | Fan9_Speed | uint16 | 430680 | Speed-EC FAN#9 | ||
| 99 | Holding_Register | 430680 | _Fan9_Speed | uint16 | 410089 | Integer | Speed-EC FAN#9 | |
| 100 | ||||||||
| 101 | ||||||||
| 102 | Holding_Register | 400005 | Fan_Speed_Max_SP | float | 410097 | Float | Setting the EC fan maximum speed | |
| 103 | ||||||||
| 104 | Holding_Register | 40029 | Fan_Speed | float | 410101 | Float | Fan Speed Feedback | |
| 105 | ||||||||
| 106 | Holding_Register | 400111 | Air_Return_Temp_Alm_Hi_SP | float | 410105 | Float | High return air temperature alarm limit | |
| 107 | ||||||||
| 108 | Holding_Register | 400114 | Air_Return_Temp_Alm_Lo_SP | float | 410109 | Float | Low return air temperature alarm limit | |
| 109 | ||||||||
| 110 | Holding_Register | 400118 | Air_Supply_Temp_Alm_Hi_SP | float | 410113 | Float | High supply air temperature alarm limit | |
| 111 | ||||||||
| 112 | Holding_Register | 400122 | Air_Supply_Temp_Alm_Lo_SP | float | 410117 | Float | Low supply air temperature alarm limit | |
| 113 | ||||||||
| 114 | Holding_Register | 400681 | Air_Return_Temp_SP | float | 410121 | Float | Return air temperature setpoint | |
| 115 | ||||||||
| 116 | Holding_Register | 400685 | Return_Humidity_Alm_Hi_SP | float | 410125 | Float | High return air humidity alarm limit | |
| 117 | ||||||||
| 118 | Holding_Register | 400689 | Return_Humidity_Alm_Lo_SP | float | 410129 | Float | Low return air humidity alarm limit | |
| 119 | ||||||||
| 120 | Holding_Register | 400693 | Space_Temp_SP | float | 410133 | Float | Setting the room temperature | |
| 121 | ||||||||
| 122 | Holding_Register | 400695 | Fan_Speed_Min_SP | float | 410137 | Float | Setting the EC fan minimum speed | |
| 123 | ||||||||
| 124 | Coil | 000301 | BMS_StartStop | bool |