@@ -1,33 +0,0 @@
# EQUIPMENT_TYPE MANUFACTURER MODEL TCP
## Brief Introduction
Equipment specifc details that make it different from other devices
## List of Equipmentt
This cofiguration has been used for these models:
* **Model**: 09-15-22
* **Model**: 09-15-23
* **Model**: 09-15-25
## Hardware Prerequisites
The code is written for an ESP8266/ESP32-style microcontroller with WiFi capabilities.
* **Microcontroller**: [Firebeetle 2 ESP32.](https://www.dfrobot.com/product-2231.html)
---
## States and Strategies
Provide a brief description of what variables and strategies were used in this configuraiton
### Standby State
* **Equipment running**: set to 0
* **Common Alarm**: set to 0
* **SAT temperature**: set to 85
### Running State
* **Equipment running**: set to 1
* **SAT temperature**: **Ramp Strategy** set to 65 deg setpoint
### Fail State
* **Commong Alarm**: set to 1
* **SAT temperature**: **Ramp Strategy** set to 105 deg setpointset

View File

@@ -1,81 +0,0 @@
/**
* @file State_Fail.cpp
* @brief Implementation of the FailState class.
* @author Emmanuel Hernandez Cruz
* @date 2025-09-05
*
* This file contains the implementation for the FailState, which defines
* the behavior of the equipment when it has entered a fault condition.
*/
#include "ModbusPoints/Modbus_Point.h"
#include "Equipment/Equipment.h"
#include "Strategies/Strategy_Ramp.h"
#include "Strategies/Strategy_SingleValue.h"
#include "Strategies/Strategy_PID.h"
#include "States/State_Standby.h"
#include "States/State_Running.h"
#include "States/State_Fail.h"
#if defined(USE_MODBUS_IP)
#include <ModbusIP_ESP8266.h>
#else
#include <ModbusRTU.h>
#endif
/**
* @brief Constructs a new FailState object with a list of active alarms.
*
* This constructor receives a list of alarm descriptions and creates strategies
* to set the corresponding Modbus points to a value of 1, indicating an
* active alarm. It also initializes a PID strategy for the 'CW Valve Position'
* to maintain its state during the fault.
* @param activeAlarms A vector of strings, where each string is the
* description of a Modbus point to be set as an active alarm.
*/
template<>
FailState<ModbusIP>::FailState(const std::vector<std::string>& activeAlarms) {
// Simulate a failure: set common alarm and a specific fan alarm.
}
/**
* @brief Executes the fail state's logic for one update cycle.
*
* This method checks the "Alarm Reset" Modbus point for a command to
* transition back to Standby, which would typically happen after a fault
* is cleared by a user. If no transition is requested, it continues to apply
* the failure strategies (e.g., keeping alarm bits active).
*
* @param equipment Pointer to the Equipment instance.
* @return A pointer to a new State if a transition should occur, otherwise nullptr.
*/
template<>
State<ModbusIP>* FailState<ModbusIP>::update(Equipment<ModbusIP>* equipment) {
// STATE control, add conditions if change to a different state is needed
Serial.println("Fail update function");
_applyStrategies(equipment);
return nullptr;
}
/**
* @brief Logic to execute once when entering the fail state.
* Sets the "Alarm Common" point to 1 to indicate a general fault condition.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void FailState<ModbusIP>::enterState(Equipment<ModbusIP>* equipment) {
// Logic to run when the equipment enters this state
Serial.println("Enter Fail State...");
}
/**
* @brief Logic to execute once when exiting the fail state.
* Clears the "Alarm Common" point to 0 before transitioning to the next state.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void FailState<ModbusIP>::exitState(Equipment<ModbusIP>* equipment) {
// Cleanup logic to run when the equipment leaves this state
Serial.println("Exit Fail State...");
}

View File

@@ -1,89 +0,0 @@
/**
* @file State_Running.cpp
* @brief Implementation of the RunningState class.
* @author Emmanuel Hernandez Cruz
* @date 2025-09-05
*
* This file contains the implementation for the RunningState, which defines
* the behavior of the equipment when it is actively running.
*/
#include "ModbusPoints/Modbus_Point.h"
#include "ModbusPoints/Modbus_FloatDecorator.h"
#include "Equipment/Equipment.h"
#include "Strategies/Strategy_Ramp.h"
#include "Strategies/Strategy_Random.h"
#include "Strategies/Strategy_Saw.h"
#include "Strategies/Strategy_SingleValue.h"
#include "Strategies/Strategy_Square.h"
#include "Strategies/Strategy_PID.h"
#include "Strategies/Strategy_Totalizer.h"
#include "States/State_Standby.h"
#include "States/State_Running.h"
#include "States/State_Fail.h"
#include "States/State.h"
#include <vector>
#include <string>
#if defined(USE_MODBUS_IP)
#include <ModbusIP_ESP8266.h>
#else
#include <ModbusRTU.h>
#endif
/**
* @brief Constructs a new RunningState object.
*
* This constructor initializes behavior strategies active during the running
* state, such as a PID controller for the 'CW Valve Position' and totalizers
* for the run-hours of each EC fan.
*/
template<>
RunningState<ModbusIP>::RunningState() {
}
/**
* @brief Executes the running state's logic for one update cycle.
*
* This method first checks for state transition commands:
* 1. It reads the "ON/OFF Command By BMS" point. If it's 0, it transitions to StandbyState.
* 2. It reads the "Fault Code" point. If it's non-zero, it transitions to FailState,
* passing the corresponding alarm description.
*
* If no transition occurs, it applies the strategies defined for the running state.
*
* @param equipment Pointer to the Equipment instance.
* @return A pointer to a new State if a transition should occur, otherwise nullptr.
*/
template<>
State<ModbusIP>* RunningState<ModbusIP>::update(Equipment<ModbusIP>* equipment) {
// STATE control, add conditions if change to a different state is needed
Serial.println("Running update function");
// Apply any strategies defined for the standby state
_applyStrategies(equipment);
return nullptr;
}
/**
* @brief Logic to execute once when entering the running state.
* Sets the "Run Status" for all EC fans to 1 to indicate they are active.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void RunningState<ModbusIP>::enterState(Equipment<ModbusIP>* equipment) {
// Logic to run when the equipment enters this state
Serial.println("Enter Running State...");
// You could also update a Modbus register to show the "standby" state
}
/**
* @brief Logic to execute once when exiting the running state.
* Sets the "Run Status" for all EC fans to 0 before transitioning to the next state.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void RunningState<ModbusIP>::exitState(Equipment<ModbusIP>* equipment) {
// Cleanup logic to run when the equipment leaves this state
Serial.println("Exit Running State...");
}

View File

@@ -1,85 +0,0 @@
/**
* @file State_Standby.cpp
* @brief Implementation of the StandbyState class.
* @author Emmanuel Hernandez Cruz
* @date 2025-09-05
*
* This file contains the implementation for the StandbyState, which defines
* the behavior of the equipment when it is in an idle or standby mode.
*/
#include "ModbusPoints/Modbus_Point.h"
#include "ModbusPoints/Modbus_FloatDecorator.h"
#include "Equipment/Equipment.h"
#include "Strategies/Strategy_Ramp.h"
#include "Strategies/Strategy_Random.h"
#include "Strategies/Strategy_Saw.h"
#include "Strategies/Strategy_SingleValue.h"
#include "Strategies/Strategy_Square.h"
#include "Strategies/Strategy_PID.h"
#include "States/State_Standby.h"
#include "States/State_Running.h"
#include "States/State_Fail.h"
#include "States/State.h"
#include <vector>
#include <string>
#if defined(USE_MODBUS_IP)
#include <ModbusIP_ESP8266.h>
#else
#include <ModbusRTU.h>
#endif
/**
* @brief Constructs a new StandbyState object.
*
* In this state, the equipment is idle. This constructor initializes strategies
* to bring the system to a safe, idle condition. It sets a stable value for
* the SAT reading and creates ramp strategies to bring the CW valve and all
* EC fan speeds down to zero.
*/
template<>
StandbyState<ModbusIP>::StandbyState() {
// You can add initialization code here if needed
}
/**
* @brief Executes the standby state's logic for one update cycle.
*
* This method applies the strategies defined for the standby state (e.g.,
* ramping values to zero).
*
* @warning This method currently does not check for a command to transition to the
* Running state. This logic needs to be added to allow the unit to start.
* @return A pointer to a new State if a transition should occur, otherwise nullptr.
*/
template<>
State<ModbusIP>* StandbyState<ModbusIP>::update(Equipment<ModbusIP>* equipment) {
// STATE control, add conditions if change to a different state is needed
Serial.println("Standby update function");
// Apply any strategies defined for the standby state
_applyStrategies(equipment);
return nullptr;
}
/**
* @brief Logic to execute once when entering the standby state.
* This method performs cleanup by setting all alarm points and all EC fan
* run status points to 0.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void StandbyState<ModbusIP>::enterState(Equipment<ModbusIP>* equipment) {
// Logic to run when the equipment enters this state
Serial.println("Enter Standby State...");
}
/**
* @brief Logic to execute once when exiting the standby state.
* @param equipment Pointer to the Equipment instance.
*/
template<>
void StandbyState<ModbusIP>::exitState(Equipment<ModbusIP>* equipment) {
// Cleanup logic to run when the equipment leaves this state
Serial.println("Exit Standby State...");
}

View File

@@ -1,94 +0,0 @@
/**
* @file config.h
* @brief Main configuration file for the CRAH Unit (TCP) emulator.
* @author Emmanuel Hernandez Cruz
* @date 2025-09-02
*
* This file contains two important configurations: WiFi network parameters
* and the Modbus register map for the device.
*/
#ifndef CONFIG_H
#define CONFIG_H
#include "core.h"
#include "Equipment/Equipment.h"
#if defined(USE_MODBUS_IP)
/**
* @defgroup ModbusTCPConfig Modbus IP Configuration
* @brief Parameters for Modbus TCP communication.
* @{
*/
#include <ModbusIP_ESP8266.h>
const char *ssid = "wifi_name"; /**< @brief The SSID of the WiFi network. */
const char *password = "wifi_password"; /**< @brief The password for the WiFi network. */
IPAddress local_IP(192, 168, 1, 234); /**< @brief The static IP address for the device. */
IPAddress gateway(192, 168, 1, 1); /**< @brief The gateway IP address. */
IPAddress subnet(255, 255, 255, 0); /**< @brief The subnet mask. */
ModbusIP mb;
#else
/**
* @defgroup ModbusRTUConfig Modbus RTU Configuration
* @brief Parameters for serial Modbus RTU communication.
* @{
*/
#include <ModbusRTU.h>
const int BAUDRATE = 19200; /**< @brief The serial communication speed in bits per second. */
const int RX_PIN = 17; /**< @brief The GPIO pin used for receiving data (RX). */
const int TX_PIN = 16; /**< @brief The GPIO pin used for transmitting data (TX). */
const int RST_PIN = 4; /**< @brief The GPIO pin connected to the RS485 driver's DE/RE pins for direction control. */
const int MODBUS_ID = 1; /**< @brief The unique slave ID for this device on the Modbus bus. */
/** @} */
/** @brief Global instance of the Modbus RTU server. */
ModbusRTU mb;
#endif
/**
* @defgroup ModbusMapConfig Modbus Map Configuration
* @brief Defines the Modbus register map and related parameters for the emulator.
* @{
*/
/**
* @brief The Modbus map for the Equipment device.
* This array defines all the Modbus points available on the emulated device.
* The `description` field is crucial as it's used to look up points within the application logic.
*/
modbusMap mb_map[] =
{
{HR, 15, 0, "State Control"}, //Internal to control from Modscan
{HR, 16, 0, "Fault Code"}, //Internal Fault code from Modscan
{IR_LONG, 101, 0, "Amps A"},
{IR_LONG, 103, 0, "Amps B"},
{IR_LONG, 105, 0, "AMPS C"},
{IR_LONG, 107, 0, "Amps G"},
{IR_LONG, 109, 0, "Amps N"},
{IR_LONG, 223, 0, "kVA"},
{IR_LONG, 207, 0, "kW"},
{IR_LONG, 305, 0, "kWh"},
{IR, 254, 0, "Power Factor (PF)"},
{IR, 41, 0, "Data Bits"},
{IR, 155, 0, "Volts AB"},
{IR, 151, 0, "Volts AN"},
{IR, 156, 0, "Volts BC"},
{IR, 152, 0, "Volts BN"},
{IR, 157, 0, "Volts CA"},
{IR, 153, 0, "Volts CN"},
};
//Size of modbus map used in FOR cycles, automatically calculated.
/**
* @brief The total number of entries in the `mb_map` array.
* This is calculated at compile time and used for iterating over the map.
*/
const int map_size = sizeof(mb_map) / sizeof(mb_map[0]);
/** @brief The main loop update interval in milliseconds. */
int interval = 250;
/** @} */ // End of ModbusMapConfig group
#endif // CONFIG_H

View File

@@ -1,86 +0,0 @@
/**
* @file main.cpp
* @brief Main execution program for the CRAH Unit (TCP) Emulator.
* @author Emmanuel Hernandez Cruz
* @date 2025-09-02
*
* @details This file contains the main execution program for an Arduino-based emulator of a CRAH unit.
* The program uses a Wi-Fi connection to communicate via the Modbus IP protocol.
*
* The setup() function initializes the following:
* - Serial communication for debugging.
* - Wi-Fi connection using credentials from config.h.
* - A Modbus TCP server.
* - Modbus points (Coils, Holding Registers, etc.) based on a predefined map in config.h.
*
* The loop() function continuously:
* - Services the Modbus TCP server to handle incoming requests.
* - Periodically calls the main update loop for the emulated equipment, which
* manages state transitions and behavior strategies.
*
* @see config.h for Wi-Fi and Modbus configuration.
* @see Equipment.h for the main equipment logic.
* @see State.h for different equipment states.
* @see Strategies/Strategy_Behavior.h for value generation strategies.
* @see Modbus_Point.h for the base class for all Modbus points.
*/
//=================================================================================================================================
//Libraries and declaration of variables.
#include <WiFi.h>
#include "config.h"
#include "ModbusPoints/Modbus_PointFactory.h"
#if defined(USE_MODBUS_IP)
#include <ModbusIP_ESP8266.h>
#else
#include <ModbusRTU.h>
#endif
//=================================================================================================================================
/**
* @brief Initializes the application.
* @details This function runs once at startup. It configures the serial communication,
* Wi-Fi, and the Modbus server. It also creates and initializes all the Modbus points
* based on the `mb_map` array in `config.h`.
*/
void setup() {
Serial.begin(115200); //Serial comm start
WiFi.config(local_IP, gateway, subnet); // Wifi service start
WiFi.begin(ssid, password);
while (WiFi.status() != WL_CONNECTED) {
delay(1000);
Serial.print(".");
}
Serial.println("Connected!!");
mb.server(); //Modbus server start
Serial.println("Server Created");
Serial.println(map_size);
for(int i = 0; i < map_size; i++){
Modbus_Point<ModbusIP>* point = createModbus_Point(&mb, mb_map[i].category, mb_map[i].address, mb_map[i].value, mb_map[i].description);
if (point) {
point->addToModbusServer();
EquipmentInstance.addModbus_Point(mb_map[i].description, point);
}
}
Serial.println("All modbus Points created");
Serial.println("Setup function ended");
}
//=================================================================================================================================
/**
* @brief The main application loop.
* @details This function runs repeatedly after setup() has completed. It performs two main actions:
* 1. It continuously services the Modbus server by calling `mb.task()` to handle
* incoming requests from a Modbus master.
* 2. At a fixed interval (defined in `config.h`), it calls `EquipmentInstance.update()`
* to run the emulator's internal state machine and behavior logic.
*/
void loop() {
mb.task();
unsigned long currentMillis = millis();
if (currentMillis - previousMillis >= interval) {
previousMillis = currentMillis;
unsigned long startTime = millis();
EquipmentInstance.update();
unsigned long endTime = millis();
unsigned long elapsedTime = endTime - startTime;
Serial.printf("Control Execution time: %d ms\n", elapsedTime);
}
}