# Datahall CRAH UMAS 10FSV041206-058-117.00x114.00 TCP
|
||||
|
||||
## Brief Introduction
|
||||
This is first of a kind CRAH, so Modbus maps are different.
|
||||
BMS Control Source (0:speed, 1:external room temp) and
|
||||
BMS Enable Source (0:keypad, 1:DI, 2:BMS) sent from PLC/Modscan
|
||||
PLC code for these CRAHs use Speed Control, i.e. Speed Setpoint sent from PLC/BMS.
|
||||
Return Air is generally not used for control during normal operation.
|
||||
Leak Detect alarm is the only alarm that will send unit to FailState.
|
||||
This is a (9) fan array CRAH unit.
|
||||
|
||||
## List of Equipmentt
|
||||
This cofiguration has been used for these models:
|
||||
* **Model: 10FSV041206-058-117.00x114.00**: 10-07-25
|
||||
|
||||
## Hardware Prerequisites
|
||||
|
||||
The code is written for an ESP8266/ESP32-style microcontroller with WiFi capabilities.
|
||||
* **Microcontroller**: [Firebeetle 2 ESP32.](https://www.dfrobot.com/product-2231.html)
|
||||
|
||||
---
|
||||
|
||||
## States and Strategies
|
||||
Provide a brief description of what variables and strategies were used in this configuraiton
|
||||
|
||||
### Standby State
|
||||
* **CW valve**: **Ramp Strategy** ramp to 0
|
||||
* **Supply Air temperature**: **Ramp Strategy** ramp to 74
|
||||
* **Return Air temperature**: **Ramp Strategy** ramp to 86
|
||||
* **Fan speeds**: **Ramp Strategy** ramp to 0
|
||||
* **Fan amps**: **Ramp Strategy** ramp to 0
|
||||
* **Fan run status**: set to 0
|
||||
|
||||
### Running State
|
||||
* **Fan run status**: set to 1
|
||||
* **Fan min speed**: initialized to 30
|
||||
* **Fan max speed**: initialized to 100
|
||||
* **Fan speed**: **Ramp Strategy** dynamically ramps to speed setpoint
|
||||
* **Fan amps**: **Ramp Strategy** ramp to 15
|
||||
* **Fan operating hours**: initialize totalizers
|
||||
* **Supply air temperature**: **Saw Strategy** ramps back and forth between 60 and 100 deg
|
||||
* **CW valve**: **PID Strategy** adjusts until Supply Air Temperature matches Supply Air Temperature setpoint
|
||||
|
||||
### Fail State
|
||||
* **Fan run status**: set to 0
|
||||
* **CW valve**: **Ramp Strategy** ramp to 0
|
||||
* **Fan speeds**: **Ramp Strategy** ramp to 0
|
||||
* **Fan amps**: **Ramp Strategy** ramp to 0
|
||||