Files
AuDaGe/tests/assets/wa3252_plc_002_1.csv

6179 lines
1.4 MiB

Tag Name,Address,Data Type,Respect Data Type,Client Access,Scan Rate,Scaling,Raw Low,Raw High,Scaled Low,Scaled High,Scaled Data Type,Clamp Low,Clamp High,Eng Units,Description
BACKUPPROGOK,,Boolean,1,R/W,1000,,,,,,,,,,Set to 1 when the card is correct and the application is consistent with CPU Internal Application RAM
BACKUPSAVED,,Boolean,1,R/W,1000,,,,,,,,,,1 means that the application backup is consistent
APPLIBCK,,Boolean,1,R/W,1000,,,,,,,,,,Set to 1 to start a backup operation (transfer application from RAM to card)
SAVECURRVAL,,Boolean,1,R/W,1000,,,,,,,,,,Set to 1 to replace initial values with current values
WA3252_GEN_0130_2_MN,400099.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Stand-By Generator 2 Run Status
WA3252_SWG_0130_1_XN3,400099.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Load Bank Breaker Closed Status
WA3252_SWG_0130_1_XN4,400099.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Load Bank Breaker Open Status
WA3252_SWG_0130_1_XN5,400099.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS GEN-0130-2 Main Closed Status
WA3252_SWG_0130_1_XN6,400099.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS GEN-0130-2 Main Open Status
WA3252_SWG_0130_1_XN7,400099.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS ""GB"" Feeder To SWG-0112-2 Closed Status"
WA3252_SWG_0130_1_XN8,400099.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS ""GB"" Feeder To SWG-0112-2 Open Status"
WA3252_SWG_0130_1_XN9,400099.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS ""GA"" Feeder To SWG-0112-1 Closed Status"
WA3252_SWG_0130_1_XN10,400099.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS ""GA"" Feeder To SWG-0112-1 Open Status"
WA3252_SWG_0130_1_XN11,400099.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS GEN-0130-1 Main Closed Status
WA3252_SWG_0130_1_XN12,400099.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS GEN-0130-1 Main Open Status
WA3252_GEN_0130_1_MN,400099.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Stand-By Generator 1 Run Status
WA3252_PLC_002_1_GlobalReset,400100.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Global Alarm Reset
WA3252_CP_002_1_R0S2_PLCFault,400100.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Rack 0 Slot 2 Fault
WA3252_CP_002_1_R0S4_PLCFault,400100.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Rack 0 Slot 4 Fault
WA3252_CP_002_1_R0S5_PLCFault,400100.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Rack 0 Slot 5 Fault
WA3252_CP_002_1_R0S6_PLCFault,400100.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Rack 0 Slot 6 Fault
WA3252_CP_002_1_R0S7_PLCFault,400100.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 Rack 0 Slot 7 Fault
WA3252_PLC_002_1_Year,400110,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Year
WA3252_PLC_002_1_Sec,400111,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Second
WA3252_PLC_002_1_Mon,400112,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Month
WA3252_PLC_002_1_Min,400113,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Min
WA3252_PLC_002_1_Hour,400114,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Hour
WA3252_PLC_002_1_Day,400115,Short,1,R/W,1000,,,,,,,,,,RWPS CP-002-1 PLC Time - Day
BMENOC0301_4.PORT1_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 1
BMENOC0301_4.PORT2_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 2
BMENOC0301_4.PORT3_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 3
BMENOC0301_4.ETH_BKP_PORT_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet backplane port
BMENOC0301_4.HSBY_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for HSBY port
BMENOC0301_4.REDUNDANCY_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Redundancy status / backup path available
BMENOC0301_4.SCANNER_OK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Scanner OK and scanning at least 1 equipment (if at least 1 equipment configured)
BMENOC0301_4.GLOBAL_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: one or more services not operating normally / 1: all operational
BMENOC0301_4.NETWORK_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 1: No traffic overload detected / 0: Traffic overload detected (ex: broadcast storm). Check your network topology and configuration.
BMENOC0301_4.RSTP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.PORT502_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.SNMP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.MAIN_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Main IP address status (0 in case of duplicate IP or no IP assigned)
BMENOC0301_4.ETH_BKP_FAILURE,,Boolean,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: Ethernet backplane hardware status (0: failure, 1: OK)"
BMENOC0301_4.ETH_BKP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: Ethernet backplane error (0: error, 1: OK)"
BMENOC0301_4.EIP_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.MODBUS_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.NTP_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.SNTP_CLIENT,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.WEB_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FIRMWARE_UPGRADE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FTP,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FDR_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.EIP_ADAPTER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: EIP adapter (server) service 0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.A_B_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: IP address A/B status (0 in case of duplicate IP or no IP assigned)
BMENOC0301_4.LLDP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: LLDP service status
BMENOC0301_4.EVENT_LOG_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: event log service not operating normally / 1: event log service operating normally or disabled
BMENOC0301_4.LOG_SERVER_NOT_REACHABLE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 1: No acknowledgement received from the syslog server / 0: otherwise
BMENOC0301_4.PORT1_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Link up/down for Ethernet port 1
BMENOC0301_4.PORT2_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Link up/down for Ethernet port 2
BMENOC0301_4.PORT3_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Link up/down for Ethernet port 3
BMENOC0301_4.ETH_BKP_PORT_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Link up/down for Ethernet backplane port
BMENOC0301_4.SCANNER_OK,,Boolean,1,R/W,1000,,,,,,,,,,Scanner OK and scanning at least 1 equipment (if at least 1 equipment configured)
BMENOC0301_4.GLOBAL_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,0: one or more services not operating normally / 1: all operational
BMENOC0301_4.NETWORK_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,1: No traffic overload detected / 0: Traffic overload detected
BMENOC0301_4.RSTP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.PORT502_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.SNMP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.MAIN_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Main IP address status (0 in caes of duplicate IP or no IP assigned)
BMENOC0301_4.EIP_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.MODBUS_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.SNTP_CLIENT,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.WEB_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FIRMWARE_UPGRADE,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FTP,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.FDR_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.EIP_ADAPTER,,Boolean,1,R/W,1000,,,,,,,,,,0: service not operating normally / 1: service operating normally or disabled
BMENOC0301_4.LLDP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,LLDP service status
BMENOC0301_4.EVENT_LOG_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,0: event log service not operating normally / 1: event log service operating normally
BMENOC0301_4.LOG_SERVER_NOT_REACHABLE,,Boolean,1,R/W,1000,,,,,,,,,,1: No acknowledgement received from the syslog server / 0: otherwise
BMEP58_ECPU_EXT.PORT1_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 1
BMEP58_ECPU_EXT.PORT2_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 2
BMEP58_ECPU_EXT.PORT3_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 3
BMEP58_ECPU_EXT.ETH_BKP_PORT_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet backplane port
BMEP58_ECPU_EXT.HSBY_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for HSBY port
BMEP58_ECPU_EXT.REDUNDANCY_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Redundancy status / backup path available
BMEP58_ECPU_EXT.SCANNER_OK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Scanner OK and scanning at least 1 equipment (if at least 1 equipment configured)
BMEP58_ECPU_EXT.GLOBAL_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: one or more services not operating normally / 1: all operational
BMEP58_ECPU_EXT.NETWORK_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 1: No traffic overload detected / 0: Traffic overload detected (ex: broadcast storm). Check your network topology and configuration.
BMEP58_ECPU_EXT.RSTP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.PORT502_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.SNMP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.MAIN_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Main IP address status (0 in case of duplicate IP or no IP assigned)
BMEP58_ECPU_EXT.ETH_BKP_FAILURE,,Boolean,1,R/W,1000,,,,,,,,,,"Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet backplane hardware status (0: failure, 1: OK)"
BMEP58_ECPU_EXT.ETH_BKP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,"Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet backplane error (0: error, 1: OK)"
BMEP58_ECPU_EXT.EIP_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.MODBUS_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.NTP_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.SNTP_CLIENT,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.WEB_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.FIRMWARE_UPGRADE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.FTP,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.FDR_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.EIP_ADAPTER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): EIP adapter (server) service 0: service not operating normally / 1: service operating normally or disabled
BMEP58_ECPU_EXT.A_B_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): IP address A/B status (0 in case of duplicate IP or no IP assigned)
BMEP58_ECPU_EXT.LLDP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): LLDP service status
BMEP58_ECPU_EXT.EVENT_LOG_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: event log service not operating normally / 1: event log service operating normally or disabled
BMEP58_ECPU_EXT.LOG_SERVER_NOT_REACHABLE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 1: No acknowledgement received from the syslog server / 0: otherwise
BMEP58_ECPU_EXT.RES_DROP_HEALTH32,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved
BMEP58_ECPU_EXT.RES_DROP_CTRL32,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved
AI_R0_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health
DI_R0_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health
DI_R0_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health
DI_R0_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health
DI_R0_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health
WA3252_GEN_0130_1_LI.GlobalReset,401000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_LI.HH_EN,401000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm"
WA3252_GEN_0130_1_LI.H_EN,401000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm"
WA3252_GEN_0130_1_LI.L_EN,401000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm"
WA3252_GEN_0130_1_LI.LL_EN,401000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm"
WA3252_GEN_0130_1_LI.BLEN,401000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm"
WA3252_GEN_0130_1_LI.OR_EN,401000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm"
WA3252_GEN_0130_1_LI.UREN,401000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm"
WA3252_GEN_0130_1_LI.RC_EN,401000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm"
WA3252_GEN_0130_1_LI.SuppressAA,401000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms"
WA3252_GEN_0130_1_LI.SuppressLA,401000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)"
WA3252_GEN_0130_1_LI.ConfigError,401000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero"
WA3252_GEN_0130_1_LI.HH_Alarm,401000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm"
WA3252_GEN_0130_1_LI.H_Alarm,401000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm"
WA3252_GEN_0130_1_LI.L_Alarm,401000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm"
WA3252_GEN_0130_1_LI.LL_Alarm,401000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm"
WA3252_GEN_0130_1_LI.BL_Alarm,401001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm"
WA3252_GEN_0130_1_LI.OR_Alarm,401001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm"
WA3252_GEN_0130_1_LI.UR_Alarm,401001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm"
WA3252_GEN_0130_1_LI.ROC_Alarm,401001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm"
WA3252_GEN_0130_1_LI.REST,401001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB"
WA3252_GEN_0130_1_LI.ALRM,401001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_LI.ANUN,401001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_LI.AKED,401001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_LI.Resetable,401001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_LI.HH_Fault,401001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault"
WA3252_GEN_0130_1_LI.H_Fault,401001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Fault"
WA3252_GEN_0130_1_LI.L_Fault,401001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault"
WA3252_GEN_0130_1_LI.LL_Fault,401001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault"
WA3252_GEN_0130_1_LI.BL_Fault,401001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault"
WA3252_GEN_0130_1_LI.OR_Fault,401001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault"
WA3252_GEN_0130_1_LI.UR_Fault,401001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault"
WA3252_GEN_0130_1_LI.ROC_Fault,401002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault"
WA3252_GEN_0130_1_LI.Tot_EN,401002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow."
WA3252_GEN_0130_1_LI.TAGR,401002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_LI.ACKN,401002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB"
WA3252_GEN_0130_1_LI.INTK,401002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)"
WA3252_GEN_0130_1_LI.PLCFault,401002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_LI.PLCIOFault,401002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_LI.INTK_EN,401002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm"
WA3252_GEN_0130_1_LI.Shelve,401002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_LI.Shelved,401002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status"
WA3252_GEN_0130_1_LI.Suppress,401002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_LI.Suppressed,401002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status"
WA3252_GEN_0130_1_LI.PCSuppress,401002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_LI.PCUnSuppress,401002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_LI.PCUnshelve,401002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_LI.GlobalReset,401200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_LI.HH_EN,401200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm"
WA3252_GEN_0130_2_LI.H_EN,401200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm"
WA3252_GEN_0130_2_LI.L_EN,401200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm"
WA3252_GEN_0130_2_LI.LL_EN,401200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm"
WA3252_GEN_0130_2_LI.BLEN,401200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm"
WA3252_GEN_0130_2_LI.OR_EN,401200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm"
WA3252_GEN_0130_2_LI.UREN,401200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm"
WA3252_GEN_0130_2_LI.RC_EN,401200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm"
WA3252_GEN_0130_2_LI.SuppressAA,401200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms"
WA3252_GEN_0130_2_LI.SuppressLA,401200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)"
WA3252_GEN_0130_2_LI.ConfigError,401200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero"
WA3252_GEN_0130_2_LI.HH_Alarm,401200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm"
WA3252_GEN_0130_2_LI.H_Alarm,401200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm"
WA3252_GEN_0130_2_LI.L_Alarm,401200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm"
WA3252_GEN_0130_2_LI.LL_Alarm,401200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm"
WA3252_GEN_0130_2_LI.BL_Alarm,401201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm"
WA3252_GEN_0130_2_LI.OR_Alarm,401201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm"
WA3252_GEN_0130_2_LI.UR_Alarm,401201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm"
WA3252_GEN_0130_2_LI.ROC_Alarm,401201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm"
WA3252_GEN_0130_2_LI.REST,401201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB"
WA3252_GEN_0130_2_LI.ALRM,401201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_LI.ANUN,401201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_LI.AKED,401201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_LI.Resetable,401201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_LI.HH_Fault,401201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault"
WA3252_GEN_0130_2_LI.H_Fault,401201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Fault"
WA3252_GEN_0130_2_LI.L_Fault,401201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault"
WA3252_GEN_0130_2_LI.LL_Fault,401201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault"
WA3252_GEN_0130_2_LI.BL_Fault,401201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault"
WA3252_GEN_0130_2_LI.OR_Fault,401201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault"
WA3252_GEN_0130_2_LI.UR_Fault,401201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault"
WA3252_GEN_0130_2_LI.ROC_Fault,401202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault"
WA3252_GEN_0130_2_LI.Tot_EN,401202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow."
WA3252_GEN_0130_2_LI.TAGR,401202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_LI.ACKN,401202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB"
WA3252_GEN_0130_2_LI.INTK,401202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)"
WA3252_GEN_0130_2_LI.PLCFault,401202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_LI.PLCIOFault,401202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_LI.INTK_EN,401202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm"
WA3252_GEN_0130_2_LI.Shelve,401202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_LI.Shelved,401202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status"
WA3252_GEN_0130_2_LI.Suppress,401202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_LI.Suppressed,401202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status"
WA3252_GEN_0130_2_LI.PCSuppress,401202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_LI.PCUnSuppress,401202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_LI.PCUnshelve,401202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control"
WA3252_TT_0130_1_TI.GlobalReset,401400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC"
WA3252_TT_0130_1_TI.HH_EN,401400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm"
WA3252_TT_0130_1_TI.H_EN,401400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm"
WA3252_TT_0130_1_TI.L_EN,401400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm"
WA3252_TT_0130_1_TI.LL_EN,401400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm"
WA3252_TT_0130_1_TI.BLEN,401400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm"
WA3252_TT_0130_1_TI.OR_EN,401400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm"
WA3252_TT_0130_1_TI.UREN,401400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm"
WA3252_TT_0130_1_TI.RC_EN,401400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm"
WA3252_TT_0130_1_TI.SuppressAA,401400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms"
WA3252_TT_0130_1_TI.SuppressLA,401400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)"
WA3252_TT_0130_1_TI.ConfigError,401400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero"
WA3252_TT_0130_1_TI.HH_Alarm,401400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm"
WA3252_TT_0130_1_TI.H_Alarm,401400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm"
WA3252_TT_0130_1_TI.L_Alarm,401400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm"
WA3252_TT_0130_1_TI.LL_Alarm,401400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm"
WA3252_TT_0130_1_TI.BL_Alarm,401401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm"
WA3252_TT_0130_1_TI.OR_Alarm,401401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm"
WA3252_TT_0130_1_TI.UR_Alarm,401401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm"
WA3252_TT_0130_1_TI.ROC_Alarm,401401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm"
WA3252_TT_0130_1_TI.REST,401401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB"
WA3252_TT_0130_1_TI.ALRM,401401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active"
WA3252_TT_0130_1_TI.ANUN,401401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating"
WA3252_TT_0130_1_TI.AKED,401401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged"
WA3252_TT_0130_1_TI.Resetable,401401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_TT_0130_1_TI.HH_Fault,401401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault"
WA3252_TT_0130_1_TI.H_Fault,401401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Fault"
WA3252_TT_0130_1_TI.L_Fault,401401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault"
WA3252_TT_0130_1_TI.LL_Fault,401401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault"
WA3252_TT_0130_1_TI.BL_Fault,401401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault"
WA3252_TT_0130_1_TI.OR_Fault,401401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault"
WA3252_TT_0130_1_TI.UR_Fault,401401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault"
WA3252_TT_0130_1_TI.ROC_Fault,401402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault"
WA3252_TT_0130_1_TI.Tot_EN,401402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow."
WA3252_TT_0130_1_TI.TAGR,401402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service"
WA3252_TT_0130_1_TI.ACKN,401402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB"
WA3252_TT_0130_1_TI.INTK,401402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)"
WA3252_TT_0130_1_TI.PLCFault,401402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_TT_0130_1_TI.PLCIOFault,401402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_TT_0130_1_TI.INTK_EN,401402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm"
WA3252_TT_0130_1_TI.Shelve,401402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI"
WA3252_TT_0130_1_TI.Shelved,401402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status"
WA3252_TT_0130_1_TI.Suppress,401402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI"
WA3252_TT_0130_1_TI.Suppressed,401402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status"
WA3252_TT_0130_1_TI.PCSuppress,401402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control"
WA3252_TT_0130_1_TI.PCUnSuppress,401402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control"
WA3252_TT_0130_1_TI.PCUnshelve,401402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_XA1.Fault,402600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_XA1.Faulted,402600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_XA1.AlarmState,402600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_XA1.FaultInAlarm,402600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA1.Alarm_EN,402600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_XA1.REST,402600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_XA1.ACKN,402600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_XA1.MCmd_Enable,402600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA1.MCmd_Disable,402600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA1.ALRM,402600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_XA1.ANUN,402600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_XA1.AKED,402600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_XA1.Resetable,402600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_XA1.Shelve,402600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_XA1.Suppress,402600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_XA1.InputAlarm,402600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_XA1.GlobalReset,402601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_XA1.PCSuppress,402601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_XA1.PCUnSuppress,402601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_XA1.PCUnshelve,402601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_XA1.Alarm_Fault,402601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_XA1.Shelved,402601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_XA1.Suppressed,402601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_XA1.PLCIOFault,402601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_XA1.PLCF,402601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_XA1.TAGR,402601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_LL.Fault,402440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_LL.Faulted,402440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_LL.AlarmState,402440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_LL.FaultInAlarm,402440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LL.Alarm_EN,402440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_LL.REST,402440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_LL.ACKN,402440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_LL.MCmd_Enable,402440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LL.MCmd_Disable,402440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LL.ALRM,402440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_LL.ANUN,402440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_LL.AKED,402440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_LL.Resetable,402440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_LL.Shelve,402440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_LL.Suppress,402440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_LL.InputAlarm,402440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_LL.GlobalReset,402441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_LL.PCSuppress,402441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_LL.PCUnSuppress,402441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_LL.PCUnshelve,402441.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_LL.Alarm_Fault,402441.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_LL.Shelved,402441.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_LL.Suppressed,402441.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_LL.PLCIOFault,402441.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_LL.PLCF,402441.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_LL.TAGR,402441.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_PL.Fault,402480.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_PL.Faulted,402480.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_PL.AlarmState,402480.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_PL.FaultInAlarm,402480.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_PL.Alarm_EN,402480.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_PL.REST,402480.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_PL.ACKN,402480.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_PL.MCmd_Enable,402480.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_PL.MCmd_Disable,402480.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_PL.ALRM,402480.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_PL.ANUN,402480.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_PL.AKED,402480.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_PL.Resetable,402480.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_PL.Shelve,402480.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_PL.Suppress,402480.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_PL.InputAlarm,402480.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_PL.GlobalReset,402481.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_PL.PCSuppress,402481.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_PL.PCUnSuppress,402481.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_PL.PCUnshelve,402481.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_PL.Alarm_Fault,402481.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_PL.Shelved,402481.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_PL.Suppressed,402481.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_PL.PLCIOFault,402481.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_PL.PLCF,402481.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_PL.TAGR,402481.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_SH.Fault,402520.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_SH.Faulted,402520.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_SH.AlarmState,402520.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_SH.FaultInAlarm,402520.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_SH.Alarm_EN,402520.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_SH.REST,402520.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_SH.ACKN,402520.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_SH.MCmd_Enable,402520.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_SH.MCmd_Disable,402520.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_SH.ALRM,402520.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_SH.ANUN,402520.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_SH.AKED,402520.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_SH.Resetable,402520.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_SH.Shelve,402520.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_SH.Suppress,402520.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_SH.InputAlarm,402520.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_SH.GlobalReset,402521.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_SH.PCSuppress,402521.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_SH.PCUnSuppress,402521.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_SH.PCUnshelve,402521.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_SH.Alarm_Fault,402521.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_SH.Shelved,402521.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_SH.Suppressed,402521.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_SH.PLCIOFault,402521.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_SH.PLCF,402521.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_SH.TAGR,402521.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_TH.Fault,402560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_TH.Faulted,402560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_TH.AlarmState,402560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_TH.FaultInAlarm,402560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_TH.Alarm_EN,402560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_TH.REST,402560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_TH.ACKN,402560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_TH.MCmd_Enable,402560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_TH.MCmd_Disable,402560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_TH.ALRM,402560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_TH.ANUN,402560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_TH.AKED,402560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_TH.Resetable,402560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_TH.Shelve,402560.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_TH.Suppress,402560.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_TH.InputAlarm,402560.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_TH.GlobalReset,402561.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_TH.PCSuppress,402561.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_TH.PCUnSuppress,402561.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_TH.PCUnshelve,402561.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_TH.Alarm_Fault,402561.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_TH.Shelved,402561.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_TH.Suppressed,402561.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_TH.PLCIOFault,402561.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_TH.PLCF,402561.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_TH.TAGR,402561.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_2_XA2.Fault,402640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_2_XA2.Faulted,402640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_2_XA2.AlarmState,402640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_2_XA2.FaultInAlarm,402640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA2.Alarm_EN,402640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_2_XA2.REST,402640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_2_XA2.ACKN,402640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_2_XA2.MCmd_Enable,402640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA2.MCmd_Disable,402640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA2.ALRM,402640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_2_XA2.ANUN,402640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_2_XA2.AKED,402640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_2_XA2.Resetable,402640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_2_XA2.Shelve,402640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_2_XA2.Suppress,402640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_2_XA2.InputAlarm,402640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_2_XA2.GlobalReset,402641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_2_XA2.PCSuppress,402641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_2_XA2.PCUnSuppress,402641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_2_XA2.PCUnshelve,402641.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_2_XA2.Alarm_Fault,402641.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_2_XA2.Shelved,402641.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_2_XA2.Suppressed,402641.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_2_XA2.PLCIOFault,402641.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_XA2.PLCF,402641.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_2_XA2.TAGR,402641.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_ZS_0130_3_ZA.Fault,402120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_ZS_0130_3_ZA.Faulted,402120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_ZS_0130_3_ZA.AlarmState,402120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_ZS_0130_3_ZA.FaultInAlarm,402120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_ZS_0130_3_ZA.Alarm_EN,402120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_ZS_0130_3_ZA.REST,402120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_ZS_0130_3_ZA.ACKN,402120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_ZS_0130_3_ZA.MCmd_Enable,402120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_ZS_0130_3_ZA.MCmd_Disable,402120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_ZS_0130_3_ZA.ALRM,402120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_ZS_0130_3_ZA.ANUN,402120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_ZS_0130_3_ZA.AKED,402120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_ZS_0130_3_ZA.Resetable,402120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_ZS_0130_3_ZA.Shelve,402120.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_ZS_0130_3_ZA.Suppress,402120.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_ZS_0130_3_ZA.InputAlarm,402120.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_ZS_0130_3_ZA.GlobalReset,402121.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_ZS_0130_3_ZA.PCSuppress,402121.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_ZS_0130_3_ZA.PCUnSuppress,402121.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_ZS_0130_3_ZA.PCUnshelve,402121.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_ZS_0130_3_ZA.Alarm_Fault,402121.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_ZS_0130_3_ZA.Shelved,402121.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_ZS_0130_3_ZA.Suppressed,402121.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_ZS_0130_3_ZA.PLCIOFault,402121.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_ZS_0130_3_ZA.PLCF,402121.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_ZS_0130_3_ZA.TAGR,402121.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_NIP_002_1_ZA.Fault,401680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_NIP_002_1_ZA.Faulted,401680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_NIP_002_1_ZA.AlarmState,401680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_NIP_002_1_ZA.FaultInAlarm,401680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_ZA.Alarm_EN,401680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_NIP_002_1_ZA.REST,401680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_NIP_002_1_ZA.ACKN,401680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_NIP_002_1_ZA.MCmd_Enable,401680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_ZA.MCmd_Disable,401680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_ZA.ALRM,401680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_NIP_002_1_ZA.ANUN,401680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_NIP_002_1_ZA.AKED,401680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_NIP_002_1_ZA.Resetable,401680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_NIP_002_1_ZA.Shelve,401680.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_NIP_002_1_ZA.Suppress,401680.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_NIP_002_1_ZA.InputAlarm,401680.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_NIP_002_1_ZA.GlobalReset,401681.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_NIP_002_1_ZA.PCSuppress,401681.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_NIP_002_1_ZA.PCUnSuppress,401681.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_NIP_002_1_ZA.PCUnshelve,401681.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_NIP_002_1_ZA.Alarm_Fault,401681.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_NIP_002_1_ZA.Shelved,401681.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_NIP_002_1_ZA.Suppressed,401681.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_NIP_002_1_ZA.PLCIOFault,401681.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_ZA.PLCF,401681.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_ZA.TAGR,401681.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_NIP_002_1_JA.Fault,401720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_NIP_002_1_JA.Faulted,401720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_NIP_002_1_JA.AlarmState,401720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_NIP_002_1_JA.FaultInAlarm,401720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_JA.Alarm_EN,401720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_NIP_002_1_JA.REST,401720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_NIP_002_1_JA.ACKN,401720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_NIP_002_1_JA.MCmd_Enable,401720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_JA.MCmd_Disable,401720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_JA.ALRM,401720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_NIP_002_1_JA.ANUN,401720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_NIP_002_1_JA.AKED,401720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_NIP_002_1_JA.Resetable,401720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_NIP_002_1_JA.Shelve,401720.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_NIP_002_1_JA.Suppress,401720.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_NIP_002_1_JA.InputAlarm,401720.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_NIP_002_1_JA.GlobalReset,401721.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_NIP_002_1_JA.PCSuppress,401721.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_NIP_002_1_JA.PCUnSuppress,401721.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_NIP_002_1_JA.PCUnshelve,401721.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_NIP_002_1_JA.Alarm_Fault,401721.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_NIP_002_1_JA.Shelved,401721.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_NIP_002_1_JA.Suppressed,401721.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_NIP_002_1_JA.PLCIOFault,401721.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_JA.PLCF,401721.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_JA.TAGR,401721.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_NIP_002_1_XN.Fault,401760.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_NIP_002_1_XN.Faulted,401760.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_NIP_002_1_XN.AlarmState,401760.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_NIP_002_1_XN.FaultInAlarm,401760.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_XN.Alarm_EN,401760.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_NIP_002_1_XN.REST,401760.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_NIP_002_1_XN.ACKN,401760.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_NIP_002_1_XN.MCmd_Enable,401760.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_XN.MCmd_Disable,401760.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_XN.ALRM,401760.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_NIP_002_1_XN.ANUN,401760.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_NIP_002_1_XN.AKED,401760.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_NIP_002_1_XN.Resetable,401760.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_NIP_002_1_XN.Shelve,401760.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_NIP_002_1_XN.Suppress,401760.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_NIP_002_1_XN.InputAlarm,401760.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_NIP_002_1_XN.GlobalReset,401761.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_NIP_002_1_XN.PCSuppress,401761.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_NIP_002_1_XN.PCUnSuppress,401761.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_NIP_002_1_XN.PCUnshelve,401761.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_NIP_002_1_XN.Alarm_Fault,401761.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_NIP_002_1_XN.Shelved,401761.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_NIP_002_1_XN.Suppressed,401761.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_NIP_002_1_XN.PLCIOFault,401761.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_XN.PLCF,401761.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_XN.TAGR,401761.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_PLC_002_1_ZA.Fault,401600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_PLC_002_1_ZA.Faulted,401600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_PLC_002_1_ZA.AlarmState,401600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_PLC_002_1_ZA.FaultInAlarm,401600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_ZA.Alarm_EN,401600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_PLC_002_1_ZA.REST,401600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_PLC_002_1_ZA.ACKN,401600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_PLC_002_1_ZA.MCmd_Enable,401600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_ZA.MCmd_Disable,401600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_ZA.ALRM,401600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_PLC_002_1_ZA.ANUN,401600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_PLC_002_1_ZA.AKED,401600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_PLC_002_1_ZA.Resetable,401600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_PLC_002_1_ZA.Shelve,401600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_PLC_002_1_ZA.Suppress,401600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_PLC_002_1_ZA.InputAlarm,401600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_PLC_002_1_ZA.GlobalReset,401601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_PLC_002_1_ZA.PCSuppress,401601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_PLC_002_1_ZA.PCUnSuppress,401601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_PLC_002_1_ZA.PCUnshelve,401601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_PLC_002_1_ZA.Alarm_Fault,401601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_PLC_002_1_ZA.Shelved,401601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_PLC_002_1_ZA.Suppressed,401601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_PLC_002_1_ZA.PLCIOFault,401601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_PLC_002_1_ZA.PLCF,401601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_PLC_002_1_ZA.TAGR,401601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_PLC_002_1_JA.Fault,401640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_PLC_002_1_JA.Faulted,401640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_PLC_002_1_JA.AlarmState,401640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_PLC_002_1_JA.FaultInAlarm,401640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_JA.Alarm_EN,401640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_PLC_002_1_JA.REST,401640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_PLC_002_1_JA.ACKN,401640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_PLC_002_1_JA.MCmd_Enable,401640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_JA.MCmd_Disable,401640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_JA.ALRM,401640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_PLC_002_1_JA.ANUN,401640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_PLC_002_1_JA.AKED,401640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_PLC_002_1_JA.Resetable,401640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_PLC_002_1_JA.Shelve,401640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_PLC_002_1_JA.Suppress,401640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_PLC_002_1_JA.InputAlarm,401640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_PLC_002_1_JA.GlobalReset,401641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_PLC_002_1_JA.PCSuppress,401641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_PLC_002_1_JA.PCUnSuppress,401641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_PLC_002_1_JA.PCUnshelve,401641.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_PLC_002_1_JA.Alarm_Fault,401641.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_PLC_002_1_JA.Shelved,401641.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_PLC_002_1_JA.Suppressed,401641.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_PLC_002_1_JA.PLCIOFault,401641.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_PLC_002_1_JA.PLCF,401641.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_PLC_002_1_JA.TAGR,401641.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_SPD_0130_1_XA1.Fault,401960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_SPD_0130_1_XA1.Faulted,401960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_SPD_0130_1_XA1.AlarmState,401960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_SPD_0130_1_XA1.FaultInAlarm,401960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_1_XA1.Alarm_EN,401960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_SPD_0130_1_XA1.REST,401960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_SPD_0130_1_XA1.ACKN,401960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_SPD_0130_1_XA1.MCmd_Enable,401960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_1_XA1.MCmd_Disable,401960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_1_XA1.ALRM,401960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_SPD_0130_1_XA1.ANUN,401960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_SPD_0130_1_XA1.AKED,401960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_SPD_0130_1_XA1.Resetable,401960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_SPD_0130_1_XA1.Shelve,401960.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_SPD_0130_1_XA1.Suppress,401960.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_SPD_0130_1_XA1.InputAlarm,401960.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_SPD_0130_1_XA1.GlobalReset,401961.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_SPD_0130_1_XA1.PCSuppress,401961.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_SPD_0130_1_XA1.PCUnSuppress,401961.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_SPD_0130_1_XA1.PCUnshelve,401961.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_SPD_0130_1_XA1.Alarm_Fault,401961.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_SPD_0130_1_XA1.Shelved,401961.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_SPD_0130_1_XA1.Suppressed,401961.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_SPD_0130_1_XA1.PLCIOFault,401961.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SPD_0130_1_XA1.PLCF,401961.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SPD_0130_1_XA1.TAGR,401961.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_BC_0130_1_XA1.Fault,401840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_BC_0130_1_XA1.Faulted,401840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_BC_0130_1_XA1.AlarmState,401840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_BC_0130_1_XA1.FaultInAlarm,401840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BC_0130_1_XA1.Alarm_EN,401840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_BC_0130_1_XA1.REST,401840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_BC_0130_1_XA1.ACKN,401840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_BC_0130_1_XA1.MCmd_Enable,401840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_BC_0130_1_XA1.MCmd_Disable,401840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_BC_0130_1_XA1.ALRM,401840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_BC_0130_1_XA1.ANUN,401840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_BC_0130_1_XA1.AKED,401840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_BC_0130_1_XA1.Resetable,401840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_BC_0130_1_XA1.Shelve,401840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_BC_0130_1_XA1.Suppress,401840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_BC_0130_1_XA1.InputAlarm,401840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_BC_0130_1_XA1.GlobalReset,401841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_BC_0130_1_XA1.PCSuppress,401841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_BC_0130_1_XA1.PCUnSuppress,401841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_BC_0130_1_XA1.PCUnshelve,401841.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_BC_0130_1_XA1.Alarm_Fault,401841.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_BC_0130_1_XA1.Shelved,401841.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_BC_0130_1_XA1.Suppressed,401841.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_BC_0130_1_XA1.PLCIOFault,401841.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_BC_0130_1_XA1.PLCF,401841.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_BC_0130_1_XA1.TAGR,401841.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_BE_0130_2_XA2.Fault,401880.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_BE_0130_2_XA2.Faulted,401880.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_BE_0130_2_XA2.AlarmState,401880.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_BE_0130_2_XA2.FaultInAlarm,401880.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BE_0130_2_XA2.Alarm_EN,401880.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_BE_0130_2_XA2.REST,401880.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_BE_0130_2_XA2.ACKN,401880.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_BE_0130_2_XA2.MCmd_Enable,401880.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_BE_0130_2_XA2.MCmd_Disable,401880.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_BE_0130_2_XA2.ALRM,401880.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_BE_0130_2_XA2.ANUN,401880.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_BE_0130_2_XA2.AKED,401880.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_BE_0130_2_XA2.Resetable,401880.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_BE_0130_2_XA2.Shelve,401880.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_BE_0130_2_XA2.Suppress,401880.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_BE_0130_2_XA2.InputAlarm,401880.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_BE_0130_2_XA2.GlobalReset,401881.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_BE_0130_2_XA2.PCSuppress,401881.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_BE_0130_2_XA2.PCUnSuppress,401881.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_BE_0130_2_XA2.PCUnshelve,401881.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_BE_0130_2_XA2.Alarm_Fault,401881.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_BE_0130_2_XA2.Shelved,401881.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_BE_0130_2_XA2.Suppressed,401881.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_BE_0130_2_XA2.PLCIOFault,401881.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_BE_0130_2_XA2.PLCF,401881.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_BE_0130_2_XA2.TAGR,401881.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_LL.Fault,402200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_LL.Faulted,402200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_LL.AlarmState,402200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_LL.FaultInAlarm,402200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LL.Alarm_EN,402200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_LL.REST,402200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_LL.ACKN,402200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_LL.MCmd_Enable,402200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LL.MCmd_Disable,402200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LL.ALRM,402200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_LL.ANUN,402200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_LL.AKED,402200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_LL.Resetable,402200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_LL.Shelve,402200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_LL.Suppress,402200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_LL.InputAlarm,402200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_LL.GlobalReset,402201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_LL.PCSuppress,402201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_LL.PCUnSuppress,402201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_LL.PCUnshelve,402201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_LL.Alarm_Fault,402201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_LL.Shelved,402201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_LL.Suppressed,402201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_LL.PLCIOFault,402201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_LL.PLCF,402201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_LL.TAGR,402201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_PL.Fault,402240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_PL.Faulted,402240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_PL.AlarmState,402240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_PL.FaultInAlarm,402240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_PL.Alarm_EN,402240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_PL.REST,402240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_PL.ACKN,402240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_PL.MCmd_Enable,402240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_PL.MCmd_Disable,402240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_PL.ALRM,402240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_PL.ANUN,402240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_PL.AKED,402240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_PL.Resetable,402240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_PL.Shelve,402240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_PL.Suppress,402240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_PL.InputAlarm,402240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_PL.GlobalReset,402241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_PL.PCSuppress,402241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_PL.PCUnSuppress,402241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_PL.PCUnshelve,402241.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_PL.Alarm_Fault,402241.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_PL.Shelved,402241.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_PL.Suppressed,402241.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_PL.PLCIOFault,402241.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_PL.PLCF,402241.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_PL.TAGR,402241.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_SH.Fault,402280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_SH.Faulted,402280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_SH.AlarmState,402280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_SH.FaultInAlarm,402280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_SH.Alarm_EN,402280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_SH.REST,402280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_SH.ACKN,402280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_SH.MCmd_Enable,402280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_SH.MCmd_Disable,402280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_SH.ALRM,402280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_SH.ANUN,402280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_SH.AKED,402280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_SH.Resetable,402280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_SH.Shelve,402280.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_SH.Suppress,402280.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_SH.InputAlarm,402280.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_SH.GlobalReset,402281.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_SH.PCSuppress,402281.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_SH.PCUnSuppress,402281.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_SH.PCUnshelve,402281.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_SH.Alarm_Fault,402281.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_SH.Shelved,402281.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_SH.Suppressed,402281.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_SH.PLCIOFault,402281.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_SH.PLCF,402281.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_SH.TAGR,402281.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_TH.Fault,402320.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_TH.Faulted,402320.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_TH.AlarmState,402320.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_TH.FaultInAlarm,402320.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_TH.Alarm_EN,402320.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_TH.REST,402320.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_TH.ACKN,402320.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_TH.MCmd_Enable,402320.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_TH.MCmd_Disable,402320.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_TH.ALRM,402320.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_TH.ANUN,402320.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_TH.AKED,402320.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_TH.Resetable,402320.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_TH.Shelve,402320.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_TH.Suppress,402320.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_TH.InputAlarm,402320.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_TH.GlobalReset,402321.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_TH.PCSuppress,402321.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_TH.PCUnSuppress,402321.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_TH.PCUnshelve,402321.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_TH.Alarm_Fault,402321.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_TH.Shelved,402321.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_TH.Suppressed,402321.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_TH.PLCIOFault,402321.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_TH.PLCF,402321.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_TH.TAGR,402321.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_XA1.Fault,402360.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_XA1.Faulted,402360.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_XA1.AlarmState,402360.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_XA1.FaultInAlarm,402360.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA1.Alarm_EN,402360.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_XA1.REST,402360.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_XA1.ACKN,402360.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_XA1.MCmd_Enable,402360.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA1.MCmd_Disable,402360.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA1.ALRM,402360.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_XA1.ANUN,402360.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_XA1.AKED,402360.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_XA1.Resetable,402360.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_XA1.Shelve,402360.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_XA1.Suppress,402360.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_XA1.InputAlarm,402360.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_XA1.GlobalReset,402361.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_XA1.PCSuppress,402361.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_XA1.PCUnSuppress,402361.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_XA1.PCUnshelve,402361.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_XA1.Alarm_Fault,402361.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_XA1.Shelved,402361.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_XA1.Suppressed,402361.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_XA1.PLCIOFault,402361.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_XA1.PLCF,402361.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_XA1.TAGR,402361.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_GEN_0130_1_XA2.Fault,402400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_GEN_0130_1_XA2.Faulted,402400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_GEN_0130_1_XA2.AlarmState,402400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_GEN_0130_1_XA2.FaultInAlarm,402400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA2.Alarm_EN,402400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_GEN_0130_1_XA2.REST,402400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_GEN_0130_1_XA2.ACKN,402400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_GEN_0130_1_XA2.MCmd_Enable,402400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA2.MCmd_Disable,402400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA2.ALRM,402400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_GEN_0130_1_XA2.ANUN,402400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_GEN_0130_1_XA2.AKED,402400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_GEN_0130_1_XA2.Resetable,402400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_GEN_0130_1_XA2.Shelve,402400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_GEN_0130_1_XA2.Suppress,402400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_GEN_0130_1_XA2.InputAlarm,402400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_GEN_0130_1_XA2.GlobalReset,402401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_GEN_0130_1_XA2.PCSuppress,402401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_GEN_0130_1_XA2.PCUnSuppress,402401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_GEN_0130_1_XA2.PCUnshelve,402401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_GEN_0130_1_XA2.Alarm_Fault,402401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_GEN_0130_1_XA2.Shelved,402401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_GEN_0130_1_XA2.Suppressed,402401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_GEN_0130_1_XA2.PLCIOFault,402401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_XA2.PLCF,402401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_GEN_0130_1_XA2.TAGR,402401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_NIP_002_1_BM.Fault,401800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_NIP_002_1_BM.Faulted,401800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_NIP_002_1_BM.AlarmState,401800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_NIP_002_1_BM.FaultInAlarm,401800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_BM.Alarm_EN,401800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_NIP_002_1_BM.REST,401800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_NIP_002_1_BM.ACKN,401800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_NIP_002_1_BM.MCmd_Enable,401800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_BM.MCmd_Disable,401800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_BM.ALRM,401800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_NIP_002_1_BM.ANUN,401800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_NIP_002_1_BM.AKED,401800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_NIP_002_1_BM.Resetable,401800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_NIP_002_1_BM.Shelve,401800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_NIP_002_1_BM.Suppress,401800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_NIP_002_1_BM.InputAlarm,401800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_NIP_002_1_BM.GlobalReset,401801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_NIP_002_1_BM.PCSuppress,401801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_NIP_002_1_BM.PCUnSuppress,401801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_NIP_002_1_BM.PCUnshelve,401801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_NIP_002_1_BM.Alarm_Fault,401801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_NIP_002_1_BM.Shelved,401801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_NIP_002_1_BM.Suppressed,401801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_NIP_002_1_BM.PLCIOFault,401801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_BM.PLCF,401801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_NIP_002_1_BM.TAGR,401801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_SD_0130_1_XA.Fault,401920.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_SD_0130_1_XA.Faulted,401920.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_SD_0130_1_XA.AlarmState,401920.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_SD_0130_1_XA.FaultInAlarm,401920.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SD_0130_1_XA.Alarm_EN,401920.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_SD_0130_1_XA.REST,401920.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_SD_0130_1_XA.ACKN,401920.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_SD_0130_1_XA.MCmd_Enable,401920.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_SD_0130_1_XA.MCmd_Disable,401920.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_SD_0130_1_XA.ALRM,401920.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_SD_0130_1_XA.ANUN,401920.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_SD_0130_1_XA.AKED,401920.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_SD_0130_1_XA.Resetable,401920.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_SD_0130_1_XA.Shelve,401920.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_SD_0130_1_XA.Suppress,401920.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_SD_0130_1_XA.InputAlarm,401920.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_SD_0130_1_XA.GlobalReset,401921.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_SD_0130_1_XA.PCSuppress,401921.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_SD_0130_1_XA.PCUnSuppress,401921.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_SD_0130_1_XA.PCUnshelve,401921.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_SD_0130_1_XA.Alarm_Fault,401921.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_SD_0130_1_XA.Shelved,401921.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_SD_0130_1_XA.Suppressed,401921.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_SD_0130_1_XA.PLCIOFault,401921.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SD_0130_1_XA.PLCF,401921.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SD_0130_1_XA.TAGR,401921.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_SPD_0130_2_XA2.Fault,402000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_SPD_0130_2_XA2.Faulted,402000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_SPD_0130_2_XA2.AlarmState,402000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_SPD_0130_2_XA2.FaultInAlarm,402000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_2_XA2.Alarm_EN,402000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_SPD_0130_2_XA2.REST,402000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_SPD_0130_2_XA2.ACKN,402000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_SPD_0130_2_XA2.MCmd_Enable,402000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_2_XA2.MCmd_Disable,402000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_2_XA2.ALRM,402000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_SPD_0130_2_XA2.ANUN,402000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_SPD_0130_2_XA2.AKED,402000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_SPD_0130_2_XA2.Resetable,402000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_SPD_0130_2_XA2.Shelve,402000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_SPD_0130_2_XA2.Suppress,402000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_SPD_0130_2_XA2.InputAlarm,402000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_SPD_0130_2_XA2.GlobalReset,402001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_SPD_0130_2_XA2.PCSuppress,402001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_SPD_0130_2_XA2.PCUnSuppress,402001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_SPD_0130_2_XA2.PCUnshelve,402001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_SPD_0130_2_XA2.Alarm_Fault,402001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_SPD_0130_2_XA2.Shelved,402001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_SPD_0130_2_XA2.Suppressed,402001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_SPD_0130_2_XA2.PLCIOFault,402001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SPD_0130_2_XA2.PLCF,402001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SPD_0130_2_XA2.TAGR,402001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_SWG_0130_1_XN1.Fault,402040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_SWG_0130_1_XN1.Faulted,402040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_SWG_0130_1_XN1.AlarmState,402040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_SWG_0130_1_XN1.FaultInAlarm,402040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN1.Alarm_EN,402040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_SWG_0130_1_XN1.REST,402040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_SWG_0130_1_XN1.ACKN,402040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_SWG_0130_1_XN1.MCmd_Enable,402040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN1.MCmd_Disable,402040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN1.ALRM,402040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_SWG_0130_1_XN1.ANUN,402040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_SWG_0130_1_XN1.AKED,402040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_SWG_0130_1_XN1.Resetable,402040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_SWG_0130_1_XN1.Shelve,402040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_SWG_0130_1_XN1.Suppress,402040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_SWG_0130_1_XN1.InputAlarm,402040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_SWG_0130_1_XN1.GlobalReset,402041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_SWG_0130_1_XN1.PCSuppress,402041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_SWG_0130_1_XN1.PCUnSuppress,402041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_SWG_0130_1_XN1.PCUnshelve,402041.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_SWG_0130_1_XN1.Alarm_Fault,402041.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_SWG_0130_1_XN1.Shelved,402041.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_SWG_0130_1_XN1.Suppressed,402041.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_SWG_0130_1_XN1.PLCIOFault,402041.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SWG_0130_1_XN1.PLCF,402041.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SWG_0130_1_XN1.TAGR,402041.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
WA3252_SWG_0130_1_XN2.Fault,402080.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm"
WA3252_SWG_0130_1_XN2.Faulted,402080.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault"
WA3252_SWG_0130_1_XN2.AlarmState,402080.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm"
WA3252_SWG_0130_1_XN2.FaultInAlarm,402080.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN2.Alarm_EN,402080.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm"
WA3252_SWG_0130_1_XN2.REST,402080.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm"
WA3252_SWG_0130_1_XN2.ACKN,402080.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm"
WA3252_SWG_0130_1_XN2.MCmd_Enable,402080.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN2.MCmd_Disable,402080.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN2.ALRM,402080.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active"
WA3252_SWG_0130_1_XN2.ANUN,402080.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating"
WA3252_SWG_0130_1_XN2.AKED,402080.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged"
WA3252_SWG_0130_1_XN2.Resetable,402080.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable"
WA3252_SWG_0130_1_XN2.Shelve,402080.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI"
WA3252_SWG_0130_1_XN2.Suppress,402080.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI"
WA3252_SWG_0130_1_XN2.InputAlarm,402080.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: "
WA3252_SWG_0130_1_XN2.GlobalReset,402081.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC"
WA3252_SWG_0130_1_XN2.PCSuppress,402081.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control"
WA3252_SWG_0130_1_XN2.PCUnSuppress,402081.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control"
WA3252_SWG_0130_1_XN2.PCUnshelve,402081.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control"
WA3252_SWG_0130_1_XN2.Alarm_Fault,402081.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault"
WA3252_SWG_0130_1_XN2.Shelved,402081.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status"
WA3252_SWG_0130_1_XN2.Suppressed,402081.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status"
WA3252_SWG_0130_1_XN2.PLCIOFault,402081.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SWG_0130_1_XN2.PLCF,402081.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted."
WA3252_SWG_0130_1_XN2.TAGR,402081.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service"
BMENOC0301_4.ETH_PORT_1_2_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet port 1 and 2 status
BMENOC0301_4.ETH_PORT3_BKP_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet port 3 and backplane port status
BMENOC0301_4.FDR_USAGE,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: % of FDR server usage
BMENOC0301_4.RESERVED,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Hidden - Reserved
BMENOC0301_4.ETH_PORT_1_2_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Ethernet port 1 and 2 status
BMENOC0301_4.ETH_PORT3_BKP_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Ethernet port 3 and backplane port status
BMENOC0301_4.FDR_USAGE,,Byte,1,R/W,1000,,,,,,,,,,% of FDR server usage
BMEP58_ECPU_EXT.RES_CRA_CNX_HEALTH32,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved
BMEP58_ECPU_EXT.ETH_PORT_1_2_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet port 1 and 2 status
BMEP58_ECPU_EXT.ETH_PORT3_BKP_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet port 3 and backplane port status
BMEP58_ECPU_EXT.FDR_USAGE,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): % of FDR server usage
BMEP58_ECPU_EXT.RESERVED1,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved
AI_R0_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults
DI_R0_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults
DI_R0_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults
DI_R0_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults
DI_R0_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults
Clock.[0],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[1],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[2],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[3],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[4],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[5],,Short,1,R/W,1000,,,,,,,,,,System Time
Clock.[6],,Short,1,R/W,1000,,,,,,,,,,System Time
WA3252_GEN_0130_1_LI.BOOLS1,401000,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.BOOLS2,401001,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.BOOLS3,401002,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits"
WA3252_GEN_0130_1_LI.BOOLS4,401003,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)"
WA3252_GEN_0130_1_LI.INT1,401004,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_GEN_0130_1_LI.INT2,401005,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_GEN_0130_1_LI.Raw,401006,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card"
WA3252_GEN_0130_1_LI.AENotify,401196,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_LI.BOOLS1,401200,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.BOOLS2,401201,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.BOOLS3,401202,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits"
WA3252_GEN_0130_2_LI.BOOLS4,401203,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)"
WA3252_GEN_0130_2_LI.INT1,401204,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_GEN_0130_2_LI.INT2,401205,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_GEN_0130_2_LI.Raw,401206,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card"
WA3252_GEN_0130_2_LI.AENotify,401396,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI"
WA3252_TT_0130_1_TI.BOOLS1,401400,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.BOOLS2,401401,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.BOOLS3,401402,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits"
WA3252_TT_0130_1_TI.BOOLS4,401403,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)"
WA3252_TT_0130_1_TI.INT1,401404,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_TT_0130_1_TI.INT2,401405,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer"
WA3252_TT_0130_1_TI.Raw,401406,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card"
WA3252_TT_0130_1_TI.AENotify,401596,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_XA1.BOOLS1,402600,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_XA1.BOOLS2,402601,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_XA1.BOOLS3,402602,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_XA1.BOOLS4,402603,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_XA1.INT1,402604,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_XA1.INT2,402605,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_XA1.AENotify,402632,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_LL.BOOLS1,402440,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_LL.BOOLS2,402441,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_LL.BOOLS3,402442,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_LL.BOOLS4,402443,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_LL.INT1,402444,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_LL.INT2,402445,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_LL.AENotify,402472,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_PL.BOOLS1,402480,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_PL.BOOLS2,402481,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_PL.BOOLS3,402482,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_PL.BOOLS4,402483,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_PL.INT1,402484,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_PL.INT2,402485,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_PL.AENotify,402512,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_SH.BOOLS1,402520,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_SH.BOOLS2,402521,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_SH.BOOLS3,402522,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_SH.BOOLS4,402523,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_SH.INT1,402524,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_SH.INT2,402525,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_SH.AENotify,402552,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_TH.BOOLS1,402560,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_TH.BOOLS2,402561,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_TH.BOOLS3,402562,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_TH.BOOLS4,402563,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_TH.INT1,402564,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_TH.INT2,402565,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_TH.AENotify,402592,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_2_XA2.BOOLS1,402640,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_2_XA2.BOOLS2,402641,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_2_XA2.BOOLS3,402642,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_2_XA2.BOOLS4,402643,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_2_XA2.INT1,402644,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_XA2.INT2,402645,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_2_XA2.AENotify,402672,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_ZS_0130_3_ZA.BOOLS1,402120,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_ZS_0130_3_ZA.BOOLS2,402121,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_ZS_0130_3_ZA.BOOLS3,402122,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_ZS_0130_3_ZA.BOOLS4,402123,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_ZS_0130_3_ZA.INT1,402124,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_ZS_0130_3_ZA.INT2,402125,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_ZS_0130_3_ZA.AENotify,402152,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_NIP_002_1_ZA.BOOLS1,401680,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_NIP_002_1_ZA.BOOLS2,401681,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_NIP_002_1_ZA.BOOLS3,401682,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_NIP_002_1_ZA.BOOLS4,401683,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_NIP_002_1_ZA.INT1,401684,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_ZA.INT2,401685,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_ZA.AENotify,401712,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_NIP_002_1_JA.BOOLS1,401720,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_NIP_002_1_JA.BOOLS2,401721,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_NIP_002_1_JA.BOOLS3,401722,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_NIP_002_1_JA.BOOLS4,401723,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_NIP_002_1_JA.INT1,401724,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_JA.INT2,401725,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_JA.AENotify,401752,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_NIP_002_1_XN.BOOLS1,401760,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_NIP_002_1_XN.BOOLS2,401761,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_NIP_002_1_XN.BOOLS3,401762,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_NIP_002_1_XN.BOOLS4,401763,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_NIP_002_1_XN.INT1,401764,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_XN.INT2,401765,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_XN.AENotify,401792,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_PLC_002_1_ZA.BOOLS1,401600,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_PLC_002_1_ZA.BOOLS2,401601,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_PLC_002_1_ZA.BOOLS3,401602,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_PLC_002_1_ZA.BOOLS4,401603,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_PLC_002_1_ZA.INT1,401604,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_PLC_002_1_ZA.INT2,401605,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_PLC_002_1_ZA.AENotify,401632,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_PLC_002_1_JA.BOOLS1,401640,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_PLC_002_1_JA.BOOLS2,401641,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_PLC_002_1_JA.BOOLS3,401642,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_PLC_002_1_JA.BOOLS4,401643,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_PLC_002_1_JA.INT1,401644,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_PLC_002_1_JA.INT2,401645,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_PLC_002_1_JA.AENotify,401672,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_SPD_0130_1_XA1.BOOLS1,401960,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_SPD_0130_1_XA1.BOOLS2,401961,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_SPD_0130_1_XA1.BOOLS3,401962,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_SPD_0130_1_XA1.BOOLS4,401963,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_SPD_0130_1_XA1.INT1,401964,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SPD_0130_1_XA1.INT2,401965,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SPD_0130_1_XA1.AENotify,401992,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_BC_0130_1_XA1.BOOLS1,401840,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_BC_0130_1_XA1.BOOLS2,401841,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_BC_0130_1_XA1.BOOLS3,401842,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_BC_0130_1_XA1.BOOLS4,401843,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_BC_0130_1_XA1.INT1,401844,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_BC_0130_1_XA1.INT2,401845,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_BC_0130_1_XA1.AENotify,401872,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_BE_0130_2_XA2.BOOLS1,401880,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_BE_0130_2_XA2.BOOLS2,401881,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_BE_0130_2_XA2.BOOLS3,401882,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_BE_0130_2_XA2.BOOLS4,401883,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_BE_0130_2_XA2.INT1,401884,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_BE_0130_2_XA2.INT2,401885,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_BE_0130_2_XA2.AENotify,401912,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_LL.BOOLS1,402200,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_LL.BOOLS2,402201,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_LL.BOOLS3,402202,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_LL.BOOLS4,402203,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_LL.INT1,402204,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_LL.INT2,402205,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_LL.AENotify,402232,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_PL.BOOLS1,402240,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_PL.BOOLS2,402241,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_PL.BOOLS3,402242,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_PL.BOOLS4,402243,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_PL.INT1,402244,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_PL.INT2,402245,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_PL.AENotify,402272,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_SH.BOOLS1,402280,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_SH.BOOLS2,402281,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_SH.BOOLS3,402282,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_SH.BOOLS4,402283,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_SH.INT1,402284,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_SH.INT2,402285,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_SH.AENotify,402312,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_TH.BOOLS1,402320,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_TH.BOOLS2,402321,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_TH.BOOLS3,402322,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_TH.BOOLS4,402323,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_TH.INT1,402324,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_TH.INT2,402325,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_TH.AENotify,402352,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_XA1.BOOLS1,402360,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_XA1.BOOLS2,402361,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_XA1.BOOLS3,402362,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_XA1.BOOLS4,402363,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_XA1.INT1,402364,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_XA1.INT2,402365,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_XA1.AENotify,402392,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_XA2.BOOLS1,402400,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_GEN_0130_1_XA2.BOOLS2,402401,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_GEN_0130_1_XA2.BOOLS3,402402,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_GEN_0130_1_XA2.BOOLS4,402403,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_GEN_0130_1_XA2.INT1,402404,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_XA2.INT2,402405,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_GEN_0130_1_XA2.AENotify,402432,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_NIP_002_1_BM.BOOLS1,401800,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_NIP_002_1_BM.BOOLS2,401801,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_NIP_002_1_BM.BOOLS3,401802,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_NIP_002_1_BM.BOOLS4,401803,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_NIP_002_1_BM.INT1,401804,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_BM.INT2,401805,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_NIP_002_1_BM.AENotify,401832,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_SD_0130_1_XA.BOOLS1,401920,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_SD_0130_1_XA.BOOLS2,401921,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_SD_0130_1_XA.BOOLS3,401922,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_SD_0130_1_XA.BOOLS4,401923,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_SD_0130_1_XA.INT1,401924,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SD_0130_1_XA.INT2,401925,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SD_0130_1_XA.AENotify,401952,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_SPD_0130_2_XA2.BOOLS1,402000,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_SPD_0130_2_XA2.BOOLS2,402001,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_SPD_0130_2_XA2.BOOLS3,402002,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_SPD_0130_2_XA2.BOOLS4,402003,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_SPD_0130_2_XA2.INT1,402004,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SPD_0130_2_XA2.INT2,402005,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SPD_0130_2_XA2.AENotify,402032,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_SWG_0130_1_XN1.BOOLS1,402040,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_SWG_0130_1_XN1.BOOLS2,402041,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_SWG_0130_1_XN1.BOOLS3,402042,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_SWG_0130_1_XN1.BOOLS4,402043,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_SWG_0130_1_XN1.INT1,402044,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SWG_0130_1_XN1.INT2,402045,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SWG_0130_1_XN1.AENotify,402072,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_SWG_0130_1_XN2.BOOLS1,402080,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits"
WA3252_SWG_0130_1_XN2.BOOLS2,402081,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits"
WA3252_SWG_0130_1_XN2.BOOLS3,402082,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits."
WA3252_SWG_0130_1_XN2.BOOLS4,402083,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits."
WA3252_SWG_0130_1_XN2.INT1,402084,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SWG_0130_1_XN2.INT2,402085,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer"
WA3252_SWG_0130_1_XN2.AENotify,402112,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI"
WA3252_GEN_0130_1_LI.VALU,401008,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units"
WA3252_GEN_0130_1_LI.Old_Val,401010,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking"
WA3252_GEN_0130_1_LI.VMIN,401012,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin"
WA3252_GEN_0130_1_LI.VMAX,401014,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax"
WA3252_GEN_0130_1_LI.RawMin,401016,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_GEN_0130_1_LI.RawMax,401018,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_GEN_0130_1_LI.HH_SP,401020,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit"
WA3252_GEN_0130_1_LI.H_SP,401022,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit"
WA3252_GEN_0130_1_LI.L_SP,401024,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit"
WA3252_GEN_0130_1_LI.LL_SP,401026,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit"
WA3252_GEN_0130_1_LI.BLSP,401028,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop"
WA3252_GEN_0130_1_LI.ORSP,401030,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit"
WA3252_GEN_0130_1_LI.URSP,401032,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit"
WA3252_GEN_0130_1_LI.RCSP,401034,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault"
WA3252_GEN_0130_1_LI.INTK_SP,401036,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit"
WA3252_GEN_0130_1_LI.Total,401038,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset."
WA3252_GEN_0130_1_LI.INTK_Reset_SP,401194,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint"
WA3252_GEN_0130_2_LI.VALU,401208,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units"
WA3252_GEN_0130_2_LI.Old_Val,401210,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking"
WA3252_GEN_0130_2_LI.VMIN,401212,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin"
WA3252_GEN_0130_2_LI.VMAX,401214,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax"
WA3252_GEN_0130_2_LI.RawMin,401216,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_GEN_0130_2_LI.RawMax,401218,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_GEN_0130_2_LI.HH_SP,401220,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit"
WA3252_GEN_0130_2_LI.H_SP,401222,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit"
WA3252_GEN_0130_2_LI.L_SP,401224,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit"
WA3252_GEN_0130_2_LI.LL_SP,401226,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit"
WA3252_GEN_0130_2_LI.BLSP,401228,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop"
WA3252_GEN_0130_2_LI.ORSP,401230,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit"
WA3252_GEN_0130_2_LI.URSP,401232,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit"
WA3252_GEN_0130_2_LI.RCSP,401234,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault"
WA3252_GEN_0130_2_LI.INTK_SP,401236,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit"
WA3252_GEN_0130_2_LI.Total,401238,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset."
WA3252_GEN_0130_2_LI.INTK_Reset_SP,401394,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint"
WA3252_TT_0130_1_TI.VALU,401408,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units"
WA3252_TT_0130_1_TI.Old_Val,401410,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking"
WA3252_TT_0130_1_TI.VMIN,401412,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin"
WA3252_TT_0130_1_TI.VMAX,401414,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax"
WA3252_TT_0130_1_TI.RawMin,401416,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_TT_0130_1_TI.RawMax,401418,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU"
WA3252_TT_0130_1_TI.HH_SP,401420,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit"
WA3252_TT_0130_1_TI.H_SP,401422,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit"
WA3252_TT_0130_1_TI.L_SP,401424,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit"
WA3252_TT_0130_1_TI.LL_SP,401426,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit"
WA3252_TT_0130_1_TI.BLSP,401428,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop"
WA3252_TT_0130_1_TI.ORSP,401430,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit"
WA3252_TT_0130_1_TI.URSP,401432,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit"
WA3252_TT_0130_1_TI.RCSP,401434,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault"
WA3252_TT_0130_1_TI.INTK_SP,401436,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit"
WA3252_TT_0130_1_TI.Total,401438,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset."
WA3252_TT_0130_1_TI.INTK_Reset_SP,401594,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint"
WA3252_GEN_0130_2_XA1.ATRM,402630,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_2_LL.ATRM,402470,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_2_PL.ATRM,402510,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_2_SH.ATRM,402550,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_2_TH.ATRM,402590,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_2_XA2.ATRM,402670,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_ZS_0130_3_ZA.ATRM,402150,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_NIP_002_1_ZA.ATRM,401710,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_NIP_002_1_JA.ATRM,401750,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_NIP_002_1_XN.ATRM,401790,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_PLC_002_1_ZA.ATRM,401630,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_PLC_002_1_JA.ATRM,401670,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_SPD_0130_1_XA1.ATRM,401990,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_BC_0130_1_XA1.ATRM,401870,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_BE_0130_2_XA2.ATRM,401910,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_LL.ATRM,402230,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_PL.ATRM,402270,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_SH.ATRM,402310,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_TH.ATRM,402350,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_XA1.ATRM,402390,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_GEN_0130_1_XA2.ATRM,402430,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_NIP_002_1_BM.ATRM,401830,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_SD_0130_1_XA.ATRM,401950,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_SPD_0130_2_XA2.ATRM,402030,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_SWG_0130_1_XN1.ATRM,402070,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
WA3252_SWG_0130_1_XN2.ATRM,402110,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining"
BMENOC0301_4.CONF_SIG,,DWord,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Signature of all files on local module FDR Server
BMENOC0301_4.CONF_SIG,,DWord,1,R/W,1000,,,,,,,,,,Signature of all files on local module FDR server
BMEP58_ECPU_EXT.CONF_SIG,,DWord,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Signature of all files on local module FDR Server
BMENOC0301_4.IN_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of packets received on interface
BMENOC0301_4.IN_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of inbound packets that contain errors
BMENOC0301_4.OUT_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of packets sent on interface
BMENOC0301_4.OUT_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of outbound packets that contain errors
BMENOC0301_4.IN_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Number of packets received on interface
BMENOC0301_4.IN_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Number of inbound packets that contain errors
BMENOC0301_4.OUT_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Number of packets sent on interface
BMENOC0301_4.OUT_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Number of outbound packets that contain errors
BMEP58_ECPU_EXT.IN_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of packets received on interface
BMEP58_ECPU_EXT.IN_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of inbound packets that contain errors
BMEP58_ECPU_EXT.OUT_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of packets sent on interface
BMEP58_ECPU_EXT.OUT_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of outbound packets that contain errors
BMENOC0301_4.ETH_STATUS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet status
BMENOC0301_4.SERVICE_STATUS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: One bit for each user-observable feature
BMENOC0301_4.SERVICE_STATUS2,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: One bit for each user-observable feature
BMENOC0301_4.FIRMWARE_VERSION,,Word,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: MSB=Major Revision, LSB=Minor Revision"
BMENOC0301_4.ETH_STATUS,,Word,1,R/W,1000,,,,,,,,,,Ethernet status
BMENOC0301_4.SERVICE_STATUS,,Word,1,R/W,1000,,,,,,,,,,One bit for each user-observable feature
BMENOC0301_4.SERVICE_STATUS2,,Word,1,R/W,1000,,,,,,,,,,One bit for each user-observable feature
BMENOC0301_4.FIRMWARE_VERSION,,Word,1,R/W,1000,,,,,,,,,,"MSB=Major revision, LSB=Minor revision"
BMEP58_ECPU_EXT.ETH_STATUS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet status
BMEP58_ECPU_EXT.SERVICE_STATUS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): One bit for each user-observable feature
BMEP58_ECPU_EXT.SERVICE_STATUS2,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): One bit for each user-observable feature
BMEP58_ECPU_EXT.RESERVED2,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved
BMENOC0301_4.DIO_HEALTH.[0],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[17],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[18],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[19],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[20],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[21],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[22],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[23],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[24],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[25],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[26],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[27],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[28],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[29],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[30],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[31],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[32],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[33],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[34],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[35],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[36],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[37],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[38],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[39],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[40],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[41],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[42],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[43],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[44],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[45],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[46],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[47],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[48],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[49],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[50],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[51],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[52],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[53],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[54],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[55],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[56],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[57],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[58],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[59],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[60],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[61],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[62],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[63],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[64],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[65],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[66],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[67],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[68],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[69],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[70],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[71],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[72],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[73],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[74],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[75],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[76],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[77],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[78],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[79],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[80],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[81],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[82],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[83],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[84],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[85],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[86],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[87],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[88],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[89],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[90],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[91],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[92],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[93],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[94],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[95],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[96],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[97],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[98],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[99],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[100],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[101],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[102],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[103],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[104],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[105],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[106],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[107],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[108],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[109],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[110],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[111],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[112],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[113],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[114],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[115],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[116],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[117],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[118],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[119],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[120],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[121],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[122],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[123],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[124],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[125],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[126],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[127],,Boolean,1,R/W,1000,,,,,,,,,,DIO health bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.LS_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Local Slave health bits (local slave 1 to 16)
BMENOC0301_4.DIO_HEALTH.[0],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[17],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[18],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[19],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[20],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[21],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[22],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[23],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[24],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[25],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[26],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[27],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[28],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[29],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[30],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[31],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[32],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[33],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[34],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[35],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[36],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[37],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[38],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[39],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[40],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[41],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[42],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[43],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[44],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[45],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[46],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[47],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[48],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[49],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[50],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[51],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[52],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[53],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[54],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[55],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[56],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[57],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[58],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[59],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[60],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[61],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[62],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[63],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[64],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[65],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[66],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[67],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[68],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[69],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[70],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[71],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[72],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[73],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[74],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[75],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[76],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[77],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[78],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[79],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[80],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[81],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[82],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[83],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[84],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[85],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[86],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[87],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[88],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[89],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[90],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[91],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[92],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[93],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[94],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[95],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[96],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[97],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[98],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[99],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[100],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[101],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[102],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[103],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[104],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[105],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[106],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[107],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[108],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[109],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[110],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[111],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[112],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[113],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[114],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[115],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[116],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[117],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[118],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[119],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[120],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[121],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[122],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[123],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[124],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[125],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[126],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_HEALTH.[127],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[0],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[17],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[18],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[19],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[20],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[21],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[22],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[23],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[24],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[25],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[26],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[27],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[28],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[29],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[30],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[31],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[32],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[33],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[34],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[35],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[36],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[37],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[38],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[39],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[40],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[41],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[42],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[43],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[44],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[45],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[46],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[47],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[48],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[49],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[50],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[51],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[52],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[53],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[54],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[55],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[56],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[57],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[58],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[59],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[60],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[61],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[62],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[63],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[64],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[65],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[66],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[67],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[68],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[69],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[70],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[71],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[72],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[73],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[74],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[75],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[76],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[77],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[78],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[79],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[80],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[81],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[82],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[83],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[84],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[85],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[86],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[87],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[88],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[89],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[90],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[91],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[92],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[93],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[94],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[95],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[96],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[97],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[98],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[99],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[100],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[101],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[102],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[103],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[104],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[105],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[106],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[107],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[108],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[109],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[110],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[111],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[112],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[113],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[114],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[115],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[116],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[117],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[118],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[119],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[120],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[121],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[122],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[123],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[124],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[125],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[126],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[127],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[0],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[1],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[2],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[3],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[4],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[5],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[6],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[7],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[8],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[9],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[10],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[11],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[12],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[13],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[14],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[15],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[16],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[17],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[18],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[19],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[20],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[21],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[22],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[23],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[24],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[25],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[26],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[27],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[28],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[29],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[30],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[31],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[32],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[33],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[34],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[35],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[36],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[37],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[38],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[39],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[40],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[41],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[42],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[43],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[44],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[45],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[46],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[47],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[48],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[49],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[50],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[51],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[52],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[53],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[54],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[55],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[56],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[57],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[58],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[59],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[60],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[61],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[62],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[63],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[64],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[65],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[66],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[67],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[68],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[69],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[70],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[71],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[72],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[73],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[74],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[75],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[76],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[77],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[78],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[79],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[80],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[81],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[82],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[83],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[84],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[85],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[86],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[87],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[88],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[89],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[90],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[91],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[92],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[93],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[94],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[95],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[96],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[97],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[98],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[99],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[100],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[101],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[102],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[103],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[104],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[105],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[106],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[107],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[108],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[109],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[110],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[111],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[112],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[113],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[114],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[115],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[116],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[117],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[118],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[119],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[120],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[121],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[122],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[123],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[124],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[125],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[126],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.DIO_CTRL.[127],,Boolean,1,R/W,1000,,,,,,,,,,DIO control bits (1 bit per DIO up to 128 DIOs. 112-127 are reserved for future extension)
BMENOC0301_4.LS_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMENOC0301_4.LS_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16)
BMEP58_ECPU_EXT.DROP_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[17],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[18],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[19],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[20],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[21],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[22],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[23],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[24],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[25],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[26],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[27],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[28],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[29],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[30],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_HEALTH.[31],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[4],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[5],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[6],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[7],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[8],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[9],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[10],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[11],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[12],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[13],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[14],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[15],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[16],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[17],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[18],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[19],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[20],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[21],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[22],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[23],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[24],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[25],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[26],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[27],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[28],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[29],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[30],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.DROP_CTRL.[31],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31)
BMEP58_ECPU_EXT.LS_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3)
BMEP58_ECPU_EXT.LS_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3)
BMEP58_ECPU_EXT.LS_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3)
BMEP58_ECPU_EXT.RIO_HEALTH.[257],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[258],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[259],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[260],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[261],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[262],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[263],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[264],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[265],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[266],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[267],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[268],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[269],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[270],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[271],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[272],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[273],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[274],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[275],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[276],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[277],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[278],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[279],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[280],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[281],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[282],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[283],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[284],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[285],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[286],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[287],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[288],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[289],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[290],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[291],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[292],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[293],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[294],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[295],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[296],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[297],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[298],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[299],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[300],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[301],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[302],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[303],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[304],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[305],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[306],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[307],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[308],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[309],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[310],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[311],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[312],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[313],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[314],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[315],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[316],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[317],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[318],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[319],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[320],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[321],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[322],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[323],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[324],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[325],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[326],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[327],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[328],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[329],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[330],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[331],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[332],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[333],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[334],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[335],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[336],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[337],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[338],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[339],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[340],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[341],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[342],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[343],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[344],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[345],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[346],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[347],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[348],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[349],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[350],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[351],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[352],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[353],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[354],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[355],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[356],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[357],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[358],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[359],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[360],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[361],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[362],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[363],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[364],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[365],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[366],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[367],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[368],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[369],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[370],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[371],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[372],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[373],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[374],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[375],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[376],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[377],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[378],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[379],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[380],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[381],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[382],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[383],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_HEALTH.[384],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[257],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[258],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[259],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[260],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[261],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[262],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[263],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[264],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[265],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[266],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[267],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[268],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[269],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[270],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[271],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[272],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[273],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[274],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[275],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[276],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[277],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[278],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[279],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[280],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[281],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[282],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[283],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[284],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[285],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[286],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[287],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[288],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[289],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[290],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[291],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[292],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[293],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[294],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[295],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[296],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[297],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[298],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[299],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[300],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[301],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[302],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[303],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[304],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[305],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[306],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[307],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[308],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[309],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[310],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[311],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[312],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[313],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[314],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[315],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[316],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[317],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[318],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[319],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[320],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[321],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[322],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[323],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[324],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[325],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[326],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[327],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[328],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[329],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[330],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[331],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[332],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[333],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[334],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[335],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[336],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[337],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[338],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[339],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[340],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[341],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[342],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[343],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[344],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[345],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[346],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[347],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[348],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[349],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[350],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[351],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[352],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[353],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[354],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[355],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[356],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[357],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[358],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[359],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[360],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[361],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[362],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[363],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[364],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[365],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[366],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[367],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[368],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[369],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[370],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[371],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[372],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[373],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[374],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[375],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[376],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[377],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[378],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[379],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[380],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[381],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[382],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[383],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.RIO_CTRL.[384],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128)
BMEP58_ECPU_EXT.DIO_HEALTH.[513],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[514],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[515],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[516],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[517],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[518],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[519],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[520],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[521],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[522],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[523],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[524],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[525],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[526],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[527],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[528],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[529],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[530],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[531],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[532],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[533],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[534],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[535],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[536],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[537],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[538],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[539],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[540],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[541],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[542],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[543],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[544],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[545],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[546],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[547],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[548],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[549],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[550],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[551],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[552],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[553],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[554],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[555],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[556],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[557],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[558],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[559],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[560],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[561],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[562],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[563],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[564],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[565],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[566],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[567],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[568],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[569],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[570],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[571],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[572],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[573],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[574],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[575],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[576],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[577],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[578],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[579],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[580],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[581],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[582],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[583],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[584],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[585],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[586],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[587],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[588],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[589],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[590],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[591],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[592],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[593],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[594],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[595],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[596],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[597],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[598],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[599],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[600],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[601],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[602],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[603],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[604],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[605],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[606],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[607],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[608],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[609],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[610],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[611],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[612],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[613],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[614],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[615],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[616],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[617],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[618],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[619],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[620],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[621],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[622],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[623],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[624],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[625],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[626],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[627],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[628],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[629],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[630],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[631],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[632],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[633],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[634],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[635],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[636],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[637],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[638],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[639],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_HEALTH.[640],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[513],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[514],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[515],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[516],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[517],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[518],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[519],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[520],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[521],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[522],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[523],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[524],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[525],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[526],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[527],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[528],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[529],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[530],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[531],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[532],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[533],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[534],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[535],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[536],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[537],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[538],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[539],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[540],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[541],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[542],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[543],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[544],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[545],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[546],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[547],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[548],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[549],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[550],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[551],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[552],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[553],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[554],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[555],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[556],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[557],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[558],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[559],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[560],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[561],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[562],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[563],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[564],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[565],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[566],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[567],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[568],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[569],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[570],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[571],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[572],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[573],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[574],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[575],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[576],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[577],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[578],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[579],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[580],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[581],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[582],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[583],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[584],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[585],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[586],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[587],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[588],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[589],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[590],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[591],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[592],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[593],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[594],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[595],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[596],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[597],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[598],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[599],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[600],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[601],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[602],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[603],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[604],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[605],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[606],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[607],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[608],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[609],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[610],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[611],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[612],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[613],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[614],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[615],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[616],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[617],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[618],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[619],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[620],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[621],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[622],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[623],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[624],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[625],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[626],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[627],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[628],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[629],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[630],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[631],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[632],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[633],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[634],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[635],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[636],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[637],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[638],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[639],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
BMEP58_ECPU_EXT.DIO_CTRL.[640],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs)
WA3252_GEN_0130_1_LI.almHighHigh.Fault,401040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almHighHigh.AlarmState,401040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almHighHigh.GlobalReset,401040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almHighHigh.FaultInAlarm,401040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almHighHigh.ALRM,401040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almHighHigh.ANUN,401040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almHighHigh.AKED,401040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almHighHigh.Resetable,401040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almHighHigh.REST,401040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almHighHigh.ACKN,401040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almHighHigh.UACK,401040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almHighHigh.MCmd_Enable,401040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.MCmd_Disable,401040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.OCmd_Shelve,401040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.OCmd_Unshelve,401040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.SCmd_Suppress,401040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.SCmd_UnSuppress,401041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almHighHigh.AEShelveTMRDN,401041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almHighHigh.Bad,401041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almHighHigh.Suppress,401042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.UnSuppress,401042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Shelve,401042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.UnShelve,401042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Enable,401042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Disable,401042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Ack,401042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Reset,401042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Suppressed,401042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Shelved,401042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Disabled,401042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Acked,401042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almHighHigh.Alarm,401042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Fault,401052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almHigh.AlarmState,401052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almHigh.GlobalReset,401052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almHigh.FaultInAlarm,401052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almHigh.ALRM,401052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almHigh.ANUN,401052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almHigh.AKED,401052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almHigh.Resetable,401052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almHigh.REST,401052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almHigh.ACKN,401052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almHigh.UACK,401052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almHigh.MCmd_Enable,401052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almHigh.MCmd_Disable,401052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almHigh.OCmd_Shelve,401052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almHigh.OCmd_Unshelve,401052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almHigh.SCmd_Suppress,401052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almHigh.SCmd_UnSuppress,401053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almHigh.AEShelveTMRDN,401053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almHigh.Bad,401053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almHigh.Suppress,401054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.UnSuppress,401054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Shelve,401054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.UnShelve,401054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Enable,401054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Disable,401054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Ack,401054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Reset,401054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almHigh.Suppressed,401054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almHigh.Shelved,401054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almHigh.Disabled,401054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almHigh.Acked,401054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almHigh.Alarm,401054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Fault,401064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almLow.AlarmState,401064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almLow.GlobalReset,401064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almLow.FaultInAlarm,401064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almLow.ALRM,401064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almLow.ANUN,401064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almLow.AKED,401064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almLow.Resetable,401064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almLow.REST,401064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almLow.ACKN,401064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almLow.UACK,401064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almLow.MCmd_Enable,401064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almLow.MCmd_Disable,401064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almLow.OCmd_Shelve,401064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almLow.OCmd_Unshelve,401064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almLow.SCmd_Suppress,401064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almLow.SCmd_UnSuppress,401065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almLow.AEShelveTMRDN,401065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almLow.Bad,401065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almLow.Suppress,401066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.UnSuppress,401066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Shelve,401066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.UnShelve,401066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Enable,401066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Disable,401066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Ack,401066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Reset,401066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almLow.Suppressed,401066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almLow.Shelved,401066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almLow.Disabled,401066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almLow.Acked,401066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almLow.Alarm,401066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Fault,401076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almLowLow.AlarmState,401076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almLowLow.GlobalReset,401076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almLowLow.FaultInAlarm,401076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almLowLow.ALRM,401076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almLowLow.ANUN,401076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almLowLow.AKED,401076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almLowLow.Resetable,401076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almLowLow.REST,401076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almLowLow.ACKN,401076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almLowLow.UACK,401076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almLowLow.MCmd_Enable,401076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almLowLow.MCmd_Disable,401076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almLowLow.OCmd_Shelve,401076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almLowLow.OCmd_Unshelve,401076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almLowLow.SCmd_Suppress,401076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almLowLow.SCmd_UnSuppress,401077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almLowLow.AEShelveTMRDN,401077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almLowLow.Bad,401077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almLowLow.Suppress,401078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.UnSuppress,401078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Shelve,401078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.UnShelve,401078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Enable,401078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Disable,401078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Ack,401078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Reset,401078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Suppressed,401078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Shelved,401078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Disabled,401078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Acked,401078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almLowLow.Alarm,401078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Fault,401088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almBrokenLoop.AlarmState,401088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almBrokenLoop.GlobalReset,401088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almBrokenLoop.FaultInAlarm,401088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almBrokenLoop.ALRM,401088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almBrokenLoop.ANUN,401088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almBrokenLoop.AKED,401088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almBrokenLoop.Resetable,401088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almBrokenLoop.REST,401088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almBrokenLoop.ACKN,401088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almBrokenLoop.UACK,401088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almBrokenLoop.MCmd_Enable,401088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.MCmd_Disable,401088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.OCmd_Shelve,401088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.OCmd_Unshelve,401088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.SCmd_Suppress,401088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.SCmd_UnSuppress,401089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almBrokenLoop.AEShelveTMRDN,401089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almBrokenLoop.Bad,401089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almBrokenLoop.Suppress,401090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.UnSuppress,401090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Shelve,401090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.UnShelve,401090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Enable,401090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Disable,401090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Ack,401090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Reset,401090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Suppressed,401090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Shelved,401090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Disabled,401090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Acked,401090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.Alarm,401090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Fault,401100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almOverRange.AlarmState,401100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almOverRange.GlobalReset,401100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almOverRange.FaultInAlarm,401100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almOverRange.ALRM,401100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almOverRange.ANUN,401100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almOverRange.AKED,401100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almOverRange.Resetable,401100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almOverRange.REST,401100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almOverRange.ACKN,401100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almOverRange.UACK,401100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almOverRange.MCmd_Enable,401100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almOverRange.MCmd_Disable,401100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almOverRange.OCmd_Shelve,401100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almOverRange.OCmd_Unshelve,401100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almOverRange.SCmd_Suppress,401100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almOverRange.SCmd_UnSuppress,401101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almOverRange.AEShelveTMRDN,401101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almOverRange.Bad,401101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almOverRange.Suppress,401102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.UnSuppress,401102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Shelve,401102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.UnShelve,401102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Enable,401102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Disable,401102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Ack,401102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Reset,401102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Suppressed,401102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Shelved,401102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Disabled,401102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Acked,401102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almOverRange.Alarm,401102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Fault,401112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almUnderRange.AlarmState,401112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almUnderRange.GlobalReset,401112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almUnderRange.FaultInAlarm,401112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almUnderRange.ALRM,401112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almUnderRange.ANUN,401112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almUnderRange.AKED,401112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almUnderRange.Resetable,401112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almUnderRange.REST,401112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almUnderRange.ACKN,401112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almUnderRange.UACK,401112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almUnderRange.MCmd_Enable,401112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.MCmd_Disable,401112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.OCmd_Shelve,401112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.OCmd_Unshelve,401112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.SCmd_Suppress,401112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.SCmd_UnSuppress,401113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almUnderRange.AEShelveTMRDN,401113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almUnderRange.Bad,401113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almUnderRange.Suppress,401114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.UnSuppress,401114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Shelve,401114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.UnShelve,401114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Enable,401114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Disable,401114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Ack,401114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Reset,401114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Suppressed,401114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Shelved,401114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Disabled,401114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Acked,401114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almUnderRange.Alarm,401114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Fault,401124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almRateOfChange.AlarmState,401124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almRateOfChange.GlobalReset,401124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almRateOfChange.FaultInAlarm,401124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almRateOfChange.ALRM,401124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almRateOfChange.ANUN,401124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almRateOfChange.AKED,401124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almRateOfChange.Resetable,401124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almRateOfChange.REST,401124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almRateOfChange.ACKN,401124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almRateOfChange.UACK,401124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almRateOfChange.MCmd_Enable,401124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.MCmd_Disable,401124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.OCmd_Shelve,401124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.OCmd_Unshelve,401124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.SCmd_Suppress,401124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.SCmd_UnSuppress,401125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almRateOfChange.AEShelveTMRDN,401125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almRateOfChange.Bad,401125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almRateOfChange.Suppress,401126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.UnSuppress,401126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Shelve,401126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.UnShelve,401126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Enable,401126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Disable,401126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Ack,401126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Reset,401126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Suppressed,401126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Shelved,401126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Disabled,401126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Acked,401126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almRateOfChange.Alarm,401126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Fault,401136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LI.almPLCFault.AlarmState,401136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LI.almPLCFault.GlobalReset,401136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LI.almPLCFault.FaultInAlarm,401136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LI.almPLCFault.ALRM,401136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LI.almPLCFault.ANUN,401136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LI.almPLCFault.AKED,401136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LI.almPLCFault.Resetable,401136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LI.almPLCFault.REST,401136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LI.almPLCFault.ACKN,401136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LI.almPLCFault.UACK,401136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LI.almPLCFault.MCmd_Enable,401136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.MCmd_Disable,401136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.OCmd_Shelve,401136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.OCmd_Unshelve,401136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.SCmd_Suppress,401136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.SCmd_UnSuppress,401137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LI.almPLCFault.AEShelveTMRDN,401137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LI.almPLCFault.Bad,401137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LI.almPLCFault.Suppress,401138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.UnSuppress,401138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Shelve,401138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.UnShelve,401138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Enable,401138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Disable,401138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Ack,401138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Reset,401138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Suppressed,401138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Shelved,401138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Disabled,401138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Acked,401138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LI.almPLCFault.Alarm,401138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Fault,401240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almHighHigh.AlarmState,401240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almHighHigh.GlobalReset,401240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almHighHigh.FaultInAlarm,401240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almHighHigh.ALRM,401240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almHighHigh.ANUN,401240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almHighHigh.AKED,401240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almHighHigh.Resetable,401240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almHighHigh.REST,401240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almHighHigh.ACKN,401240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almHighHigh.UACK,401240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almHighHigh.MCmd_Enable,401240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.MCmd_Disable,401240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.OCmd_Shelve,401240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.OCmd_Unshelve,401240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.SCmd_Suppress,401240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.SCmd_UnSuppress,401241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almHighHigh.AEShelveTMRDN,401241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almHighHigh.Bad,401241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almHighHigh.Suppress,401242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.UnSuppress,401242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Shelve,401242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.UnShelve,401242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Enable,401242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Disable,401242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Ack,401242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Reset,401242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Suppressed,401242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Shelved,401242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Disabled,401242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Acked,401242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almHighHigh.Alarm,401242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Fault,401252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almHigh.AlarmState,401252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almHigh.GlobalReset,401252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almHigh.FaultInAlarm,401252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almHigh.ALRM,401252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almHigh.ANUN,401252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almHigh.AKED,401252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almHigh.Resetable,401252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almHigh.REST,401252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almHigh.ACKN,401252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almHigh.UACK,401252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almHigh.MCmd_Enable,401252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almHigh.MCmd_Disable,401252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almHigh.OCmd_Shelve,401252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almHigh.OCmd_Unshelve,401252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almHigh.SCmd_Suppress,401252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almHigh.SCmd_UnSuppress,401253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almHigh.AEShelveTMRDN,401253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almHigh.Bad,401253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almHigh.Suppress,401254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.UnSuppress,401254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Shelve,401254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.UnShelve,401254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Enable,401254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Disable,401254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Ack,401254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Reset,401254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almHigh.Suppressed,401254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almHigh.Shelved,401254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almHigh.Disabled,401254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almHigh.Acked,401254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almHigh.Alarm,401254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Fault,401264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almLow.AlarmState,401264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almLow.GlobalReset,401264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almLow.FaultInAlarm,401264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almLow.ALRM,401264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almLow.ANUN,401264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almLow.AKED,401264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almLow.Resetable,401264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almLow.REST,401264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almLow.ACKN,401264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almLow.UACK,401264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almLow.MCmd_Enable,401264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almLow.MCmd_Disable,401264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almLow.OCmd_Shelve,401264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almLow.OCmd_Unshelve,401264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almLow.SCmd_Suppress,401264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almLow.SCmd_UnSuppress,401265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almLow.AEShelveTMRDN,401265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almLow.Bad,401265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almLow.Suppress,401266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.UnSuppress,401266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Shelve,401266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.UnShelve,401266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Enable,401266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Disable,401266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Ack,401266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Reset,401266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almLow.Suppressed,401266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almLow.Shelved,401266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almLow.Disabled,401266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almLow.Acked,401266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almLow.Alarm,401266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Fault,401276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almLowLow.AlarmState,401276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almLowLow.GlobalReset,401276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almLowLow.FaultInAlarm,401276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almLowLow.ALRM,401276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almLowLow.ANUN,401276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almLowLow.AKED,401276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almLowLow.Resetable,401276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almLowLow.REST,401276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almLowLow.ACKN,401276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almLowLow.UACK,401276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almLowLow.MCmd_Enable,401276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almLowLow.MCmd_Disable,401276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almLowLow.OCmd_Shelve,401276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almLowLow.OCmd_Unshelve,401276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almLowLow.SCmd_Suppress,401276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almLowLow.SCmd_UnSuppress,401277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almLowLow.AEShelveTMRDN,401277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almLowLow.Bad,401277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almLowLow.Suppress,401278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.UnSuppress,401278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Shelve,401278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.UnShelve,401278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Enable,401278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Disable,401278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Ack,401278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Reset,401278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Suppressed,401278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Shelved,401278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Disabled,401278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Acked,401278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almLowLow.Alarm,401278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Fault,401288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almBrokenLoop.AlarmState,401288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almBrokenLoop.GlobalReset,401288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almBrokenLoop.FaultInAlarm,401288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almBrokenLoop.ALRM,401288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almBrokenLoop.ANUN,401288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almBrokenLoop.AKED,401288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almBrokenLoop.Resetable,401288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almBrokenLoop.REST,401288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almBrokenLoop.ACKN,401288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almBrokenLoop.UACK,401288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almBrokenLoop.MCmd_Enable,401288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.MCmd_Disable,401288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.OCmd_Shelve,401288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.OCmd_Unshelve,401288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.SCmd_Suppress,401288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.SCmd_UnSuppress,401289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almBrokenLoop.AEShelveTMRDN,401289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almBrokenLoop.Bad,401289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almBrokenLoop.Suppress,401290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.UnSuppress,401290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Shelve,401290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.UnShelve,401290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Enable,401290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Disable,401290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Ack,401290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Reset,401290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Suppressed,401290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Shelved,401290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Disabled,401290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Acked,401290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.Alarm,401290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Fault,401300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almOverRange.AlarmState,401300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almOverRange.GlobalReset,401300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almOverRange.FaultInAlarm,401300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almOverRange.ALRM,401300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almOverRange.ANUN,401300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almOverRange.AKED,401300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almOverRange.Resetable,401300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almOverRange.REST,401300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almOverRange.ACKN,401300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almOverRange.UACK,401300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almOverRange.MCmd_Enable,401300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almOverRange.MCmd_Disable,401300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almOverRange.OCmd_Shelve,401300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almOverRange.OCmd_Unshelve,401300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almOverRange.SCmd_Suppress,401300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almOverRange.SCmd_UnSuppress,401301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almOverRange.AEShelveTMRDN,401301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almOverRange.Bad,401301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almOverRange.Suppress,401302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.UnSuppress,401302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Shelve,401302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.UnShelve,401302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Enable,401302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Disable,401302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Ack,401302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Reset,401302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Suppressed,401302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Shelved,401302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Disabled,401302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Acked,401302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almOverRange.Alarm,401302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Fault,401312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almUnderRange.AlarmState,401312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almUnderRange.GlobalReset,401312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almUnderRange.FaultInAlarm,401312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almUnderRange.ALRM,401312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almUnderRange.ANUN,401312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almUnderRange.AKED,401312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almUnderRange.Resetable,401312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almUnderRange.REST,401312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almUnderRange.ACKN,401312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almUnderRange.UACK,401312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almUnderRange.MCmd_Enable,401312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.MCmd_Disable,401312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.OCmd_Shelve,401312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.OCmd_Unshelve,401312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.SCmd_Suppress,401312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.SCmd_UnSuppress,401313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almUnderRange.AEShelveTMRDN,401313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almUnderRange.Bad,401313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almUnderRange.Suppress,401314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.UnSuppress,401314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Shelve,401314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.UnShelve,401314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Enable,401314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Disable,401314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Ack,401314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Reset,401314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Suppressed,401314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Shelved,401314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Disabled,401314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Acked,401314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almUnderRange.Alarm,401314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Fault,401324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almRateOfChange.AlarmState,401324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almRateOfChange.GlobalReset,401324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almRateOfChange.FaultInAlarm,401324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almRateOfChange.ALRM,401324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almRateOfChange.ANUN,401324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almRateOfChange.AKED,401324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almRateOfChange.Resetable,401324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almRateOfChange.REST,401324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almRateOfChange.ACKN,401324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almRateOfChange.UACK,401324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almRateOfChange.MCmd_Enable,401324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.MCmd_Disable,401324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.OCmd_Shelve,401324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.OCmd_Unshelve,401324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.SCmd_Suppress,401324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.SCmd_UnSuppress,401325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almRateOfChange.AEShelveTMRDN,401325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almRateOfChange.Bad,401325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almRateOfChange.Suppress,401326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.UnSuppress,401326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Shelve,401326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.UnShelve,401326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Enable,401326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Disable,401326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Ack,401326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Reset,401326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Suppressed,401326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Shelved,401326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Disabled,401326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Acked,401326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almRateOfChange.Alarm,401326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Fault,401336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LI.almPLCFault.AlarmState,401336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LI.almPLCFault.GlobalReset,401336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LI.almPLCFault.FaultInAlarm,401336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LI.almPLCFault.ALRM,401336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LI.almPLCFault.ANUN,401336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LI.almPLCFault.AKED,401336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LI.almPLCFault.Resetable,401336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LI.almPLCFault.REST,401336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LI.almPLCFault.ACKN,401336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LI.almPLCFault.UACK,401336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LI.almPLCFault.MCmd_Enable,401336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.MCmd_Disable,401336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.OCmd_Shelve,401336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.OCmd_Unshelve,401336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.SCmd_Suppress,401336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.SCmd_UnSuppress,401337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LI.almPLCFault.AEShelveTMRDN,401337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LI.almPLCFault.Bad,401337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LI.almPLCFault.Suppress,401338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.UnSuppress,401338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Shelve,401338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.UnShelve,401338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Enable,401338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Disable,401338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Ack,401338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Reset,401338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Suppressed,401338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Shelved,401338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Disabled,401338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Acked,401338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LI.almPLCFault.Alarm,401338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Fault,401440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almHighHigh.AlarmState,401440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almHighHigh.GlobalReset,401440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almHighHigh.FaultInAlarm,401440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almHighHigh.ALRM,401440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almHighHigh.ANUN,401440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almHighHigh.AKED,401440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almHighHigh.Resetable,401440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almHighHigh.REST,401440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almHighHigh.ACKN,401440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almHighHigh.UACK,401440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almHighHigh.MCmd_Enable,401440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almHighHigh.MCmd_Disable,401440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almHighHigh.OCmd_Shelve,401440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almHighHigh.OCmd_Unshelve,401440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almHighHigh.SCmd_Suppress,401440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almHighHigh.SCmd_UnSuppress,401441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almHighHigh.AEShelveTMRDN,401441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almHighHigh.Bad,401441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almHighHigh.Suppress,401442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.UnSuppress,401442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Shelve,401442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.UnShelve,401442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Enable,401442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Disable,401442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Ack,401442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Reset,401442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Suppressed,401442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Shelved,401442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Disabled,401442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Acked,401442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almHighHigh.Alarm,401442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Fault,401452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almHigh.AlarmState,401452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almHigh.GlobalReset,401452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almHigh.FaultInAlarm,401452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almHigh.ALRM,401452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almHigh.ANUN,401452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almHigh.AKED,401452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almHigh.Resetable,401452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almHigh.REST,401452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almHigh.ACKN,401452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almHigh.UACK,401452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almHigh.MCmd_Enable,401452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almHigh.MCmd_Disable,401452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almHigh.OCmd_Shelve,401452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almHigh.OCmd_Unshelve,401452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almHigh.SCmd_Suppress,401452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almHigh.SCmd_UnSuppress,401453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almHigh.AEShelveTMRDN,401453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almHigh.Bad,401453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almHigh.Suppress,401454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.UnSuppress,401454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Shelve,401454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.UnShelve,401454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Enable,401454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Disable,401454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Ack,401454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Reset,401454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almHigh.Suppressed,401454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almHigh.Shelved,401454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almHigh.Disabled,401454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almHigh.Acked,401454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almHigh.Alarm,401454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Fault,401464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almLow.AlarmState,401464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almLow.GlobalReset,401464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almLow.FaultInAlarm,401464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almLow.ALRM,401464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almLow.ANUN,401464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almLow.AKED,401464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almLow.Resetable,401464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almLow.REST,401464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almLow.ACKN,401464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almLow.UACK,401464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almLow.MCmd_Enable,401464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almLow.MCmd_Disable,401464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almLow.OCmd_Shelve,401464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almLow.OCmd_Unshelve,401464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almLow.SCmd_Suppress,401464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almLow.SCmd_UnSuppress,401465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almLow.AEShelveTMRDN,401465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almLow.Bad,401465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almLow.Suppress,401466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.UnSuppress,401466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Shelve,401466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.UnShelve,401466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Enable,401466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Disable,401466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Ack,401466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Reset,401466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almLow.Suppressed,401466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almLow.Shelved,401466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almLow.Disabled,401466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almLow.Acked,401466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almLow.Alarm,401466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Fault,401476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almLowLow.AlarmState,401476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almLowLow.GlobalReset,401476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almLowLow.FaultInAlarm,401476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almLowLow.ALRM,401476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almLowLow.ANUN,401476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almLowLow.AKED,401476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almLowLow.Resetable,401476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almLowLow.REST,401476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almLowLow.ACKN,401476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almLowLow.UACK,401476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almLowLow.MCmd_Enable,401476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almLowLow.MCmd_Disable,401476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almLowLow.OCmd_Shelve,401476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almLowLow.OCmd_Unshelve,401476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almLowLow.SCmd_Suppress,401476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almLowLow.SCmd_UnSuppress,401477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almLowLow.AEShelveTMRDN,401477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almLowLow.Bad,401477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almLowLow.Suppress,401478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.UnSuppress,401478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Shelve,401478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.UnShelve,401478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Enable,401478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Disable,401478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Ack,401478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Reset,401478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almLowLow.Suppressed,401478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almLowLow.Shelved,401478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almLowLow.Disabled,401478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almLowLow.Acked,401478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almLowLow.Alarm,401478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Fault,401488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almBrokenLoop.AlarmState,401488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almBrokenLoop.GlobalReset,401488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almBrokenLoop.FaultInAlarm,401488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almBrokenLoop.ALRM,401488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almBrokenLoop.ANUN,401488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almBrokenLoop.AKED,401488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almBrokenLoop.Resetable,401488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almBrokenLoop.REST,401488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almBrokenLoop.ACKN,401488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almBrokenLoop.UACK,401488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almBrokenLoop.MCmd_Enable,401488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.MCmd_Disable,401488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.OCmd_Shelve,401488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.OCmd_Unshelve,401488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.SCmd_Suppress,401488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.SCmd_UnSuppress,401489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almBrokenLoop.AEShelveTMRDN,401489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almBrokenLoop.Bad,401489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almBrokenLoop.Suppress,401490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.UnSuppress,401490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Shelve,401490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.UnShelve,401490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Enable,401490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Disable,401490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Ack,401490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Reset,401490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Suppressed,401490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Shelved,401490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Disabled,401490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Acked,401490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almBrokenLoop.Alarm,401490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Fault,401500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almOverRange.AlarmState,401500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almOverRange.GlobalReset,401500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almOverRange.FaultInAlarm,401500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almOverRange.ALRM,401500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almOverRange.ANUN,401500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almOverRange.AKED,401500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almOverRange.Resetable,401500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almOverRange.REST,401500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almOverRange.ACKN,401500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almOverRange.UACK,401500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almOverRange.MCmd_Enable,401500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almOverRange.MCmd_Disable,401500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almOverRange.OCmd_Shelve,401500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almOverRange.OCmd_Unshelve,401500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almOverRange.SCmd_Suppress,401500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almOverRange.SCmd_UnSuppress,401501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almOverRange.AEShelveTMRDN,401501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almOverRange.Bad,401501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almOverRange.Suppress,401502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.UnSuppress,401502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Shelve,401502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.UnShelve,401502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Enable,401502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Disable,401502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Ack,401502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Reset,401502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almOverRange.Suppressed,401502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almOverRange.Shelved,401502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almOverRange.Disabled,401502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almOverRange.Acked,401502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almOverRange.Alarm,401502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Fault,401512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almUnderRange.AlarmState,401512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almUnderRange.GlobalReset,401512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almUnderRange.FaultInAlarm,401512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almUnderRange.ALRM,401512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almUnderRange.ANUN,401512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almUnderRange.AKED,401512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almUnderRange.Resetable,401512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almUnderRange.REST,401512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almUnderRange.ACKN,401512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almUnderRange.UACK,401512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almUnderRange.MCmd_Enable,401512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almUnderRange.MCmd_Disable,401512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almUnderRange.OCmd_Shelve,401512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almUnderRange.OCmd_Unshelve,401512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almUnderRange.SCmd_Suppress,401512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almUnderRange.SCmd_UnSuppress,401513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almUnderRange.AEShelveTMRDN,401513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almUnderRange.Bad,401513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almUnderRange.Suppress,401514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.UnSuppress,401514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Shelve,401514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.UnShelve,401514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Enable,401514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Disable,401514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Ack,401514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Reset,401514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Suppressed,401514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Shelved,401514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Disabled,401514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Acked,401514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almUnderRange.Alarm,401514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Fault,401524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almRateOfChange.AlarmState,401524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almRateOfChange.GlobalReset,401524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almRateOfChange.FaultInAlarm,401524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almRateOfChange.ALRM,401524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almRateOfChange.ANUN,401524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almRateOfChange.AKED,401524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almRateOfChange.Resetable,401524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almRateOfChange.REST,401524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almRateOfChange.ACKN,401524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almRateOfChange.UACK,401524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almRateOfChange.MCmd_Enable,401524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.MCmd_Disable,401524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.OCmd_Shelve,401524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.OCmd_Unshelve,401524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.SCmd_Suppress,401524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.SCmd_UnSuppress,401525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almRateOfChange.AEShelveTMRDN,401525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almRateOfChange.Bad,401525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almRateOfChange.Suppress,401526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.UnSuppress,401526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Shelve,401526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.UnShelve,401526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Enable,401526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Disable,401526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Ack,401526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Reset,401526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Suppressed,401526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Shelved,401526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Disabled,401526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Acked,401526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almRateOfChange.Alarm,401526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Fault,401536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_TT_0130_1_TI.almPLCFault.AlarmState,401536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_TT_0130_1_TI.almPLCFault.GlobalReset,401536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_TT_0130_1_TI.almPLCFault.FaultInAlarm,401536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_TT_0130_1_TI.almPLCFault.ALRM,401536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_TT_0130_1_TI.almPLCFault.ANUN,401536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_TT_0130_1_TI.almPLCFault.AKED,401536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_TT_0130_1_TI.almPLCFault.Resetable,401536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_TT_0130_1_TI.almPLCFault.REST,401536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_TT_0130_1_TI.almPLCFault.ACKN,401536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_TT_0130_1_TI.almPLCFault.UACK,401536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_TT_0130_1_TI.almPLCFault.MCmd_Enable,401536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_TT_0130_1_TI.almPLCFault.MCmd_Disable,401536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_TT_0130_1_TI.almPLCFault.OCmd_Shelve,401536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_TT_0130_1_TI.almPLCFault.OCmd_Unshelve,401536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_TT_0130_1_TI.almPLCFault.SCmd_Suppress,401536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_TT_0130_1_TI.almPLCFault.SCmd_UnSuppress,401537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_TT_0130_1_TI.almPLCFault.AEShelveTMRDN,401537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_TT_0130_1_TI.almPLCFault.Bad,401537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_TT_0130_1_TI.almPLCFault.Suppress,401538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.UnSuppress,401538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Shelve,401538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.UnShelve,401538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Enable,401538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Disable,401538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Ack,401538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Reset,401538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Suppressed,401538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Shelved,401538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Disabled,401538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Acked,401538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_TT_0130_1_TI.almPLCFault.Alarm,401538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Fault,402606.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_XA1.Alarm.AlarmState,402606.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_XA1.Alarm.GlobalReset,402606.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_XA1.Alarm.FaultInAlarm,402606.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA1.Alarm.ALRM,402606.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_XA1.Alarm.ANUN,402606.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_XA1.Alarm.AKED,402606.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_XA1.Alarm.Resetable,402606.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_XA1.Alarm.REST,402606.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_XA1.Alarm.ACKN,402606.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_XA1.Alarm.UACK,402606.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_XA1.Alarm.MCmd_Enable,402606.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA1.Alarm.MCmd_Disable,402606.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA1.Alarm.OCmd_Shelve,402606.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_XA1.Alarm.OCmd_Unshelve,402606.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_XA1.Alarm.SCmd_Suppress,402606.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_XA1.Alarm.SCmd_UnSuppress,402607.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_XA1.Alarm.AEShelveTMRDN,402607.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_XA1.Alarm.Bad,402607.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_XA1.Alarm.Suppress,402608.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.UnSuppress,402608.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Shelve,402608.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.UnShelve,402608.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Enable,402608.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Disable,402608.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Ack,402608.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Reset,402608.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Suppressed,402608.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Shelved,402608.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Disabled,402608.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Acked,402608.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_XA1.Alarm.Alarm,402608.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Fault,402618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_XA1.almPLCFault.AlarmState,402618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_XA1.almPLCFault.GlobalReset,402618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_XA1.almPLCFault.FaultInAlarm,402618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA1.almPLCFault.ALRM,402618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_XA1.almPLCFault.ANUN,402618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_XA1.almPLCFault.AKED,402618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_XA1.almPLCFault.Resetable,402618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_XA1.almPLCFault.REST,402618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_XA1.almPLCFault.ACKN,402618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_XA1.almPLCFault.UACK,402618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_XA1.almPLCFault.MCmd_Enable,402618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.MCmd_Disable,402618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.OCmd_Shelve,402618.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.OCmd_Unshelve,402618.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.SCmd_Suppress,402618.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.SCmd_UnSuppress,402619.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_XA1.almPLCFault.AEShelveTMRDN,402619.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_XA1.almPLCFault.Bad,402619.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_XA1.almPLCFault.Suppress,402620.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.UnSuppress,402620.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Shelve,402620.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.UnShelve,402620.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Enable,402620.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Disable,402620.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Ack,402620.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Reset,402620.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Suppressed,402620.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Shelved,402620.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Disabled,402620.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Acked,402620.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_XA1.almPLCFault.Alarm,402620.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Fault,402446.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LL.Alarm.AlarmState,402446.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LL.Alarm.GlobalReset,402446.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LL.Alarm.FaultInAlarm,402446.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LL.Alarm.ALRM,402446.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LL.Alarm.ANUN,402446.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LL.Alarm.AKED,402446.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LL.Alarm.Resetable,402446.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LL.Alarm.REST,402446.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LL.Alarm.ACKN,402446.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LL.Alarm.UACK,402446.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LL.Alarm.MCmd_Enable,402446.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LL.Alarm.MCmd_Disable,402446.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LL.Alarm.OCmd_Shelve,402446.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LL.Alarm.OCmd_Unshelve,402446.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LL.Alarm.SCmd_Suppress,402446.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LL.Alarm.SCmd_UnSuppress,402447.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LL.Alarm.AEShelveTMRDN,402447.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LL.Alarm.Bad,402447.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LL.Alarm.Suppress,402448.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.UnSuppress,402448.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Shelve,402448.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.UnShelve,402448.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Enable,402448.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Disable,402448.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Ack,402448.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Reset,402448.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LL.Alarm.Suppressed,402448.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LL.Alarm.Shelved,402448.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LL.Alarm.Disabled,402448.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LL.Alarm.Acked,402448.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LL.Alarm.Alarm,402448.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Fault,402458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_LL.almPLCFault.AlarmState,402458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_LL.almPLCFault.GlobalReset,402458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_LL.almPLCFault.FaultInAlarm,402458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_LL.almPLCFault.ALRM,402458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_LL.almPLCFault.ANUN,402458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_LL.almPLCFault.AKED,402458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_LL.almPLCFault.Resetable,402458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_LL.almPLCFault.REST,402458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_LL.almPLCFault.ACKN,402458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_LL.almPLCFault.UACK,402458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_LL.almPLCFault.MCmd_Enable,402458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.MCmd_Disable,402458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.OCmd_Shelve,402458.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.OCmd_Unshelve,402458.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.SCmd_Suppress,402458.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.SCmd_UnSuppress,402459.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_LL.almPLCFault.AEShelveTMRDN,402459.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_LL.almPLCFault.Bad,402459.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_LL.almPLCFault.Suppress,402460.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.UnSuppress,402460.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Shelve,402460.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.UnShelve,402460.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Enable,402460.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Disable,402460.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Ack,402460.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Reset,402460.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Suppressed,402460.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Shelved,402460.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Disabled,402460.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Acked,402460.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_LL.almPLCFault.Alarm,402460.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Fault,402486.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_PL.Alarm.AlarmState,402486.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_PL.Alarm.GlobalReset,402486.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_PL.Alarm.FaultInAlarm,402486.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_PL.Alarm.ALRM,402486.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_PL.Alarm.ANUN,402486.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_PL.Alarm.AKED,402486.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_PL.Alarm.Resetable,402486.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_PL.Alarm.REST,402486.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_PL.Alarm.ACKN,402486.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_PL.Alarm.UACK,402486.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_PL.Alarm.MCmd_Enable,402486.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_PL.Alarm.MCmd_Disable,402486.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_PL.Alarm.OCmd_Shelve,402486.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_PL.Alarm.OCmd_Unshelve,402486.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_PL.Alarm.SCmd_Suppress,402486.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_PL.Alarm.SCmd_UnSuppress,402487.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_PL.Alarm.AEShelveTMRDN,402487.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_PL.Alarm.Bad,402487.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_PL.Alarm.Suppress,402488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.UnSuppress,402488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Shelve,402488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.UnShelve,402488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Enable,402488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Disable,402488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Ack,402488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Reset,402488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_PL.Alarm.Suppressed,402488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_PL.Alarm.Shelved,402488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_PL.Alarm.Disabled,402488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_PL.Alarm.Acked,402488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_PL.Alarm.Alarm,402488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Fault,402498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_PL.almPLCFault.AlarmState,402498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_PL.almPLCFault.GlobalReset,402498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_PL.almPLCFault.FaultInAlarm,402498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_PL.almPLCFault.ALRM,402498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_PL.almPLCFault.ANUN,402498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_PL.almPLCFault.AKED,402498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_PL.almPLCFault.Resetable,402498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_PL.almPLCFault.REST,402498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_PL.almPLCFault.ACKN,402498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_PL.almPLCFault.UACK,402498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_PL.almPLCFault.MCmd_Enable,402498.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.MCmd_Disable,402498.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.OCmd_Shelve,402498.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.OCmd_Unshelve,402498.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.SCmd_Suppress,402498.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.SCmd_UnSuppress,402499.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_PL.almPLCFault.AEShelveTMRDN,402499.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_PL.almPLCFault.Bad,402499.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_PL.almPLCFault.Suppress,402500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.UnSuppress,402500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Shelve,402500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.UnShelve,402500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Enable,402500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Disable,402500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Ack,402500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Reset,402500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Suppressed,402500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Shelved,402500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Disabled,402500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Acked,402500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_PL.almPLCFault.Alarm,402500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Fault,402526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_SH.Alarm.AlarmState,402526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_SH.Alarm.GlobalReset,402526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_SH.Alarm.FaultInAlarm,402526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_SH.Alarm.ALRM,402526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_SH.Alarm.ANUN,402526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_SH.Alarm.AKED,402526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_SH.Alarm.Resetable,402526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_SH.Alarm.REST,402526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_SH.Alarm.ACKN,402526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_SH.Alarm.UACK,402526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_SH.Alarm.MCmd_Enable,402526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_SH.Alarm.MCmd_Disable,402526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_SH.Alarm.OCmd_Shelve,402526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_SH.Alarm.OCmd_Unshelve,402526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_SH.Alarm.SCmd_Suppress,402526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_SH.Alarm.SCmd_UnSuppress,402527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_SH.Alarm.AEShelveTMRDN,402527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_SH.Alarm.Bad,402527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_SH.Alarm.Suppress,402528.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.UnSuppress,402528.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Shelve,402528.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.UnShelve,402528.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Enable,402528.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Disable,402528.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Ack,402528.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Reset,402528.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_SH.Alarm.Suppressed,402528.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_SH.Alarm.Shelved,402528.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_SH.Alarm.Disabled,402528.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_SH.Alarm.Acked,402528.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_SH.Alarm.Alarm,402528.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Fault,402538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_SH.almPLCFault.AlarmState,402538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_SH.almPLCFault.GlobalReset,402538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_SH.almPLCFault.FaultInAlarm,402538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_SH.almPLCFault.ALRM,402538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_SH.almPLCFault.ANUN,402538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_SH.almPLCFault.AKED,402538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_SH.almPLCFault.Resetable,402538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_SH.almPLCFault.REST,402538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_SH.almPLCFault.ACKN,402538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_SH.almPLCFault.UACK,402538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_SH.almPLCFault.MCmd_Enable,402538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.MCmd_Disable,402538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.OCmd_Shelve,402538.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.OCmd_Unshelve,402538.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.SCmd_Suppress,402538.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.SCmd_UnSuppress,402539.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_SH.almPLCFault.AEShelveTMRDN,402539.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_SH.almPLCFault.Bad,402539.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_SH.almPLCFault.Suppress,402540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.UnSuppress,402540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Shelve,402540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.UnShelve,402540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Enable,402540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Disable,402540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Ack,402540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Reset,402540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Suppressed,402540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Shelved,402540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Disabled,402540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Acked,402540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_SH.almPLCFault.Alarm,402540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Fault,402566.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_TH.Alarm.AlarmState,402566.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_TH.Alarm.GlobalReset,402566.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_TH.Alarm.FaultInAlarm,402566.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_TH.Alarm.ALRM,402566.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_TH.Alarm.ANUN,402566.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_TH.Alarm.AKED,402566.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_TH.Alarm.Resetable,402566.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_TH.Alarm.REST,402566.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_TH.Alarm.ACKN,402566.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_TH.Alarm.UACK,402566.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_TH.Alarm.MCmd_Enable,402566.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_TH.Alarm.MCmd_Disable,402566.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_TH.Alarm.OCmd_Shelve,402566.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_TH.Alarm.OCmd_Unshelve,402566.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_TH.Alarm.SCmd_Suppress,402566.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_TH.Alarm.SCmd_UnSuppress,402567.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_TH.Alarm.AEShelveTMRDN,402567.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_TH.Alarm.Bad,402567.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_TH.Alarm.Suppress,402568.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.UnSuppress,402568.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Shelve,402568.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.UnShelve,402568.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Enable,402568.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Disable,402568.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Ack,402568.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Reset,402568.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_TH.Alarm.Suppressed,402568.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_TH.Alarm.Shelved,402568.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_TH.Alarm.Disabled,402568.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_TH.Alarm.Acked,402568.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_TH.Alarm.Alarm,402568.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Fault,402578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_TH.almPLCFault.AlarmState,402578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_TH.almPLCFault.GlobalReset,402578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_TH.almPLCFault.FaultInAlarm,402578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_TH.almPLCFault.ALRM,402578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_TH.almPLCFault.ANUN,402578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_TH.almPLCFault.AKED,402578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_TH.almPLCFault.Resetable,402578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_TH.almPLCFault.REST,402578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_TH.almPLCFault.ACKN,402578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_TH.almPLCFault.UACK,402578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_TH.almPLCFault.MCmd_Enable,402578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.MCmd_Disable,402578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.OCmd_Shelve,402578.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.OCmd_Unshelve,402578.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.SCmd_Suppress,402578.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.SCmd_UnSuppress,402579.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_TH.almPLCFault.AEShelveTMRDN,402579.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_TH.almPLCFault.Bad,402579.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_TH.almPLCFault.Suppress,402580.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.UnSuppress,402580.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Shelve,402580.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.UnShelve,402580.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Enable,402580.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Disable,402580.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Ack,402580.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Reset,402580.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Suppressed,402580.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Shelved,402580.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Disabled,402580.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Acked,402580.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_TH.almPLCFault.Alarm,402580.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Fault,402646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_XA2.Alarm.AlarmState,402646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_XA2.Alarm.GlobalReset,402646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_XA2.Alarm.FaultInAlarm,402646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA2.Alarm.ALRM,402646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_XA2.Alarm.ANUN,402646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_XA2.Alarm.AKED,402646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_XA2.Alarm.Resetable,402646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_XA2.Alarm.REST,402646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_XA2.Alarm.ACKN,402646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_XA2.Alarm.UACK,402646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_XA2.Alarm.MCmd_Enable,402646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA2.Alarm.MCmd_Disable,402646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA2.Alarm.OCmd_Shelve,402646.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_XA2.Alarm.OCmd_Unshelve,402646.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_XA2.Alarm.SCmd_Suppress,402646.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_XA2.Alarm.SCmd_UnSuppress,402647.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_XA2.Alarm.AEShelveTMRDN,402647.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_XA2.Alarm.Bad,402647.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_XA2.Alarm.Suppress,402648.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.UnSuppress,402648.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Shelve,402648.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.UnShelve,402648.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Enable,402648.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Disable,402648.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Ack,402648.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Reset,402648.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Suppressed,402648.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Shelved,402648.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Disabled,402648.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Acked,402648.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_XA2.Alarm.Alarm,402648.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Fault,402658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_2_XA2.almPLCFault.AlarmState,402658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_2_XA2.almPLCFault.GlobalReset,402658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_2_XA2.almPLCFault.FaultInAlarm,402658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_2_XA2.almPLCFault.ALRM,402658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_2_XA2.almPLCFault.ANUN,402658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_2_XA2.almPLCFault.AKED,402658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_2_XA2.almPLCFault.Resetable,402658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_2_XA2.almPLCFault.REST,402658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_2_XA2.almPLCFault.ACKN,402658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_2_XA2.almPLCFault.UACK,402658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_2_XA2.almPLCFault.MCmd_Enable,402658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.MCmd_Disable,402658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.OCmd_Shelve,402658.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.OCmd_Unshelve,402658.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.SCmd_Suppress,402658.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.SCmd_UnSuppress,402659.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_2_XA2.almPLCFault.AEShelveTMRDN,402659.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_2_XA2.almPLCFault.Bad,402659.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_2_XA2.almPLCFault.Suppress,402660.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.UnSuppress,402660.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Shelve,402660.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.UnShelve,402660.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Enable,402660.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Disable,402660.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Ack,402660.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Reset,402660.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Suppressed,402660.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Shelved,402660.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Disabled,402660.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Acked,402660.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_2_XA2.almPLCFault.Alarm,402660.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Fault,402126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_ZS_0130_3_ZA.Alarm.AlarmState,402126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_ZS_0130_3_ZA.Alarm.GlobalReset,402126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_ZS_0130_3_ZA.Alarm.FaultInAlarm,402126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_ZS_0130_3_ZA.Alarm.ALRM,402126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_ZS_0130_3_ZA.Alarm.ANUN,402126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_ZS_0130_3_ZA.Alarm.AKED,402126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_ZS_0130_3_ZA.Alarm.Resetable,402126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_ZS_0130_3_ZA.Alarm.REST,402126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_ZS_0130_3_ZA.Alarm.ACKN,402126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_ZS_0130_3_ZA.Alarm.UACK,402126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_ZS_0130_3_ZA.Alarm.MCmd_Enable,402126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_ZS_0130_3_ZA.Alarm.MCmd_Disable,402126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_ZS_0130_3_ZA.Alarm.OCmd_Shelve,402126.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_ZS_0130_3_ZA.Alarm.OCmd_Unshelve,402126.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_ZS_0130_3_ZA.Alarm.SCmd_Suppress,402126.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_ZS_0130_3_ZA.Alarm.SCmd_UnSuppress,402127.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_ZS_0130_3_ZA.Alarm.AEShelveTMRDN,402127.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_ZS_0130_3_ZA.Alarm.Bad,402127.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_ZS_0130_3_ZA.Alarm.Suppress,402128.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.UnSuppress,402128.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Shelve,402128.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.UnShelve,402128.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Enable,402128.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Disable,402128.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Ack,402128.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Reset,402128.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Suppressed,402128.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Shelved,402128.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Disabled,402128.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Acked,402128.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_ZS_0130_3_ZA.Alarm.Alarm,402128.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Fault,402138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_ZS_0130_3_ZA.almPLCFault.AlarmState,402138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_ZS_0130_3_ZA.almPLCFault.GlobalReset,402138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_ZS_0130_3_ZA.almPLCFault.FaultInAlarm,402138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_ZS_0130_3_ZA.almPLCFault.ALRM,402138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_ZS_0130_3_ZA.almPLCFault.ANUN,402138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_ZS_0130_3_ZA.almPLCFault.AKED,402138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_ZS_0130_3_ZA.almPLCFault.Resetable,402138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_ZS_0130_3_ZA.almPLCFault.REST,402138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_ZS_0130_3_ZA.almPLCFault.ACKN,402138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_ZS_0130_3_ZA.almPLCFault.UACK,402138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_ZS_0130_3_ZA.almPLCFault.MCmd_Enable,402138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.MCmd_Disable,402138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.OCmd_Shelve,402138.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.OCmd_Unshelve,402138.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.SCmd_Suppress,402138.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.SCmd_UnSuppress,402139.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_ZS_0130_3_ZA.almPLCFault.AEShelveTMRDN,402139.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_ZS_0130_3_ZA.almPLCFault.Bad,402139.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_ZS_0130_3_ZA.almPLCFault.Suppress,402140.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.UnSuppress,402140.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Shelve,402140.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.UnShelve,402140.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Enable,402140.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Disable,402140.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Ack,402140.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Reset,402140.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Suppressed,402140.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Shelved,402140.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Disabled,402140.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Acked,402140.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_ZS_0130_3_ZA.almPLCFault.Alarm,402140.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Fault,401686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_ZA.Alarm.AlarmState,401686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_ZA.Alarm.GlobalReset,401686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_ZA.Alarm.FaultInAlarm,401686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_ZA.Alarm.ALRM,401686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_ZA.Alarm.ANUN,401686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_ZA.Alarm.AKED,401686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_ZA.Alarm.Resetable,401686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_ZA.Alarm.REST,401686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_ZA.Alarm.ACKN,401686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_ZA.Alarm.UACK,401686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_ZA.Alarm.MCmd_Enable,401686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_ZA.Alarm.MCmd_Disable,401686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_ZA.Alarm.OCmd_Shelve,401686.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_ZA.Alarm.OCmd_Unshelve,401686.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_ZA.Alarm.SCmd_Suppress,401686.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_ZA.Alarm.SCmd_UnSuppress,401687.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_ZA.Alarm.AEShelveTMRDN,401687.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_ZA.Alarm.Bad,401687.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_ZA.Alarm.Suppress,401688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.UnSuppress,401688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Shelve,401688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.UnShelve,401688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Enable,401688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Disable,401688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Ack,401688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Reset,401688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_ZA.Alarm.Suppressed,401688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_ZA.Alarm.Shelved,401688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_ZA.Alarm.Disabled,401688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_ZA.Alarm.Acked,401688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_ZA.Alarm.Alarm,401688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Fault,401698.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_ZA.almPLCFault.AlarmState,401698.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_ZA.almPLCFault.GlobalReset,401698.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_ZA.almPLCFault.FaultInAlarm,401698.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_ZA.almPLCFault.ALRM,401698.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_ZA.almPLCFault.ANUN,401698.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_ZA.almPLCFault.AKED,401698.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_ZA.almPLCFault.Resetable,401698.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_ZA.almPLCFault.REST,401698.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_ZA.almPLCFault.ACKN,401698.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_ZA.almPLCFault.UACK,401698.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_ZA.almPLCFault.MCmd_Enable,401698.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.MCmd_Disable,401698.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.OCmd_Shelve,401698.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.OCmd_Unshelve,401698.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.SCmd_Suppress,401698.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.SCmd_UnSuppress,401699.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_ZA.almPLCFault.AEShelveTMRDN,401699.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_ZA.almPLCFault.Bad,401699.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_ZA.almPLCFault.Suppress,401700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.UnSuppress,401700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Shelve,401700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.UnShelve,401700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Enable,401700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Disable,401700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Ack,401700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Reset,401700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Suppressed,401700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Shelved,401700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Disabled,401700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Acked,401700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_ZA.almPLCFault.Alarm,401700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Fault,401726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_JA.Alarm.AlarmState,401726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_JA.Alarm.GlobalReset,401726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_JA.Alarm.FaultInAlarm,401726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_JA.Alarm.ALRM,401726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_JA.Alarm.ANUN,401726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_JA.Alarm.AKED,401726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_JA.Alarm.Resetable,401726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_JA.Alarm.REST,401726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_JA.Alarm.ACKN,401726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_JA.Alarm.UACK,401726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_JA.Alarm.MCmd_Enable,401726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_JA.Alarm.MCmd_Disable,401726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_JA.Alarm.OCmd_Shelve,401726.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_JA.Alarm.OCmd_Unshelve,401726.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_JA.Alarm.SCmd_Suppress,401726.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_JA.Alarm.SCmd_UnSuppress,401727.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_JA.Alarm.AEShelveTMRDN,401727.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_JA.Alarm.Bad,401727.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_JA.Alarm.Suppress,401728.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.UnSuppress,401728.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Shelve,401728.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.UnShelve,401728.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Enable,401728.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Disable,401728.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Ack,401728.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Reset,401728.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_JA.Alarm.Suppressed,401728.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_JA.Alarm.Shelved,401728.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_JA.Alarm.Disabled,401728.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_JA.Alarm.Acked,401728.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_JA.Alarm.Alarm,401728.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Fault,401738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_JA.almPLCFault.AlarmState,401738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_JA.almPLCFault.GlobalReset,401738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_JA.almPLCFault.FaultInAlarm,401738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_JA.almPLCFault.ALRM,401738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_JA.almPLCFault.ANUN,401738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_JA.almPLCFault.AKED,401738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_JA.almPLCFault.Resetable,401738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_JA.almPLCFault.REST,401738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_JA.almPLCFault.ACKN,401738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_JA.almPLCFault.UACK,401738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_JA.almPLCFault.MCmd_Enable,401738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_JA.almPLCFault.MCmd_Disable,401738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_JA.almPLCFault.OCmd_Shelve,401738.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_JA.almPLCFault.OCmd_Unshelve,401738.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_JA.almPLCFault.SCmd_Suppress,401738.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_JA.almPLCFault.SCmd_UnSuppress,401739.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_JA.almPLCFault.AEShelveTMRDN,401739.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_JA.almPLCFault.Bad,401739.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_JA.almPLCFault.Suppress,401740.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.UnSuppress,401740.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Shelve,401740.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.UnShelve,401740.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Enable,401740.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Disable,401740.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Ack,401740.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Reset,401740.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Suppressed,401740.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Shelved,401740.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Disabled,401740.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Acked,401740.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_JA.almPLCFault.Alarm,401740.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Fault,401766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_XN.Alarm.AlarmState,401766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_XN.Alarm.GlobalReset,401766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_XN.Alarm.FaultInAlarm,401766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_XN.Alarm.ALRM,401766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_XN.Alarm.ANUN,401766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_XN.Alarm.AKED,401766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_XN.Alarm.Resetable,401766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_XN.Alarm.REST,401766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_XN.Alarm.ACKN,401766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_XN.Alarm.UACK,401766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_XN.Alarm.MCmd_Enable,401766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_XN.Alarm.MCmd_Disable,401766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_XN.Alarm.OCmd_Shelve,401766.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_XN.Alarm.OCmd_Unshelve,401766.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_XN.Alarm.SCmd_Suppress,401766.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_XN.Alarm.SCmd_UnSuppress,401767.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_XN.Alarm.AEShelveTMRDN,401767.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_XN.Alarm.Bad,401767.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_XN.Alarm.Suppress,401768.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.UnSuppress,401768.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Shelve,401768.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.UnShelve,401768.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Enable,401768.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Disable,401768.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Ack,401768.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Reset,401768.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_XN.Alarm.Suppressed,401768.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_XN.Alarm.Shelved,401768.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_XN.Alarm.Disabled,401768.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_XN.Alarm.Acked,401768.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_XN.Alarm.Alarm,401768.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Fault,401778.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_XN.almPLCFault.AlarmState,401778.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_XN.almPLCFault.GlobalReset,401778.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_XN.almPLCFault.FaultInAlarm,401778.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_XN.almPLCFault.ALRM,401778.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_XN.almPLCFault.ANUN,401778.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_XN.almPLCFault.AKED,401778.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_XN.almPLCFault.Resetable,401778.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_XN.almPLCFault.REST,401778.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_XN.almPLCFault.ACKN,401778.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_XN.almPLCFault.UACK,401778.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_XN.almPLCFault.MCmd_Enable,401778.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_XN.almPLCFault.MCmd_Disable,401778.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_XN.almPLCFault.OCmd_Shelve,401778.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_XN.almPLCFault.OCmd_Unshelve,401778.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_XN.almPLCFault.SCmd_Suppress,401778.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_XN.almPLCFault.SCmd_UnSuppress,401779.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_XN.almPLCFault.AEShelveTMRDN,401779.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_XN.almPLCFault.Bad,401779.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_XN.almPLCFault.Suppress,401780.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.UnSuppress,401780.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Shelve,401780.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.UnShelve,401780.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Enable,401780.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Disable,401780.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Ack,401780.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Reset,401780.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Suppressed,401780.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Shelved,401780.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Disabled,401780.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Acked,401780.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_XN.almPLCFault.Alarm,401780.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Fault,401606.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_PLC_002_1_ZA.Alarm.AlarmState,401606.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_PLC_002_1_ZA.Alarm.GlobalReset,401606.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_PLC_002_1_ZA.Alarm.FaultInAlarm,401606.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_ZA.Alarm.ALRM,401606.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_PLC_002_1_ZA.Alarm.ANUN,401606.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_PLC_002_1_ZA.Alarm.AKED,401606.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_PLC_002_1_ZA.Alarm.Resetable,401606.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_PLC_002_1_ZA.Alarm.REST,401606.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_PLC_002_1_ZA.Alarm.ACKN,401606.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_PLC_002_1_ZA.Alarm.UACK,401606.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_PLC_002_1_ZA.Alarm.MCmd_Enable,401606.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_ZA.Alarm.MCmd_Disable,401606.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_ZA.Alarm.OCmd_Shelve,401606.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_PLC_002_1_ZA.Alarm.OCmd_Unshelve,401606.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_PLC_002_1_ZA.Alarm.SCmd_Suppress,401606.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_PLC_002_1_ZA.Alarm.SCmd_UnSuppress,401607.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_PLC_002_1_ZA.Alarm.AEShelveTMRDN,401607.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_PLC_002_1_ZA.Alarm.Bad,401607.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_PLC_002_1_ZA.Alarm.Suppress,401608.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.UnSuppress,401608.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Shelve,401608.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.UnShelve,401608.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Enable,401608.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Disable,401608.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Ack,401608.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Reset,401608.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_PLC_002_1_ZA.Alarm.Suppressed,401608.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_PLC_002_1_ZA.Alarm.Shelved,401608.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_PLC_002_1_ZA.Alarm.Disabled,401608.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_PLC_002_1_ZA.Alarm.Acked,401608.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_PLC_002_1_ZA.Alarm.Alarm,401608.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Fault,401618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_PLC_002_1_ZA.almPLCFault.AlarmState,401618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_PLC_002_1_ZA.almPLCFault.GlobalReset,401618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_PLC_002_1_ZA.almPLCFault.FaultInAlarm,401618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_ZA.almPLCFault.ALRM,401618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_PLC_002_1_ZA.almPLCFault.ANUN,401618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_PLC_002_1_ZA.almPLCFault.AKED,401618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_PLC_002_1_ZA.almPLCFault.Resetable,401618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_PLC_002_1_ZA.almPLCFault.REST,401618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_PLC_002_1_ZA.almPLCFault.ACKN,401618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_PLC_002_1_ZA.almPLCFault.UACK,401618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_PLC_002_1_ZA.almPLCFault.MCmd_Enable,401618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.MCmd_Disable,401618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.OCmd_Shelve,401618.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.OCmd_Unshelve,401618.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.SCmd_Suppress,401618.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.SCmd_UnSuppress,401619.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_PLC_002_1_ZA.almPLCFault.AEShelveTMRDN,401619.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_PLC_002_1_ZA.almPLCFault.Bad,401619.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_PLC_002_1_ZA.almPLCFault.Suppress,401620.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.UnSuppress,401620.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Shelve,401620.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.UnShelve,401620.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Enable,401620.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Disable,401620.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Ack,401620.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Reset,401620.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Suppressed,401620.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Shelved,401620.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Disabled,401620.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Acked,401620.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_PLC_002_1_ZA.almPLCFault.Alarm,401620.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Fault,401646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_PLC_002_1_JA.Alarm.AlarmState,401646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_PLC_002_1_JA.Alarm.GlobalReset,401646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_PLC_002_1_JA.Alarm.FaultInAlarm,401646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_JA.Alarm.ALRM,401646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_PLC_002_1_JA.Alarm.ANUN,401646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_PLC_002_1_JA.Alarm.AKED,401646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_PLC_002_1_JA.Alarm.Resetable,401646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_PLC_002_1_JA.Alarm.REST,401646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_PLC_002_1_JA.Alarm.ACKN,401646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_PLC_002_1_JA.Alarm.UACK,401646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_PLC_002_1_JA.Alarm.MCmd_Enable,401646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_JA.Alarm.MCmd_Disable,401646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_JA.Alarm.OCmd_Shelve,401646.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_PLC_002_1_JA.Alarm.OCmd_Unshelve,401646.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_PLC_002_1_JA.Alarm.SCmd_Suppress,401646.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_PLC_002_1_JA.Alarm.SCmd_UnSuppress,401647.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_PLC_002_1_JA.Alarm.AEShelveTMRDN,401647.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_PLC_002_1_JA.Alarm.Bad,401647.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_PLC_002_1_JA.Alarm.Suppress,401648.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.UnSuppress,401648.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Shelve,401648.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.UnShelve,401648.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Enable,401648.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Disable,401648.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Ack,401648.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Reset,401648.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_PLC_002_1_JA.Alarm.Suppressed,401648.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_PLC_002_1_JA.Alarm.Shelved,401648.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_PLC_002_1_JA.Alarm.Disabled,401648.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_PLC_002_1_JA.Alarm.Acked,401648.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_PLC_002_1_JA.Alarm.Alarm,401648.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Fault,401658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_PLC_002_1_JA.almPLCFault.AlarmState,401658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_PLC_002_1_JA.almPLCFault.GlobalReset,401658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_PLC_002_1_JA.almPLCFault.FaultInAlarm,401658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_PLC_002_1_JA.almPLCFault.ALRM,401658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_PLC_002_1_JA.almPLCFault.ANUN,401658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_PLC_002_1_JA.almPLCFault.AKED,401658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_PLC_002_1_JA.almPLCFault.Resetable,401658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_PLC_002_1_JA.almPLCFault.REST,401658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_PLC_002_1_JA.almPLCFault.ACKN,401658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_PLC_002_1_JA.almPLCFault.UACK,401658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_PLC_002_1_JA.almPLCFault.MCmd_Enable,401658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_PLC_002_1_JA.almPLCFault.MCmd_Disable,401658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_PLC_002_1_JA.almPLCFault.OCmd_Shelve,401658.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_PLC_002_1_JA.almPLCFault.OCmd_Unshelve,401658.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_PLC_002_1_JA.almPLCFault.SCmd_Suppress,401658.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_PLC_002_1_JA.almPLCFault.SCmd_UnSuppress,401659.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_PLC_002_1_JA.almPLCFault.AEShelveTMRDN,401659.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_PLC_002_1_JA.almPLCFault.Bad,401659.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_PLC_002_1_JA.almPLCFault.Suppress,401660.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.UnSuppress,401660.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Shelve,401660.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.UnShelve,401660.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Enable,401660.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Disable,401660.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Ack,401660.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Reset,401660.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Suppressed,401660.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Shelved,401660.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Disabled,401660.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Acked,401660.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_PLC_002_1_JA.almPLCFault.Alarm,401660.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Fault,401966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SPD_0130_1_XA1.Alarm.AlarmState,401966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SPD_0130_1_XA1.Alarm.GlobalReset,401966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SPD_0130_1_XA1.Alarm.FaultInAlarm,401966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_1_XA1.Alarm.ALRM,401966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SPD_0130_1_XA1.Alarm.ANUN,401966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SPD_0130_1_XA1.Alarm.AKED,401966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SPD_0130_1_XA1.Alarm.Resetable,401966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SPD_0130_1_XA1.Alarm.REST,401966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SPD_0130_1_XA1.Alarm.ACKN,401966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SPD_0130_1_XA1.Alarm.UACK,401966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SPD_0130_1_XA1.Alarm.MCmd_Enable,401966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_1_XA1.Alarm.MCmd_Disable,401966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_1_XA1.Alarm.OCmd_Shelve,401966.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SPD_0130_1_XA1.Alarm.OCmd_Unshelve,401966.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SPD_0130_1_XA1.Alarm.SCmd_Suppress,401966.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SPD_0130_1_XA1.Alarm.SCmd_UnSuppress,401967.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SPD_0130_1_XA1.Alarm.AEShelveTMRDN,401967.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SPD_0130_1_XA1.Alarm.Bad,401967.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SPD_0130_1_XA1.Alarm.Suppress,401968.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.UnSuppress,401968.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Shelve,401968.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.UnShelve,401968.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Enable,401968.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Disable,401968.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Ack,401968.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Reset,401968.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Suppressed,401968.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Shelved,401968.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Disabled,401968.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Acked,401968.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SPD_0130_1_XA1.Alarm.Alarm,401968.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Fault,401978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SPD_0130_1_XA1.almPLCFault.AlarmState,401978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SPD_0130_1_XA1.almPLCFault.GlobalReset,401978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SPD_0130_1_XA1.almPLCFault.FaultInAlarm,401978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_1_XA1.almPLCFault.ALRM,401978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SPD_0130_1_XA1.almPLCFault.ANUN,401978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SPD_0130_1_XA1.almPLCFault.AKED,401978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SPD_0130_1_XA1.almPLCFault.Resetable,401978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SPD_0130_1_XA1.almPLCFault.REST,401978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SPD_0130_1_XA1.almPLCFault.ACKN,401978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SPD_0130_1_XA1.almPLCFault.UACK,401978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SPD_0130_1_XA1.almPLCFault.MCmd_Enable,401978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.MCmd_Disable,401978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.OCmd_Shelve,401978.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.OCmd_Unshelve,401978.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.SCmd_Suppress,401978.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.SCmd_UnSuppress,401979.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SPD_0130_1_XA1.almPLCFault.AEShelveTMRDN,401979.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SPD_0130_1_XA1.almPLCFault.Bad,401979.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SPD_0130_1_XA1.almPLCFault.Suppress,401980.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.UnSuppress,401980.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Shelve,401980.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.UnShelve,401980.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Enable,401980.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Disable,401980.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Ack,401980.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Reset,401980.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Suppressed,401980.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Shelved,401980.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Disabled,401980.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Acked,401980.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SPD_0130_1_XA1.almPLCFault.Alarm,401980.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Fault,401846.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_BC_0130_1_XA1.Alarm.AlarmState,401846.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_BC_0130_1_XA1.Alarm.GlobalReset,401846.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_BC_0130_1_XA1.Alarm.FaultInAlarm,401846.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BC_0130_1_XA1.Alarm.ALRM,401846.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_BC_0130_1_XA1.Alarm.ANUN,401846.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_BC_0130_1_XA1.Alarm.AKED,401846.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_BC_0130_1_XA1.Alarm.Resetable,401846.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_BC_0130_1_XA1.Alarm.REST,401846.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_BC_0130_1_XA1.Alarm.ACKN,401846.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_BC_0130_1_XA1.Alarm.UACK,401846.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_BC_0130_1_XA1.Alarm.MCmd_Enable,401846.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_BC_0130_1_XA1.Alarm.MCmd_Disable,401846.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_BC_0130_1_XA1.Alarm.OCmd_Shelve,401846.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_BC_0130_1_XA1.Alarm.OCmd_Unshelve,401846.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_BC_0130_1_XA1.Alarm.SCmd_Suppress,401846.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_BC_0130_1_XA1.Alarm.SCmd_UnSuppress,401847.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_BC_0130_1_XA1.Alarm.AEShelveTMRDN,401847.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_BC_0130_1_XA1.Alarm.Bad,401847.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_BC_0130_1_XA1.Alarm.Suppress,401848.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.UnSuppress,401848.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Shelve,401848.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.UnShelve,401848.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Enable,401848.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Disable,401848.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Ack,401848.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Reset,401848.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_BC_0130_1_XA1.Alarm.Suppressed,401848.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_BC_0130_1_XA1.Alarm.Shelved,401848.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_BC_0130_1_XA1.Alarm.Disabled,401848.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_BC_0130_1_XA1.Alarm.Acked,401848.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_BC_0130_1_XA1.Alarm.Alarm,401848.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Fault,401858.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_BC_0130_1_XA1.almPLCFault.AlarmState,401858.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_BC_0130_1_XA1.almPLCFault.GlobalReset,401858.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_BC_0130_1_XA1.almPLCFault.FaultInAlarm,401858.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BC_0130_1_XA1.almPLCFault.ALRM,401858.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_BC_0130_1_XA1.almPLCFault.ANUN,401858.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_BC_0130_1_XA1.almPLCFault.AKED,401858.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_BC_0130_1_XA1.almPLCFault.Resetable,401858.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_BC_0130_1_XA1.almPLCFault.REST,401858.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_BC_0130_1_XA1.almPLCFault.ACKN,401858.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_BC_0130_1_XA1.almPLCFault.UACK,401858.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_BC_0130_1_XA1.almPLCFault.MCmd_Enable,401858.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.MCmd_Disable,401858.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.OCmd_Shelve,401858.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.OCmd_Unshelve,401858.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.SCmd_Suppress,401858.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.SCmd_UnSuppress,401859.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_BC_0130_1_XA1.almPLCFault.AEShelveTMRDN,401859.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_BC_0130_1_XA1.almPLCFault.Bad,401859.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_BC_0130_1_XA1.almPLCFault.Suppress,401860.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.UnSuppress,401860.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Shelve,401860.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.UnShelve,401860.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Enable,401860.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Disable,401860.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Ack,401860.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Reset,401860.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Suppressed,401860.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Shelved,401860.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Disabled,401860.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Acked,401860.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_BC_0130_1_XA1.almPLCFault.Alarm,401860.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Fault,401886.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_BE_0130_2_XA2.Alarm.AlarmState,401886.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_BE_0130_2_XA2.Alarm.GlobalReset,401886.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_BE_0130_2_XA2.Alarm.FaultInAlarm,401886.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BE_0130_2_XA2.Alarm.ALRM,401886.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_BE_0130_2_XA2.Alarm.ANUN,401886.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_BE_0130_2_XA2.Alarm.AKED,401886.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_BE_0130_2_XA2.Alarm.Resetable,401886.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_BE_0130_2_XA2.Alarm.REST,401886.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_BE_0130_2_XA2.Alarm.ACKN,401886.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_BE_0130_2_XA2.Alarm.UACK,401886.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_BE_0130_2_XA2.Alarm.MCmd_Enable,401886.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_BE_0130_2_XA2.Alarm.MCmd_Disable,401886.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_BE_0130_2_XA2.Alarm.OCmd_Shelve,401886.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_BE_0130_2_XA2.Alarm.OCmd_Unshelve,401886.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_BE_0130_2_XA2.Alarm.SCmd_Suppress,401886.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_BE_0130_2_XA2.Alarm.SCmd_UnSuppress,401887.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_BE_0130_2_XA2.Alarm.AEShelveTMRDN,401887.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_BE_0130_2_XA2.Alarm.Bad,401887.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_BE_0130_2_XA2.Alarm.Suppress,401888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.UnSuppress,401888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Shelve,401888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.UnShelve,401888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Enable,401888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Disable,401888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Ack,401888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Reset,401888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_BE_0130_2_XA2.Alarm.Suppressed,401888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_BE_0130_2_XA2.Alarm.Shelved,401888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_BE_0130_2_XA2.Alarm.Disabled,401888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_BE_0130_2_XA2.Alarm.Acked,401888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_BE_0130_2_XA2.Alarm.Alarm,401888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Fault,401898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_BE_0130_2_XA2.almPLCFault.AlarmState,401898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_BE_0130_2_XA2.almPLCFault.GlobalReset,401898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_BE_0130_2_XA2.almPLCFault.FaultInAlarm,401898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_BE_0130_2_XA2.almPLCFault.ALRM,401898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_BE_0130_2_XA2.almPLCFault.ANUN,401898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_BE_0130_2_XA2.almPLCFault.AKED,401898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_BE_0130_2_XA2.almPLCFault.Resetable,401898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_BE_0130_2_XA2.almPLCFault.REST,401898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_BE_0130_2_XA2.almPLCFault.ACKN,401898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_BE_0130_2_XA2.almPLCFault.UACK,401898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_BE_0130_2_XA2.almPLCFault.MCmd_Enable,401898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.MCmd_Disable,401898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.OCmd_Shelve,401898.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.OCmd_Unshelve,401898.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.SCmd_Suppress,401898.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.SCmd_UnSuppress,401899.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_BE_0130_2_XA2.almPLCFault.AEShelveTMRDN,401899.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_BE_0130_2_XA2.almPLCFault.Bad,401899.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_BE_0130_2_XA2.almPLCFault.Suppress,401900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.UnSuppress,401900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Shelve,401900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.UnShelve,401900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Enable,401900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Disable,401900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Ack,401900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Reset,401900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Suppressed,401900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Shelved,401900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Disabled,401900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Acked,401900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_BE_0130_2_XA2.almPLCFault.Alarm,401900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Fault,402206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LL.Alarm.AlarmState,402206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LL.Alarm.GlobalReset,402206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LL.Alarm.FaultInAlarm,402206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LL.Alarm.ALRM,402206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LL.Alarm.ANUN,402206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LL.Alarm.AKED,402206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LL.Alarm.Resetable,402206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LL.Alarm.REST,402206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LL.Alarm.ACKN,402206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LL.Alarm.UACK,402206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LL.Alarm.MCmd_Enable,402206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LL.Alarm.MCmd_Disable,402206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LL.Alarm.OCmd_Shelve,402206.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LL.Alarm.OCmd_Unshelve,402206.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LL.Alarm.SCmd_Suppress,402206.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LL.Alarm.SCmd_UnSuppress,402207.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LL.Alarm.AEShelveTMRDN,402207.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LL.Alarm.Bad,402207.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LL.Alarm.Suppress,402208.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.UnSuppress,402208.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Shelve,402208.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.UnShelve,402208.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Enable,402208.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Disable,402208.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Ack,402208.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Reset,402208.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LL.Alarm.Suppressed,402208.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LL.Alarm.Shelved,402208.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LL.Alarm.Disabled,402208.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LL.Alarm.Acked,402208.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LL.Alarm.Alarm,402208.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Fault,402218.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_LL.almPLCFault.AlarmState,402218.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_LL.almPLCFault.GlobalReset,402218.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_LL.almPLCFault.FaultInAlarm,402218.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_LL.almPLCFault.ALRM,402218.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_LL.almPLCFault.ANUN,402218.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_LL.almPLCFault.AKED,402218.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_LL.almPLCFault.Resetable,402218.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_LL.almPLCFault.REST,402218.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_LL.almPLCFault.ACKN,402218.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_LL.almPLCFault.UACK,402218.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_LL.almPLCFault.MCmd_Enable,402218.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.MCmd_Disable,402218.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.OCmd_Shelve,402218.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.OCmd_Unshelve,402218.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.SCmd_Suppress,402218.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.SCmd_UnSuppress,402219.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_LL.almPLCFault.AEShelveTMRDN,402219.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_LL.almPLCFault.Bad,402219.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_LL.almPLCFault.Suppress,402220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.UnSuppress,402220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Shelve,402220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.UnShelve,402220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Enable,402220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Disable,402220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Ack,402220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Reset,402220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Suppressed,402220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Shelved,402220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Disabled,402220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Acked,402220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_LL.almPLCFault.Alarm,402220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Fault,402246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_PL.Alarm.AlarmState,402246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_PL.Alarm.GlobalReset,402246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_PL.Alarm.FaultInAlarm,402246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_PL.Alarm.ALRM,402246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_PL.Alarm.ANUN,402246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_PL.Alarm.AKED,402246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_PL.Alarm.Resetable,402246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_PL.Alarm.REST,402246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_PL.Alarm.ACKN,402246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_PL.Alarm.UACK,402246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_PL.Alarm.MCmd_Enable,402246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_PL.Alarm.MCmd_Disable,402246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_PL.Alarm.OCmd_Shelve,402246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_PL.Alarm.OCmd_Unshelve,402246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_PL.Alarm.SCmd_Suppress,402246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_PL.Alarm.SCmd_UnSuppress,402247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_PL.Alarm.AEShelveTMRDN,402247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_PL.Alarm.Bad,402247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_PL.Alarm.Suppress,402248.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.UnSuppress,402248.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Shelve,402248.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.UnShelve,402248.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Enable,402248.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Disable,402248.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Ack,402248.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Reset,402248.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_PL.Alarm.Suppressed,402248.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_PL.Alarm.Shelved,402248.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_PL.Alarm.Disabled,402248.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_PL.Alarm.Acked,402248.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_PL.Alarm.Alarm,402248.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Fault,402258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_PL.almPLCFault.AlarmState,402258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_PL.almPLCFault.GlobalReset,402258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_PL.almPLCFault.FaultInAlarm,402258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_PL.almPLCFault.ALRM,402258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_PL.almPLCFault.ANUN,402258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_PL.almPLCFault.AKED,402258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_PL.almPLCFault.Resetable,402258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_PL.almPLCFault.REST,402258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_PL.almPLCFault.ACKN,402258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_PL.almPLCFault.UACK,402258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_PL.almPLCFault.MCmd_Enable,402258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.MCmd_Disable,402258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.OCmd_Shelve,402258.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.OCmd_Unshelve,402258.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.SCmd_Suppress,402258.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.SCmd_UnSuppress,402259.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_PL.almPLCFault.AEShelveTMRDN,402259.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_PL.almPLCFault.Bad,402259.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_PL.almPLCFault.Suppress,402260.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.UnSuppress,402260.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Shelve,402260.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.UnShelve,402260.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Enable,402260.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Disable,402260.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Ack,402260.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Reset,402260.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Suppressed,402260.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Shelved,402260.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Disabled,402260.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Acked,402260.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_PL.almPLCFault.Alarm,402260.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Fault,402286.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_SH.Alarm.AlarmState,402286.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_SH.Alarm.GlobalReset,402286.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_SH.Alarm.FaultInAlarm,402286.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_SH.Alarm.ALRM,402286.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_SH.Alarm.ANUN,402286.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_SH.Alarm.AKED,402286.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_SH.Alarm.Resetable,402286.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_SH.Alarm.REST,402286.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_SH.Alarm.ACKN,402286.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_SH.Alarm.UACK,402286.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_SH.Alarm.MCmd_Enable,402286.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_SH.Alarm.MCmd_Disable,402286.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_SH.Alarm.OCmd_Shelve,402286.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_SH.Alarm.OCmd_Unshelve,402286.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_SH.Alarm.SCmd_Suppress,402286.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_SH.Alarm.SCmd_UnSuppress,402287.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_SH.Alarm.AEShelveTMRDN,402287.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_SH.Alarm.Bad,402287.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_SH.Alarm.Suppress,402288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.UnSuppress,402288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Shelve,402288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.UnShelve,402288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Enable,402288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Disable,402288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Ack,402288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Reset,402288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_SH.Alarm.Suppressed,402288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_SH.Alarm.Shelved,402288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_SH.Alarm.Disabled,402288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_SH.Alarm.Acked,402288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_SH.Alarm.Alarm,402288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Fault,402298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_SH.almPLCFault.AlarmState,402298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_SH.almPLCFault.GlobalReset,402298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_SH.almPLCFault.FaultInAlarm,402298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_SH.almPLCFault.ALRM,402298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_SH.almPLCFault.ANUN,402298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_SH.almPLCFault.AKED,402298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_SH.almPLCFault.Resetable,402298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_SH.almPLCFault.REST,402298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_SH.almPLCFault.ACKN,402298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_SH.almPLCFault.UACK,402298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_SH.almPLCFault.MCmd_Enable,402298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.MCmd_Disable,402298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.OCmd_Shelve,402298.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.OCmd_Unshelve,402298.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.SCmd_Suppress,402298.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.SCmd_UnSuppress,402299.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_SH.almPLCFault.AEShelveTMRDN,402299.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_SH.almPLCFault.Bad,402299.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_SH.almPLCFault.Suppress,402300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.UnSuppress,402300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Shelve,402300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.UnShelve,402300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Enable,402300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Disable,402300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Ack,402300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Reset,402300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Suppressed,402300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Shelved,402300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Disabled,402300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Acked,402300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_SH.almPLCFault.Alarm,402300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Fault,402326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_TH.Alarm.AlarmState,402326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_TH.Alarm.GlobalReset,402326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_TH.Alarm.FaultInAlarm,402326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_TH.Alarm.ALRM,402326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_TH.Alarm.ANUN,402326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_TH.Alarm.AKED,402326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_TH.Alarm.Resetable,402326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_TH.Alarm.REST,402326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_TH.Alarm.ACKN,402326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_TH.Alarm.UACK,402326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_TH.Alarm.MCmd_Enable,402326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_TH.Alarm.MCmd_Disable,402326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_TH.Alarm.OCmd_Shelve,402326.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_TH.Alarm.OCmd_Unshelve,402326.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_TH.Alarm.SCmd_Suppress,402326.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_TH.Alarm.SCmd_UnSuppress,402327.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_TH.Alarm.AEShelveTMRDN,402327.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_TH.Alarm.Bad,402327.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_TH.Alarm.Suppress,402328.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.UnSuppress,402328.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Shelve,402328.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.UnShelve,402328.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Enable,402328.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Disable,402328.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Ack,402328.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Reset,402328.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_TH.Alarm.Suppressed,402328.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_TH.Alarm.Shelved,402328.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_TH.Alarm.Disabled,402328.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_TH.Alarm.Acked,402328.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_TH.Alarm.Alarm,402328.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Fault,402338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_TH.almPLCFault.AlarmState,402338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_TH.almPLCFault.GlobalReset,402338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_TH.almPLCFault.FaultInAlarm,402338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_TH.almPLCFault.ALRM,402338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_TH.almPLCFault.ANUN,402338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_TH.almPLCFault.AKED,402338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_TH.almPLCFault.Resetable,402338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_TH.almPLCFault.REST,402338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_TH.almPLCFault.ACKN,402338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_TH.almPLCFault.UACK,402338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_TH.almPLCFault.MCmd_Enable,402338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.MCmd_Disable,402338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.OCmd_Shelve,402338.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.OCmd_Unshelve,402338.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.SCmd_Suppress,402338.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.SCmd_UnSuppress,402339.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_TH.almPLCFault.AEShelveTMRDN,402339.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_TH.almPLCFault.Bad,402339.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_TH.almPLCFault.Suppress,402340.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.UnSuppress,402340.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Shelve,402340.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.UnShelve,402340.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Enable,402340.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Disable,402340.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Ack,402340.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Reset,402340.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Suppressed,402340.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Shelved,402340.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Disabled,402340.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Acked,402340.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_TH.almPLCFault.Alarm,402340.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Fault,402366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_XA1.Alarm.AlarmState,402366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_XA1.Alarm.GlobalReset,402366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_XA1.Alarm.FaultInAlarm,402366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA1.Alarm.ALRM,402366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_XA1.Alarm.ANUN,402366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_XA1.Alarm.AKED,402366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_XA1.Alarm.Resetable,402366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_XA1.Alarm.REST,402366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_XA1.Alarm.ACKN,402366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_XA1.Alarm.UACK,402366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_XA1.Alarm.MCmd_Enable,402366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA1.Alarm.MCmd_Disable,402366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA1.Alarm.OCmd_Shelve,402366.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_XA1.Alarm.OCmd_Unshelve,402366.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_XA1.Alarm.SCmd_Suppress,402366.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_XA1.Alarm.SCmd_UnSuppress,402367.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_XA1.Alarm.AEShelveTMRDN,402367.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_XA1.Alarm.Bad,402367.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_XA1.Alarm.Suppress,402368.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.UnSuppress,402368.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Shelve,402368.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.UnShelve,402368.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Enable,402368.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Disable,402368.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Ack,402368.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Reset,402368.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Suppressed,402368.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Shelved,402368.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Disabled,402368.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Acked,402368.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_XA1.Alarm.Alarm,402368.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Fault,402378.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_XA1.almPLCFault.AlarmState,402378.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_XA1.almPLCFault.GlobalReset,402378.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_XA1.almPLCFault.FaultInAlarm,402378.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA1.almPLCFault.ALRM,402378.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_XA1.almPLCFault.ANUN,402378.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_XA1.almPLCFault.AKED,402378.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_XA1.almPLCFault.Resetable,402378.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_XA1.almPLCFault.REST,402378.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_XA1.almPLCFault.ACKN,402378.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_XA1.almPLCFault.UACK,402378.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_XA1.almPLCFault.MCmd_Enable,402378.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.MCmd_Disable,402378.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.OCmd_Shelve,402378.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.OCmd_Unshelve,402378.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.SCmd_Suppress,402378.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.SCmd_UnSuppress,402379.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_XA1.almPLCFault.AEShelveTMRDN,402379.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_XA1.almPLCFault.Bad,402379.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_XA1.almPLCFault.Suppress,402380.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.UnSuppress,402380.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Shelve,402380.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.UnShelve,402380.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Enable,402380.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Disable,402380.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Ack,402380.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Reset,402380.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Suppressed,402380.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Shelved,402380.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Disabled,402380.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Acked,402380.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_XA1.almPLCFault.Alarm,402380.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Fault,402406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_XA2.Alarm.AlarmState,402406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_XA2.Alarm.GlobalReset,402406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_XA2.Alarm.FaultInAlarm,402406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA2.Alarm.ALRM,402406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_XA2.Alarm.ANUN,402406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_XA2.Alarm.AKED,402406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_XA2.Alarm.Resetable,402406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_XA2.Alarm.REST,402406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_XA2.Alarm.ACKN,402406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_XA2.Alarm.UACK,402406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_XA2.Alarm.MCmd_Enable,402406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA2.Alarm.MCmd_Disable,402406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA2.Alarm.OCmd_Shelve,402406.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_XA2.Alarm.OCmd_Unshelve,402406.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_XA2.Alarm.SCmd_Suppress,402406.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_XA2.Alarm.SCmd_UnSuppress,402407.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_XA2.Alarm.AEShelveTMRDN,402407.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_XA2.Alarm.Bad,402407.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_XA2.Alarm.Suppress,402408.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.UnSuppress,402408.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Shelve,402408.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.UnShelve,402408.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Enable,402408.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Disable,402408.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Ack,402408.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Reset,402408.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Suppressed,402408.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Shelved,402408.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Disabled,402408.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Acked,402408.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_XA2.Alarm.Alarm,402408.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Fault,402418.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_GEN_0130_1_XA2.almPLCFault.AlarmState,402418.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_GEN_0130_1_XA2.almPLCFault.GlobalReset,402418.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_GEN_0130_1_XA2.almPLCFault.FaultInAlarm,402418.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_GEN_0130_1_XA2.almPLCFault.ALRM,402418.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_GEN_0130_1_XA2.almPLCFault.ANUN,402418.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_GEN_0130_1_XA2.almPLCFault.AKED,402418.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_GEN_0130_1_XA2.almPLCFault.Resetable,402418.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_GEN_0130_1_XA2.almPLCFault.REST,402418.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_GEN_0130_1_XA2.almPLCFault.ACKN,402418.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_GEN_0130_1_XA2.almPLCFault.UACK,402418.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_GEN_0130_1_XA2.almPLCFault.MCmd_Enable,402418.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.MCmd_Disable,402418.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.OCmd_Shelve,402418.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.OCmd_Unshelve,402418.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.SCmd_Suppress,402418.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.SCmd_UnSuppress,402419.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_GEN_0130_1_XA2.almPLCFault.AEShelveTMRDN,402419.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_GEN_0130_1_XA2.almPLCFault.Bad,402419.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_GEN_0130_1_XA2.almPLCFault.Suppress,402420.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.UnSuppress,402420.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Shelve,402420.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.UnShelve,402420.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Enable,402420.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Disable,402420.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Ack,402420.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Reset,402420.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Suppressed,402420.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Shelved,402420.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Disabled,402420.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Acked,402420.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_GEN_0130_1_XA2.almPLCFault.Alarm,402420.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Fault,401806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_BM.Alarm.AlarmState,401806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_BM.Alarm.GlobalReset,401806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_BM.Alarm.FaultInAlarm,401806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_BM.Alarm.ALRM,401806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_BM.Alarm.ANUN,401806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_BM.Alarm.AKED,401806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_BM.Alarm.Resetable,401806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_BM.Alarm.REST,401806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_BM.Alarm.ACKN,401806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_BM.Alarm.UACK,401806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_BM.Alarm.MCmd_Enable,401806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_BM.Alarm.MCmd_Disable,401806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_BM.Alarm.OCmd_Shelve,401806.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_BM.Alarm.OCmd_Unshelve,401806.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_BM.Alarm.SCmd_Suppress,401806.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_BM.Alarm.SCmd_UnSuppress,401807.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_BM.Alarm.AEShelveTMRDN,401807.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_BM.Alarm.Bad,401807.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_BM.Alarm.Suppress,401808.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.UnSuppress,401808.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Shelve,401808.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.UnShelve,401808.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Enable,401808.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Disable,401808.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Ack,401808.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Reset,401808.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_BM.Alarm.Suppressed,401808.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_BM.Alarm.Shelved,401808.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_BM.Alarm.Disabled,401808.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_BM.Alarm.Acked,401808.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_BM.Alarm.Alarm,401808.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Fault,401818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_NIP_002_1_BM.almPLCFault.AlarmState,401818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_NIP_002_1_BM.almPLCFault.GlobalReset,401818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_NIP_002_1_BM.almPLCFault.FaultInAlarm,401818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_NIP_002_1_BM.almPLCFault.ALRM,401818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_NIP_002_1_BM.almPLCFault.ANUN,401818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_NIP_002_1_BM.almPLCFault.AKED,401818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_NIP_002_1_BM.almPLCFault.Resetable,401818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_NIP_002_1_BM.almPLCFault.REST,401818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_NIP_002_1_BM.almPLCFault.ACKN,401818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_NIP_002_1_BM.almPLCFault.UACK,401818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_NIP_002_1_BM.almPLCFault.MCmd_Enable,401818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_NIP_002_1_BM.almPLCFault.MCmd_Disable,401818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_NIP_002_1_BM.almPLCFault.OCmd_Shelve,401818.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_NIP_002_1_BM.almPLCFault.OCmd_Unshelve,401818.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_NIP_002_1_BM.almPLCFault.SCmd_Suppress,401818.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_NIP_002_1_BM.almPLCFault.SCmd_UnSuppress,401819.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_NIP_002_1_BM.almPLCFault.AEShelveTMRDN,401819.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_NIP_002_1_BM.almPLCFault.Bad,401819.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_NIP_002_1_BM.almPLCFault.Suppress,401820.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.UnSuppress,401820.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Shelve,401820.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.UnShelve,401820.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Enable,401820.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Disable,401820.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Ack,401820.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Reset,401820.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Suppressed,401820.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Shelved,401820.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Disabled,401820.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Acked,401820.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_NIP_002_1_BM.almPLCFault.Alarm,401820.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Fault,401926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SD_0130_1_XA.Alarm.AlarmState,401926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SD_0130_1_XA.Alarm.GlobalReset,401926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SD_0130_1_XA.Alarm.FaultInAlarm,401926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SD_0130_1_XA.Alarm.ALRM,401926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SD_0130_1_XA.Alarm.ANUN,401926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SD_0130_1_XA.Alarm.AKED,401926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SD_0130_1_XA.Alarm.Resetable,401926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SD_0130_1_XA.Alarm.REST,401926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SD_0130_1_XA.Alarm.ACKN,401926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SD_0130_1_XA.Alarm.UACK,401926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SD_0130_1_XA.Alarm.MCmd_Enable,401926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SD_0130_1_XA.Alarm.MCmd_Disable,401926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SD_0130_1_XA.Alarm.OCmd_Shelve,401926.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SD_0130_1_XA.Alarm.OCmd_Unshelve,401926.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SD_0130_1_XA.Alarm.SCmd_Suppress,401926.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SD_0130_1_XA.Alarm.SCmd_UnSuppress,401927.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SD_0130_1_XA.Alarm.AEShelveTMRDN,401927.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SD_0130_1_XA.Alarm.Bad,401927.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SD_0130_1_XA.Alarm.Suppress,401928.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.UnSuppress,401928.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Shelve,401928.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.UnShelve,401928.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Enable,401928.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Disable,401928.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Ack,401928.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Reset,401928.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SD_0130_1_XA.Alarm.Suppressed,401928.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SD_0130_1_XA.Alarm.Shelved,401928.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SD_0130_1_XA.Alarm.Disabled,401928.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SD_0130_1_XA.Alarm.Acked,401928.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SD_0130_1_XA.Alarm.Alarm,401928.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Fault,401938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SD_0130_1_XA.almPLCFault.AlarmState,401938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SD_0130_1_XA.almPLCFault.GlobalReset,401938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SD_0130_1_XA.almPLCFault.FaultInAlarm,401938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SD_0130_1_XA.almPLCFault.ALRM,401938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SD_0130_1_XA.almPLCFault.ANUN,401938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SD_0130_1_XA.almPLCFault.AKED,401938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SD_0130_1_XA.almPLCFault.Resetable,401938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SD_0130_1_XA.almPLCFault.REST,401938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SD_0130_1_XA.almPLCFault.ACKN,401938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SD_0130_1_XA.almPLCFault.UACK,401938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SD_0130_1_XA.almPLCFault.MCmd_Enable,401938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SD_0130_1_XA.almPLCFault.MCmd_Disable,401938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SD_0130_1_XA.almPLCFault.OCmd_Shelve,401938.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SD_0130_1_XA.almPLCFault.OCmd_Unshelve,401938.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SD_0130_1_XA.almPLCFault.SCmd_Suppress,401938.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SD_0130_1_XA.almPLCFault.SCmd_UnSuppress,401939.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SD_0130_1_XA.almPLCFault.AEShelveTMRDN,401939.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SD_0130_1_XA.almPLCFault.Bad,401939.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SD_0130_1_XA.almPLCFault.Suppress,401940.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.UnSuppress,401940.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Shelve,401940.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.UnShelve,401940.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Enable,401940.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Disable,401940.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Ack,401940.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Reset,401940.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Suppressed,401940.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Shelved,401940.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Disabled,401940.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Acked,401940.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SD_0130_1_XA.almPLCFault.Alarm,401940.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Fault,402006.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SPD_0130_2_XA2.Alarm.AlarmState,402006.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SPD_0130_2_XA2.Alarm.GlobalReset,402006.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SPD_0130_2_XA2.Alarm.FaultInAlarm,402006.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_2_XA2.Alarm.ALRM,402006.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SPD_0130_2_XA2.Alarm.ANUN,402006.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SPD_0130_2_XA2.Alarm.AKED,402006.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SPD_0130_2_XA2.Alarm.Resetable,402006.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SPD_0130_2_XA2.Alarm.REST,402006.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SPD_0130_2_XA2.Alarm.ACKN,402006.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SPD_0130_2_XA2.Alarm.UACK,402006.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SPD_0130_2_XA2.Alarm.MCmd_Enable,402006.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_2_XA2.Alarm.MCmd_Disable,402006.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_2_XA2.Alarm.OCmd_Shelve,402006.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SPD_0130_2_XA2.Alarm.OCmd_Unshelve,402006.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SPD_0130_2_XA2.Alarm.SCmd_Suppress,402006.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SPD_0130_2_XA2.Alarm.SCmd_UnSuppress,402007.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SPD_0130_2_XA2.Alarm.AEShelveTMRDN,402007.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SPD_0130_2_XA2.Alarm.Bad,402007.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SPD_0130_2_XA2.Alarm.Suppress,402008.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.UnSuppress,402008.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Shelve,402008.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.UnShelve,402008.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Enable,402008.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Disable,402008.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Ack,402008.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Reset,402008.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Suppressed,402008.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Shelved,402008.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Disabled,402008.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Acked,402008.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SPD_0130_2_XA2.Alarm.Alarm,402008.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Fault,402018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SPD_0130_2_XA2.almPLCFault.AlarmState,402018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SPD_0130_2_XA2.almPLCFault.GlobalReset,402018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SPD_0130_2_XA2.almPLCFault.FaultInAlarm,402018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SPD_0130_2_XA2.almPLCFault.ALRM,402018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SPD_0130_2_XA2.almPLCFault.ANUN,402018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SPD_0130_2_XA2.almPLCFault.AKED,402018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SPD_0130_2_XA2.almPLCFault.Resetable,402018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SPD_0130_2_XA2.almPLCFault.REST,402018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SPD_0130_2_XA2.almPLCFault.ACKN,402018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SPD_0130_2_XA2.almPLCFault.UACK,402018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SPD_0130_2_XA2.almPLCFault.MCmd_Enable,402018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.MCmd_Disable,402018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.OCmd_Shelve,402018.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.OCmd_Unshelve,402018.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.SCmd_Suppress,402018.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.SCmd_UnSuppress,402019.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SPD_0130_2_XA2.almPLCFault.AEShelveTMRDN,402019.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SPD_0130_2_XA2.almPLCFault.Bad,402019.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SPD_0130_2_XA2.almPLCFault.Suppress,402020.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.UnSuppress,402020.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Shelve,402020.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.UnShelve,402020.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Enable,402020.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Disable,402020.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Ack,402020.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Reset,402020.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Suppressed,402020.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Shelved,402020.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Disabled,402020.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Acked,402020.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SPD_0130_2_XA2.almPLCFault.Alarm,402020.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Fault,402046.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SWG_0130_1_XN1.Alarm.AlarmState,402046.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SWG_0130_1_XN1.Alarm.GlobalReset,402046.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SWG_0130_1_XN1.Alarm.FaultInAlarm,402046.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN1.Alarm.ALRM,402046.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SWG_0130_1_XN1.Alarm.ANUN,402046.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SWG_0130_1_XN1.Alarm.AKED,402046.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SWG_0130_1_XN1.Alarm.Resetable,402046.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SWG_0130_1_XN1.Alarm.REST,402046.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SWG_0130_1_XN1.Alarm.ACKN,402046.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SWG_0130_1_XN1.Alarm.UACK,402046.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SWG_0130_1_XN1.Alarm.MCmd_Enable,402046.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN1.Alarm.MCmd_Disable,402046.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN1.Alarm.OCmd_Shelve,402046.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SWG_0130_1_XN1.Alarm.OCmd_Unshelve,402046.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SWG_0130_1_XN1.Alarm.SCmd_Suppress,402046.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SWG_0130_1_XN1.Alarm.SCmd_UnSuppress,402047.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SWG_0130_1_XN1.Alarm.AEShelveTMRDN,402047.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SWG_0130_1_XN1.Alarm.Bad,402047.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SWG_0130_1_XN1.Alarm.Suppress,402048.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.UnSuppress,402048.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Shelve,402048.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.UnShelve,402048.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Enable,402048.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Disable,402048.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Ack,402048.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Reset,402048.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Suppressed,402048.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Shelved,402048.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Disabled,402048.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Acked,402048.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SWG_0130_1_XN1.Alarm.Alarm,402048.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Fault,402058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SWG_0130_1_XN1.almPLCFault.AlarmState,402058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SWG_0130_1_XN1.almPLCFault.GlobalReset,402058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SWG_0130_1_XN1.almPLCFault.FaultInAlarm,402058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN1.almPLCFault.ALRM,402058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SWG_0130_1_XN1.almPLCFault.ANUN,402058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SWG_0130_1_XN1.almPLCFault.AKED,402058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SWG_0130_1_XN1.almPLCFault.Resetable,402058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SWG_0130_1_XN1.almPLCFault.REST,402058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SWG_0130_1_XN1.almPLCFault.ACKN,402058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SWG_0130_1_XN1.almPLCFault.UACK,402058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SWG_0130_1_XN1.almPLCFault.MCmd_Enable,402058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.MCmd_Disable,402058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.OCmd_Shelve,402058.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.OCmd_Unshelve,402058.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.SCmd_Suppress,402058.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.SCmd_UnSuppress,402059.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SWG_0130_1_XN1.almPLCFault.AEShelveTMRDN,402059.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SWG_0130_1_XN1.almPLCFault.Bad,402059.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SWG_0130_1_XN1.almPLCFault.Suppress,402060.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.UnSuppress,402060.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Shelve,402060.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.UnShelve,402060.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Enable,402060.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Disable,402060.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Ack,402060.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Reset,402060.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Suppressed,402060.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Shelved,402060.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Disabled,402060.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Acked,402060.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SWG_0130_1_XN1.almPLCFault.Alarm,402060.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Fault,402086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SWG_0130_1_XN2.Alarm.AlarmState,402086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SWG_0130_1_XN2.Alarm.GlobalReset,402086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SWG_0130_1_XN2.Alarm.FaultInAlarm,402086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN2.Alarm.ALRM,402086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SWG_0130_1_XN2.Alarm.ANUN,402086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SWG_0130_1_XN2.Alarm.AKED,402086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SWG_0130_1_XN2.Alarm.Resetable,402086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SWG_0130_1_XN2.Alarm.REST,402086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SWG_0130_1_XN2.Alarm.ACKN,402086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SWG_0130_1_XN2.Alarm.UACK,402086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SWG_0130_1_XN2.Alarm.MCmd_Enable,402086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN2.Alarm.MCmd_Disable,402086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN2.Alarm.OCmd_Shelve,402086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SWG_0130_1_XN2.Alarm.OCmd_Unshelve,402086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SWG_0130_1_XN2.Alarm.SCmd_Suppress,402086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SWG_0130_1_XN2.Alarm.SCmd_UnSuppress,402087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SWG_0130_1_XN2.Alarm.AEShelveTMRDN,402087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SWG_0130_1_XN2.Alarm.Bad,402087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SWG_0130_1_XN2.Alarm.Suppress,402088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.UnSuppress,402088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Shelve,402088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.UnShelve,402088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Enable,402088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Disable,402088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Ack,402088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Reset,402088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Suppressed,402088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Shelved,402088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Disabled,402088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Acked,402088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SWG_0130_1_XN2.Alarm.Alarm,402088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Fault,402098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state."
WA3252_SWG_0130_1_XN2.almPLCFault.AlarmState,402098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition"
WA3252_SWG_0130_1_XN2.almPLCFault.GlobalReset,402098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC"
WA3252_SWG_0130_1_XN2.almPLCFault.FaultInAlarm,402098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)"
WA3252_SWG_0130_1_XN2.almPLCFault.ALRM,402098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state."
WA3252_SWG_0130_1_XN2.almPLCFault.ANUN,402098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again."
WA3252_SWG_0130_1_XN2.almPLCFault.AKED,402098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups"
WA3252_SWG_0130_1_XN2.almPLCFault.Resetable,402098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared."
WA3252_SWG_0130_1_XN2.almPLCFault.REST,402098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only"
WA3252_SWG_0130_1_XN2.almPLCFault.ACKN,402098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command"
WA3252_SWG_0130_1_XN2.almPLCFault.UACK,402098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status"
WA3252_SWG_0130_1_XN2.almPLCFault.MCmd_Enable,402098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.MCmd_Disable,402098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.OCmd_Shelve,402098.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.OCmd_Unshelve,402098.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.SCmd_Suppress,402098.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.SCmd_UnSuppress,402099.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm"
WA3252_SWG_0130_1_XN2.almPLCFault.AEShelveTMRDN,402099.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done"
WA3252_SWG_0130_1_XN2.almPLCFault.Bad,402099.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition"
WA3252_SWG_0130_1_XN2.almPLCFault.Suppress,402100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.UnSuppress,402100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Shelve,402100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.UnShelve,402100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Enable,402100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Disable,402100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Ack,402100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Reset,402100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Suppressed,402100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Shelved,402100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Disabled,402100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Acked,402100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server"
WA3252_SWG_0130_1_XN2.almPLCFault.Alarm,402100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server"
WA3252_GEN_0130_1_LI.Totalize.First_Scan,401148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:"
WA3252_GEN_0130_1_LI.Totalize.EnableTot,401148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum"
WA3252_GEN_0130_1_LI.Totalize.REST,401148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals"
WA3252_GEN_0130_1_LI.Totalize.RollDay,401148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_GEN_0130_2_LI.Totalize.First_Scan,401348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:"
WA3252_GEN_0130_2_LI.Totalize.EnableTot,401348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum"
WA3252_GEN_0130_2_LI.Totalize.REST,401348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals"
WA3252_GEN_0130_2_LI.Totalize.RollDay,401348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_TT_0130_1_TI.Totalize.First_Scan,401548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:"
WA3252_TT_0130_1_TI.Totalize.EnableTot,401548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum"
WA3252_TT_0130_1_TI.Totalize.REST,401548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals"
WA3252_TT_0130_1_TI.Totalize.RollDay,401548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[1],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[2],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[3],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[4],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[5],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[6],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[7],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[8],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[9],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[10],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[11],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[12],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[13],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[14],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[15],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[16],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[17],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[18],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[19],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[20],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[21],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[22],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[23],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[24],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[25],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[26],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[27],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[28],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[29],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[30],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[31],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31)
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[1],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[2],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[3],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[4],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[5],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[6],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[7],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[8],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects
WA3252_GEN_0130_1_LI.Totalize.TimeBase,401154,Long,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day"
WA3252_GEN_0130_1_LI.Totalize.TwoMinuteCount,401192,Long,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_GEN_0130_2_LI.Totalize.TimeBase,401354,Long,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day"
WA3252_GEN_0130_2_LI.Totalize.TwoMinuteCount,401392,Long,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_TT_0130_1_TI.Totalize.TimeBase,401554,Long,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day"
WA3252_TT_0130_1_TI.Totalize.TwoMinuteCount,401592,Long,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_GEN_0130_1_LI.almHighHigh.BOOLS1,401040,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almHighHigh.BOOLS2,401041,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almHighHigh.AEBOOLS,401042,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almHighHigh.INT1,401043,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almHighHigh.INT2,401044,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almHighHigh.AENotify,401045,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almHighHigh.AESeverity,401046,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almHighHigh.AEShelveDuration,401047,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almHigh.BOOLS1,401052,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almHigh.BOOLS2,401053,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almHigh.AEBOOLS,401054,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almHigh.INT1,401055,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almHigh.INT2,401056,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almHigh.AENotify,401057,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almHigh.AESeverity,401058,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almHigh.AEShelveDuration,401059,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almLow.BOOLS1,401064,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almLow.BOOLS2,401065,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almLow.AEBOOLS,401066,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almLow.INT1,401067,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almLow.INT2,401068,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almLow.AENotify,401069,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almLow.AESeverity,401070,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almLow.AEShelveDuration,401071,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almLowLow.BOOLS1,401076,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almLowLow.BOOLS2,401077,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almLowLow.AEBOOLS,401078,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almLowLow.INT1,401079,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almLowLow.INT2,401080,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almLowLow.AENotify,401081,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almLowLow.AESeverity,401082,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almLowLow.AEShelveDuration,401083,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almBrokenLoop.BOOLS1,401088,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almBrokenLoop.BOOLS2,401089,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almBrokenLoop.AEBOOLS,401090,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almBrokenLoop.INT1,401091,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almBrokenLoop.INT2,401092,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almBrokenLoop.AENotify,401093,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almBrokenLoop.AESeverity,401094,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almBrokenLoop.AEShelveDuration,401095,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almOverRange.BOOLS1,401100,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almOverRange.BOOLS2,401101,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almOverRange.AEBOOLS,401102,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almOverRange.INT1,401103,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almOverRange.INT2,401104,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almOverRange.AENotify,401105,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almOverRange.AESeverity,401106,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almOverRange.AEShelveDuration,401107,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almUnderRange.BOOLS1,401112,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almUnderRange.BOOLS2,401113,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almUnderRange.AEBOOLS,401114,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almUnderRange.INT1,401115,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almUnderRange.INT2,401116,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almUnderRange.AENotify,401117,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almUnderRange.AESeverity,401118,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almUnderRange.AEShelveDuration,401119,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almRateOfChange.BOOLS1,401124,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almRateOfChange.BOOLS2,401125,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almRateOfChange.AEBOOLS,401126,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almRateOfChange.INT1,401127,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almRateOfChange.INT2,401128,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almRateOfChange.AENotify,401129,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almRateOfChange.AESeverity,401130,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almRateOfChange.AEShelveDuration,401131,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.almPLCFault.BOOLS1,401136,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LI.almPLCFault.BOOLS2,401137,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LI.almPLCFault.AEBOOLS,401138,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LI.almPLCFault.INT1,401139,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almPLCFault.INT2,401140,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LI.almPLCFault.AENotify,401141,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LI.almPLCFault.AESeverity,401142,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LI.almPLCFault.AEShelveDuration,401143,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almHighHigh.BOOLS1,401240,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almHighHigh.BOOLS2,401241,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almHighHigh.AEBOOLS,401242,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almHighHigh.INT1,401243,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almHighHigh.INT2,401244,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almHighHigh.AENotify,401245,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almHighHigh.AESeverity,401246,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almHighHigh.AEShelveDuration,401247,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almHigh.BOOLS1,401252,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almHigh.BOOLS2,401253,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almHigh.AEBOOLS,401254,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almHigh.INT1,401255,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almHigh.INT2,401256,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almHigh.AENotify,401257,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almHigh.AESeverity,401258,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almHigh.AEShelveDuration,401259,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almLow.BOOLS1,401264,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almLow.BOOLS2,401265,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almLow.AEBOOLS,401266,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almLow.INT1,401267,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almLow.INT2,401268,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almLow.AENotify,401269,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almLow.AESeverity,401270,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almLow.AEShelveDuration,401271,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almLowLow.BOOLS1,401276,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almLowLow.BOOLS2,401277,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almLowLow.AEBOOLS,401278,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almLowLow.INT1,401279,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almLowLow.INT2,401280,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almLowLow.AENotify,401281,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almLowLow.AESeverity,401282,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almLowLow.AEShelveDuration,401283,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almBrokenLoop.BOOLS1,401288,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almBrokenLoop.BOOLS2,401289,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almBrokenLoop.AEBOOLS,401290,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almBrokenLoop.INT1,401291,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almBrokenLoop.INT2,401292,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almBrokenLoop.AENotify,401293,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almBrokenLoop.AESeverity,401294,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almBrokenLoop.AEShelveDuration,401295,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almOverRange.BOOLS1,401300,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almOverRange.BOOLS2,401301,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almOverRange.AEBOOLS,401302,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almOverRange.INT1,401303,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almOverRange.INT2,401304,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almOverRange.AENotify,401305,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almOverRange.AESeverity,401306,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almOverRange.AEShelveDuration,401307,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almUnderRange.BOOLS1,401312,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almUnderRange.BOOLS2,401313,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almUnderRange.AEBOOLS,401314,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almUnderRange.INT1,401315,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almUnderRange.INT2,401316,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almUnderRange.AENotify,401317,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almUnderRange.AESeverity,401318,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almUnderRange.AEShelveDuration,401319,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almRateOfChange.BOOLS1,401324,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almRateOfChange.BOOLS2,401325,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almRateOfChange.AEBOOLS,401326,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almRateOfChange.INT1,401327,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almRateOfChange.INT2,401328,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almRateOfChange.AENotify,401329,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almRateOfChange.AESeverity,401330,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almRateOfChange.AEShelveDuration,401331,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LI.almPLCFault.BOOLS1,401336,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LI.almPLCFault.BOOLS2,401337,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LI.almPLCFault.AEBOOLS,401338,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LI.almPLCFault.INT1,401339,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almPLCFault.INT2,401340,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LI.almPLCFault.AENotify,401341,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LI.almPLCFault.AESeverity,401342,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LI.almPLCFault.AEShelveDuration,401343,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almHighHigh.BOOLS1,401440,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almHighHigh.BOOLS2,401441,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almHighHigh.AEBOOLS,401442,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almHighHigh.INT1,401443,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almHighHigh.INT2,401444,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almHighHigh.AENotify,401445,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almHighHigh.AESeverity,401446,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almHighHigh.AEShelveDuration,401447,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almHigh.BOOLS1,401452,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almHigh.BOOLS2,401453,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almHigh.AEBOOLS,401454,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almHigh.INT1,401455,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almHigh.INT2,401456,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almHigh.AENotify,401457,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almHigh.AESeverity,401458,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almHigh.AEShelveDuration,401459,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almLow.BOOLS1,401464,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almLow.BOOLS2,401465,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almLow.AEBOOLS,401466,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almLow.INT1,401467,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almLow.INT2,401468,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almLow.AENotify,401469,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almLow.AESeverity,401470,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almLow.AEShelveDuration,401471,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almLowLow.BOOLS1,401476,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almLowLow.BOOLS2,401477,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almLowLow.AEBOOLS,401478,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almLowLow.INT1,401479,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almLowLow.INT2,401480,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almLowLow.AENotify,401481,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almLowLow.AESeverity,401482,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almLowLow.AEShelveDuration,401483,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almBrokenLoop.BOOLS1,401488,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almBrokenLoop.BOOLS2,401489,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almBrokenLoop.AEBOOLS,401490,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almBrokenLoop.INT1,401491,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almBrokenLoop.INT2,401492,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almBrokenLoop.AENotify,401493,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almBrokenLoop.AESeverity,401494,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almBrokenLoop.AEShelveDuration,401495,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almOverRange.BOOLS1,401500,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almOverRange.BOOLS2,401501,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almOverRange.AEBOOLS,401502,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almOverRange.INT1,401503,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almOverRange.INT2,401504,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almOverRange.AENotify,401505,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almOverRange.AESeverity,401506,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almOverRange.AEShelveDuration,401507,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almUnderRange.BOOLS1,401512,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almUnderRange.BOOLS2,401513,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almUnderRange.AEBOOLS,401514,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almUnderRange.INT1,401515,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almUnderRange.INT2,401516,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almUnderRange.AENotify,401517,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almUnderRange.AESeverity,401518,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almUnderRange.AEShelveDuration,401519,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almRateOfChange.BOOLS1,401524,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almRateOfChange.BOOLS2,401525,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almRateOfChange.AEBOOLS,401526,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almRateOfChange.INT1,401527,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almRateOfChange.INT2,401528,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almRateOfChange.AENotify,401529,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almRateOfChange.AESeverity,401530,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almRateOfChange.AEShelveDuration,401531,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_TT_0130_1_TI.almPLCFault.BOOLS1,401536,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_TT_0130_1_TI.almPLCFault.BOOLS2,401537,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_TT_0130_1_TI.almPLCFault.AEBOOLS,401538,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_TT_0130_1_TI.almPLCFault.INT1,401539,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almPLCFault.INT2,401540,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_TT_0130_1_TI.almPLCFault.AENotify,401541,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_TT_0130_1_TI.almPLCFault.AESeverity,401542,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_TT_0130_1_TI.almPLCFault.AEShelveDuration,401543,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_XA1.Alarm.BOOLS1,402606,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_XA1.Alarm.BOOLS2,402607,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_XA1.Alarm.AEBOOLS,402608,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_XA1.Alarm.INT1,402609,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA1.Alarm.INT2,402610,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA1.Alarm.AENotify,402611,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_XA1.Alarm.AESeverity,402612,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_XA1.Alarm.AEShelveDuration,402613,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_XA1.almPLCFault.BOOLS1,402618,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_XA1.almPLCFault.BOOLS2,402619,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_XA1.almPLCFault.AEBOOLS,402620,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_XA1.almPLCFault.INT1,402621,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA1.almPLCFault.INT2,402622,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA1.almPLCFault.AENotify,402623,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_XA1.almPLCFault.AESeverity,402624,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_XA1.almPLCFault.AEShelveDuration,402625,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LL.Alarm.BOOLS1,402446,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LL.Alarm.BOOLS2,402447,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LL.Alarm.AEBOOLS,402448,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LL.Alarm.INT1,402449,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LL.Alarm.INT2,402450,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LL.Alarm.AENotify,402451,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LL.Alarm.AESeverity,402452,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LL.Alarm.AEShelveDuration,402453,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_LL.almPLCFault.BOOLS1,402458,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_LL.almPLCFault.BOOLS2,402459,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_LL.almPLCFault.AEBOOLS,402460,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_LL.almPLCFault.INT1,402461,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LL.almPLCFault.INT2,402462,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_LL.almPLCFault.AENotify,402463,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_LL.almPLCFault.AESeverity,402464,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_LL.almPLCFault.AEShelveDuration,402465,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_PL.Alarm.BOOLS1,402486,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_PL.Alarm.BOOLS2,402487,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_PL.Alarm.AEBOOLS,402488,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_PL.Alarm.INT1,402489,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_PL.Alarm.INT2,402490,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_PL.Alarm.AENotify,402491,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_PL.Alarm.AESeverity,402492,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_PL.Alarm.AEShelveDuration,402493,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_PL.almPLCFault.BOOLS1,402498,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_PL.almPLCFault.BOOLS2,402499,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_PL.almPLCFault.AEBOOLS,402500,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_PL.almPLCFault.INT1,402501,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_PL.almPLCFault.INT2,402502,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_PL.almPLCFault.AENotify,402503,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_PL.almPLCFault.AESeverity,402504,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_PL.almPLCFault.AEShelveDuration,402505,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_SH.Alarm.BOOLS1,402526,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_SH.Alarm.BOOLS2,402527,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_SH.Alarm.AEBOOLS,402528,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_SH.Alarm.INT1,402529,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_SH.Alarm.INT2,402530,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_SH.Alarm.AENotify,402531,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_SH.Alarm.AESeverity,402532,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_SH.Alarm.AEShelveDuration,402533,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_SH.almPLCFault.BOOLS1,402538,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_SH.almPLCFault.BOOLS2,402539,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_SH.almPLCFault.AEBOOLS,402540,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_SH.almPLCFault.INT1,402541,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_SH.almPLCFault.INT2,402542,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_SH.almPLCFault.AENotify,402543,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_SH.almPLCFault.AESeverity,402544,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_SH.almPLCFault.AEShelveDuration,402545,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_TH.Alarm.BOOLS1,402566,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_TH.Alarm.BOOLS2,402567,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_TH.Alarm.AEBOOLS,402568,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_TH.Alarm.INT1,402569,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_TH.Alarm.INT2,402570,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_TH.Alarm.AENotify,402571,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_TH.Alarm.AESeverity,402572,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_TH.Alarm.AEShelveDuration,402573,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_TH.almPLCFault.BOOLS1,402578,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_TH.almPLCFault.BOOLS2,402579,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_TH.almPLCFault.AEBOOLS,402580,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_TH.almPLCFault.INT1,402581,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_TH.almPLCFault.INT2,402582,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_TH.almPLCFault.AENotify,402583,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_TH.almPLCFault.AESeverity,402584,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_TH.almPLCFault.AEShelveDuration,402585,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_XA2.Alarm.BOOLS1,402646,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_XA2.Alarm.BOOLS2,402647,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_XA2.Alarm.AEBOOLS,402648,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_XA2.Alarm.INT1,402649,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA2.Alarm.INT2,402650,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA2.Alarm.AENotify,402651,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_XA2.Alarm.AESeverity,402652,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_XA2.Alarm.AEShelveDuration,402653,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_2_XA2.almPLCFault.BOOLS1,402658,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_2_XA2.almPLCFault.BOOLS2,402659,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_2_XA2.almPLCFault.AEBOOLS,402660,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_2_XA2.almPLCFault.INT1,402661,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA2.almPLCFault.INT2,402662,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_2_XA2.almPLCFault.AENotify,402663,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_2_XA2.almPLCFault.AESeverity,402664,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_2_XA2.almPLCFault.AEShelveDuration,402665,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_ZS_0130_3_ZA.Alarm.BOOLS1,402126,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_ZS_0130_3_ZA.Alarm.BOOLS2,402127,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_ZS_0130_3_ZA.Alarm.AEBOOLS,402128,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_ZS_0130_3_ZA.Alarm.INT1,402129,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_ZS_0130_3_ZA.Alarm.INT2,402130,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_ZS_0130_3_ZA.Alarm.AENotify,402131,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_ZS_0130_3_ZA.Alarm.AESeverity,402132,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_ZS_0130_3_ZA.Alarm.AEShelveDuration,402133,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_ZS_0130_3_ZA.almPLCFault.BOOLS1,402138,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_ZS_0130_3_ZA.almPLCFault.BOOLS2,402139,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_ZS_0130_3_ZA.almPLCFault.AEBOOLS,402140,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_ZS_0130_3_ZA.almPLCFault.INT1,402141,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_ZS_0130_3_ZA.almPLCFault.INT2,402142,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_ZS_0130_3_ZA.almPLCFault.AENotify,402143,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_ZS_0130_3_ZA.almPLCFault.AESeverity,402144,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_ZS_0130_3_ZA.almPLCFault.AEShelveDuration,402145,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_ZA.Alarm.BOOLS1,401686,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_ZA.Alarm.BOOLS2,401687,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_ZA.Alarm.AEBOOLS,401688,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_ZA.Alarm.INT1,401689,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_ZA.Alarm.INT2,401690,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_ZA.Alarm.AENotify,401691,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_ZA.Alarm.AESeverity,401692,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_ZA.Alarm.AEShelveDuration,401693,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_ZA.almPLCFault.BOOLS1,401698,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_ZA.almPLCFault.BOOLS2,401699,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_ZA.almPLCFault.AEBOOLS,401700,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_ZA.almPLCFault.INT1,401701,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_ZA.almPLCFault.INT2,401702,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_ZA.almPLCFault.AENotify,401703,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_ZA.almPLCFault.AESeverity,401704,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_ZA.almPLCFault.AEShelveDuration,401705,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_JA.Alarm.BOOLS1,401726,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_JA.Alarm.BOOLS2,401727,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_JA.Alarm.AEBOOLS,401728,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_JA.Alarm.INT1,401729,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_JA.Alarm.INT2,401730,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_JA.Alarm.AENotify,401731,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_JA.Alarm.AESeverity,401732,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_JA.Alarm.AEShelveDuration,401733,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_JA.almPLCFault.BOOLS1,401738,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_JA.almPLCFault.BOOLS2,401739,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_JA.almPLCFault.AEBOOLS,401740,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_JA.almPLCFault.INT1,401741,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_JA.almPLCFault.INT2,401742,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_JA.almPLCFault.AENotify,401743,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_JA.almPLCFault.AESeverity,401744,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_JA.almPLCFault.AEShelveDuration,401745,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_XN.Alarm.BOOLS1,401766,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_XN.Alarm.BOOLS2,401767,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_XN.Alarm.AEBOOLS,401768,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_XN.Alarm.INT1,401769,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_XN.Alarm.INT2,401770,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_XN.Alarm.AENotify,401771,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_XN.Alarm.AESeverity,401772,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_XN.Alarm.AEShelveDuration,401773,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_XN.almPLCFault.BOOLS1,401778,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_XN.almPLCFault.BOOLS2,401779,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_XN.almPLCFault.AEBOOLS,401780,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_XN.almPLCFault.INT1,401781,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_XN.almPLCFault.INT2,401782,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_XN.almPLCFault.AENotify,401783,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_XN.almPLCFault.AESeverity,401784,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_XN.almPLCFault.AEShelveDuration,401785,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_PLC_002_1_ZA.Alarm.BOOLS1,401606,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_PLC_002_1_ZA.Alarm.BOOLS2,401607,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_PLC_002_1_ZA.Alarm.AEBOOLS,401608,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_PLC_002_1_ZA.Alarm.INT1,401609,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_ZA.Alarm.INT2,401610,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_ZA.Alarm.AENotify,401611,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_PLC_002_1_ZA.Alarm.AESeverity,401612,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_PLC_002_1_ZA.Alarm.AEShelveDuration,401613,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_PLC_002_1_ZA.almPLCFault.BOOLS1,401618,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_PLC_002_1_ZA.almPLCFault.BOOLS2,401619,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_PLC_002_1_ZA.almPLCFault.AEBOOLS,401620,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_PLC_002_1_ZA.almPLCFault.INT1,401621,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_ZA.almPLCFault.INT2,401622,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_ZA.almPLCFault.AENotify,401623,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_PLC_002_1_ZA.almPLCFault.AESeverity,401624,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_PLC_002_1_ZA.almPLCFault.AEShelveDuration,401625,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_PLC_002_1_JA.Alarm.BOOLS1,401646,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_PLC_002_1_JA.Alarm.BOOLS2,401647,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_PLC_002_1_JA.Alarm.AEBOOLS,401648,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_PLC_002_1_JA.Alarm.INT1,401649,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_JA.Alarm.INT2,401650,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_JA.Alarm.AENotify,401651,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_PLC_002_1_JA.Alarm.AESeverity,401652,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_PLC_002_1_JA.Alarm.AEShelveDuration,401653,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_PLC_002_1_JA.almPLCFault.BOOLS1,401658,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_PLC_002_1_JA.almPLCFault.BOOLS2,401659,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_PLC_002_1_JA.almPLCFault.AEBOOLS,401660,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_PLC_002_1_JA.almPLCFault.INT1,401661,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_JA.almPLCFault.INT2,401662,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_PLC_002_1_JA.almPLCFault.AENotify,401663,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_PLC_002_1_JA.almPLCFault.AESeverity,401664,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_PLC_002_1_JA.almPLCFault.AEShelveDuration,401665,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SPD_0130_1_XA1.Alarm.BOOLS1,401966,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SPD_0130_1_XA1.Alarm.BOOLS2,401967,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SPD_0130_1_XA1.Alarm.AEBOOLS,401968,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SPD_0130_1_XA1.Alarm.INT1,401969,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_1_XA1.Alarm.INT2,401970,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_1_XA1.Alarm.AENotify,401971,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SPD_0130_1_XA1.Alarm.AESeverity,401972,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SPD_0130_1_XA1.Alarm.AEShelveDuration,401973,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SPD_0130_1_XA1.almPLCFault.BOOLS1,401978,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SPD_0130_1_XA1.almPLCFault.BOOLS2,401979,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SPD_0130_1_XA1.almPLCFault.AEBOOLS,401980,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SPD_0130_1_XA1.almPLCFault.INT1,401981,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_1_XA1.almPLCFault.INT2,401982,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_1_XA1.almPLCFault.AENotify,401983,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SPD_0130_1_XA1.almPLCFault.AESeverity,401984,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SPD_0130_1_XA1.almPLCFault.AEShelveDuration,401985,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_BC_0130_1_XA1.Alarm.BOOLS1,401846,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_BC_0130_1_XA1.Alarm.BOOLS2,401847,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_BC_0130_1_XA1.Alarm.AEBOOLS,401848,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_BC_0130_1_XA1.Alarm.INT1,401849,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BC_0130_1_XA1.Alarm.INT2,401850,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BC_0130_1_XA1.Alarm.AENotify,401851,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_BC_0130_1_XA1.Alarm.AESeverity,401852,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_BC_0130_1_XA1.Alarm.AEShelveDuration,401853,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_BC_0130_1_XA1.almPLCFault.BOOLS1,401858,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_BC_0130_1_XA1.almPLCFault.BOOLS2,401859,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_BC_0130_1_XA1.almPLCFault.AEBOOLS,401860,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_BC_0130_1_XA1.almPLCFault.INT1,401861,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BC_0130_1_XA1.almPLCFault.INT2,401862,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BC_0130_1_XA1.almPLCFault.AENotify,401863,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_BC_0130_1_XA1.almPLCFault.AESeverity,401864,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_BC_0130_1_XA1.almPLCFault.AEShelveDuration,401865,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_BE_0130_2_XA2.Alarm.BOOLS1,401886,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_BE_0130_2_XA2.Alarm.BOOLS2,401887,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_BE_0130_2_XA2.Alarm.AEBOOLS,401888,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_BE_0130_2_XA2.Alarm.INT1,401889,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BE_0130_2_XA2.Alarm.INT2,401890,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BE_0130_2_XA2.Alarm.AENotify,401891,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_BE_0130_2_XA2.Alarm.AESeverity,401892,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_BE_0130_2_XA2.Alarm.AEShelveDuration,401893,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_BE_0130_2_XA2.almPLCFault.BOOLS1,401898,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_BE_0130_2_XA2.almPLCFault.BOOLS2,401899,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_BE_0130_2_XA2.almPLCFault.AEBOOLS,401900,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_BE_0130_2_XA2.almPLCFault.INT1,401901,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BE_0130_2_XA2.almPLCFault.INT2,401902,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_BE_0130_2_XA2.almPLCFault.AENotify,401903,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_BE_0130_2_XA2.almPLCFault.AESeverity,401904,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_BE_0130_2_XA2.almPLCFault.AEShelveDuration,401905,Short,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LL.Alarm.BOOLS1,402206,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LL.Alarm.BOOLS2,402207,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LL.Alarm.AEBOOLS,402208,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LL.Alarm.INT1,402209,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LL.Alarm.INT2,402210,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LL.Alarm.AENotify,402211,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LL.Alarm.AESeverity,402212,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LL.Alarm.AEShelveDuration,402213,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LL.almPLCFault.BOOLS1,402218,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_LL.almPLCFault.BOOLS2,402219,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_LL.almPLCFault.AEBOOLS,402220,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_LL.almPLCFault.INT1,402221,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LL.almPLCFault.INT2,402222,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_LL.almPLCFault.AENotify,402223,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_LL.almPLCFault.AESeverity,402224,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_LL.almPLCFault.AEShelveDuration,402225,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_PL.Alarm.BOOLS1,402246,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_PL.Alarm.BOOLS2,402247,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_PL.Alarm.AEBOOLS,402248,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_PL.Alarm.INT1,402249,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_PL.Alarm.INT2,402250,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_PL.Alarm.AENotify,402251,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_PL.Alarm.AESeverity,402252,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_PL.Alarm.AEShelveDuration,402253,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_PL.almPLCFault.BOOLS1,402258,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_PL.almPLCFault.BOOLS2,402259,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_PL.almPLCFault.AEBOOLS,402260,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_PL.almPLCFault.INT1,402261,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_PL.almPLCFault.INT2,402262,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_PL.almPLCFault.AENotify,402263,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_PL.almPLCFault.AESeverity,402264,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_PL.almPLCFault.AEShelveDuration,402265,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_SH.Alarm.BOOLS1,402286,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_SH.Alarm.BOOLS2,402287,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_SH.Alarm.AEBOOLS,402288,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_SH.Alarm.INT1,402289,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_SH.Alarm.INT2,402290,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_SH.Alarm.AENotify,402291,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_SH.Alarm.AESeverity,402292,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_SH.Alarm.AEShelveDuration,402293,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_SH.almPLCFault.BOOLS1,402298,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_SH.almPLCFault.BOOLS2,402299,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_SH.almPLCFault.AEBOOLS,402300,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_SH.almPLCFault.INT1,402301,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_SH.almPLCFault.INT2,402302,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_SH.almPLCFault.AENotify,402303,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_SH.almPLCFault.AESeverity,402304,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_SH.almPLCFault.AEShelveDuration,402305,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_TH.Alarm.BOOLS1,402326,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_TH.Alarm.BOOLS2,402327,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_TH.Alarm.AEBOOLS,402328,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_TH.Alarm.INT1,402329,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_TH.Alarm.INT2,402330,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_TH.Alarm.AENotify,402331,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_TH.Alarm.AESeverity,402332,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_TH.Alarm.AEShelveDuration,402333,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_TH.almPLCFault.BOOLS1,402338,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_TH.almPLCFault.BOOLS2,402339,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_TH.almPLCFault.AEBOOLS,402340,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_TH.almPLCFault.INT1,402341,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_TH.almPLCFault.INT2,402342,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_TH.almPLCFault.AENotify,402343,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_TH.almPLCFault.AESeverity,402344,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_TH.almPLCFault.AEShelveDuration,402345,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_XA1.Alarm.BOOLS1,402366,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_XA1.Alarm.BOOLS2,402367,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_XA1.Alarm.AEBOOLS,402368,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_XA1.Alarm.INT1,402369,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA1.Alarm.INT2,402370,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA1.Alarm.AENotify,402371,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_XA1.Alarm.AESeverity,402372,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_XA1.Alarm.AEShelveDuration,402373,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_XA1.almPLCFault.BOOLS1,402378,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_XA1.almPLCFault.BOOLS2,402379,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_XA1.almPLCFault.AEBOOLS,402380,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_XA1.almPLCFault.INT1,402381,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA1.almPLCFault.INT2,402382,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA1.almPLCFault.AENotify,402383,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_XA1.almPLCFault.AESeverity,402384,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_XA1.almPLCFault.AEShelveDuration,402385,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_XA2.Alarm.BOOLS1,402406,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_XA2.Alarm.BOOLS2,402407,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_XA2.Alarm.AEBOOLS,402408,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_XA2.Alarm.INT1,402409,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA2.Alarm.INT2,402410,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA2.Alarm.AENotify,402411,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_XA2.Alarm.AESeverity,402412,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_XA2.Alarm.AEShelveDuration,402413,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_XA2.almPLCFault.BOOLS1,402418,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_GEN_0130_1_XA2.almPLCFault.BOOLS2,402419,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_GEN_0130_1_XA2.almPLCFault.AEBOOLS,402420,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_GEN_0130_1_XA2.almPLCFault.INT1,402421,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA2.almPLCFault.INT2,402422,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_GEN_0130_1_XA2.almPLCFault.AENotify,402423,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_GEN_0130_1_XA2.almPLCFault.AESeverity,402424,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_GEN_0130_1_XA2.almPLCFault.AEShelveDuration,402425,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_BM.Alarm.BOOLS1,401806,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_BM.Alarm.BOOLS2,401807,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_BM.Alarm.AEBOOLS,401808,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_BM.Alarm.INT1,401809,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_BM.Alarm.INT2,401810,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_BM.Alarm.AENotify,401811,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_BM.Alarm.AESeverity,401812,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_BM.Alarm.AEShelveDuration,401813,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_NIP_002_1_BM.almPLCFault.BOOLS1,401818,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_NIP_002_1_BM.almPLCFault.BOOLS2,401819,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_NIP_002_1_BM.almPLCFault.AEBOOLS,401820,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_NIP_002_1_BM.almPLCFault.INT1,401821,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_BM.almPLCFault.INT2,401822,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_NIP_002_1_BM.almPLCFault.AENotify,401823,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_NIP_002_1_BM.almPLCFault.AESeverity,401824,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_NIP_002_1_BM.almPLCFault.AEShelveDuration,401825,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SD_0130_1_XA.Alarm.BOOLS1,401926,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SD_0130_1_XA.Alarm.BOOLS2,401927,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SD_0130_1_XA.Alarm.AEBOOLS,401928,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SD_0130_1_XA.Alarm.INT1,401929,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SD_0130_1_XA.Alarm.INT2,401930,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SD_0130_1_XA.Alarm.AENotify,401931,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SD_0130_1_XA.Alarm.AESeverity,401932,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SD_0130_1_XA.Alarm.AEShelveDuration,401933,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SD_0130_1_XA.almPLCFault.BOOLS1,401938,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SD_0130_1_XA.almPLCFault.BOOLS2,401939,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SD_0130_1_XA.almPLCFault.AEBOOLS,401940,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SD_0130_1_XA.almPLCFault.INT1,401941,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SD_0130_1_XA.almPLCFault.INT2,401942,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SD_0130_1_XA.almPLCFault.AENotify,401943,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SD_0130_1_XA.almPLCFault.AESeverity,401944,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SD_0130_1_XA.almPLCFault.AEShelveDuration,401945,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SPD_0130_2_XA2.Alarm.BOOLS1,402006,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SPD_0130_2_XA2.Alarm.BOOLS2,402007,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SPD_0130_2_XA2.Alarm.AEBOOLS,402008,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SPD_0130_2_XA2.Alarm.INT1,402009,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_2_XA2.Alarm.INT2,402010,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_2_XA2.Alarm.AENotify,402011,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SPD_0130_2_XA2.Alarm.AESeverity,402012,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SPD_0130_2_XA2.Alarm.AEShelveDuration,402013,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SPD_0130_2_XA2.almPLCFault.BOOLS1,402018,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SPD_0130_2_XA2.almPLCFault.BOOLS2,402019,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SPD_0130_2_XA2.almPLCFault.AEBOOLS,402020,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SPD_0130_2_XA2.almPLCFault.INT1,402021,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_2_XA2.almPLCFault.INT2,402022,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SPD_0130_2_XA2.almPLCFault.AENotify,402023,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SPD_0130_2_XA2.almPLCFault.AESeverity,402024,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SPD_0130_2_XA2.almPLCFault.AEShelveDuration,402025,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SWG_0130_1_XN1.Alarm.BOOLS1,402046,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SWG_0130_1_XN1.Alarm.BOOLS2,402047,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SWG_0130_1_XN1.Alarm.AEBOOLS,402048,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SWG_0130_1_XN1.Alarm.INT1,402049,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN1.Alarm.INT2,402050,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN1.Alarm.AENotify,402051,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SWG_0130_1_XN1.Alarm.AESeverity,402052,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SWG_0130_1_XN1.Alarm.AEShelveDuration,402053,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SWG_0130_1_XN1.almPLCFault.BOOLS1,402058,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SWG_0130_1_XN1.almPLCFault.BOOLS2,402059,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SWG_0130_1_XN1.almPLCFault.AEBOOLS,402060,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SWG_0130_1_XN1.almPLCFault.INT1,402061,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN1.almPLCFault.INT2,402062,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN1.almPLCFault.AENotify,402063,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SWG_0130_1_XN1.almPLCFault.AESeverity,402064,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SWG_0130_1_XN1.almPLCFault.AEShelveDuration,402065,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SWG_0130_1_XN2.Alarm.BOOLS1,402086,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SWG_0130_1_XN2.Alarm.BOOLS2,402087,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SWG_0130_1_XN2.Alarm.AEBOOLS,402088,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SWG_0130_1_XN2.Alarm.INT1,402089,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN2.Alarm.INT2,402090,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN2.Alarm.AENotify,402091,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SWG_0130_1_XN2.Alarm.AESeverity,402092,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SWG_0130_1_XN2.Alarm.AEShelveDuration,402093,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_SWG_0130_1_XN2.almPLCFault.BOOLS1,402098,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits"
WA3252_SWG_0130_1_XN2.almPLCFault.BOOLS2,402099,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits"
WA3252_SWG_0130_1_XN2.almPLCFault.AEBOOLS,402100,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools"
WA3252_SWG_0130_1_XN2.almPLCFault.INT1,402101,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN2.almPLCFault.INT2,402102,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int"
WA3252_SWG_0130_1_XN2.almPLCFault.AENotify,402103,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server"
WA3252_SWG_0130_1_XN2.almPLCFault.AESeverity,402104,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)"
WA3252_SWG_0130_1_XN2.almPLCFault.AEShelveDuration,402105,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint"
WA3252_GEN_0130_1_LI.Totalize.BOOLS1,401148,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits."
WA3252_GEN_0130_1_LI.Totalize.BOOLS2,401149,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_1_LI.Totalize.BOOLS3,401150,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_1_LI.Totalize.BOOLS4,401151,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_1_LI.Totalize.INT1,401152,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_GEN_0130_1_LI.Totalize.INT2,401153,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_GEN_0130_1_LI.Totalize.Day500,401168,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days"
WA3252_GEN_0130_2_LI.Totalize.BOOLS1,401348,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits."
WA3252_GEN_0130_2_LI.Totalize.BOOLS2,401349,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_2_LI.Totalize.BOOLS3,401350,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_2_LI.Totalize.BOOLS4,401351,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)"
WA3252_GEN_0130_2_LI.Totalize.INT1,401352,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_GEN_0130_2_LI.Totalize.INT2,401353,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_GEN_0130_2_LI.Totalize.Day500,401368,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days"
WA3252_TT_0130_1_TI.Totalize.BOOLS1,401548,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits."
WA3252_TT_0130_1_TI.Totalize.BOOLS2,401549,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)"
WA3252_TT_0130_1_TI.Totalize.BOOLS3,401550,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)"
WA3252_TT_0130_1_TI.Totalize.BOOLS4,401551,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)"
WA3252_TT_0130_1_TI.Totalize.INT1,401552,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_TT_0130_1_TI.Totalize.INT2,401553,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer"
WA3252_TT_0130_1_TI.Totalize.Day500,401568,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days"
WA3252_GEN_0130_1_LI.almHighHigh.ALDL,401048,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almHighHigh.ATRM,401050,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almHigh.ALDL,401060,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almHigh.ATRM,401062,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almLow.ALDL,401072,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almLow.ATRM,401074,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almLowLow.ALDL,401084,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almLowLow.ATRM,401086,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almBrokenLoop.ALDL,401096,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almBrokenLoop.ATRM,401098,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almOverRange.ALDL,401108,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almOverRange.ATRM,401110,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almUnderRange.ALDL,401120,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almUnderRange.ATRM,401122,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almRateOfChange.ALDL,401132,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almRateOfChange.ATRM,401134,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.almPLCFault.ALDL,401144,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LI.almPLCFault.ATRM,401146,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almHighHigh.ALDL,401248,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almHighHigh.ATRM,401250,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almHigh.ALDL,401260,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almHigh.ATRM,401262,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almLow.ALDL,401272,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almLow.ATRM,401274,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almLowLow.ALDL,401284,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almLowLow.ATRM,401286,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almBrokenLoop.ALDL,401296,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almBrokenLoop.ATRM,401298,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almOverRange.ALDL,401308,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almOverRange.ATRM,401310,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almUnderRange.ALDL,401320,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almUnderRange.ATRM,401322,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almRateOfChange.ALDL,401332,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almRateOfChange.ATRM,401334,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LI.almPLCFault.ALDL,401344,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LI.almPLCFault.ATRM,401346,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almHighHigh.ALDL,401448,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almHighHigh.ATRM,401450,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almHigh.ALDL,401460,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almHigh.ATRM,401462,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almLow.ALDL,401472,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almLow.ATRM,401474,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almLowLow.ALDL,401484,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almLowLow.ATRM,401486,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almBrokenLoop.ALDL,401496,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almBrokenLoop.ATRM,401498,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almOverRange.ALDL,401508,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almOverRange.ATRM,401510,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almUnderRange.ALDL,401520,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almUnderRange.ATRM,401522,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almRateOfChange.ALDL,401532,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almRateOfChange.ATRM,401534,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_TT_0130_1_TI.almPLCFault.ALDL,401544,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_TT_0130_1_TI.almPLCFault.ATRM,401546,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_XA1.Alarm.ALDL,402614,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_XA1.Alarm.ATRM,402616,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_XA1.almPLCFault.ALDL,402626,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_XA1.almPLCFault.ATRM,402628,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LL.Alarm.ALDL,402454,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LL.Alarm.ATRM,402456,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_LL.almPLCFault.ALDL,402466,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_LL.almPLCFault.ATRM,402468,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_PL.Alarm.ALDL,402494,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_PL.Alarm.ATRM,402496,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_PL.almPLCFault.ALDL,402506,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_PL.almPLCFault.ATRM,402508,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_SH.Alarm.ALDL,402534,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_SH.Alarm.ATRM,402536,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_SH.almPLCFault.ALDL,402546,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_SH.almPLCFault.ATRM,402548,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_TH.Alarm.ALDL,402574,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_TH.Alarm.ATRM,402576,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_TH.almPLCFault.ALDL,402586,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_TH.almPLCFault.ATRM,402588,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 High Water Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_XA2.Alarm.ALDL,402654,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_XA2.Alarm.ATRM,402656,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_2_XA2.almPLCFault.ALDL,402666,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_2_XA2.almPLCFault.ATRM,402668,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Battery System Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_ZS_0130_3_ZA.Alarm.ALDL,402134,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_ZS_0130_3_ZA.Alarm.ATRM,402136,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_ZS_0130_3_ZA.almPLCFault.ALDL,402146,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_ZS_0130_3_ZA.almPLCFault.ATRM,402148,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_ZA.Alarm.ALDL,401694,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_ZA.Alarm.ATRM,401696,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_ZA.almPLCFault.ALDL,401706,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_ZA.almPLCFault.ATRM,401708,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_JA.Alarm.ALDL,401734,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_JA.Alarm.ATRM,401736,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_JA.almPLCFault.ALDL,401746,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_JA.almPLCFault.ATRM,401748,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - 24V DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_XN.Alarm.ALDL,401774,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_XN.Alarm.ATRM,401776,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_XN.almPLCFault.ALDL,401786,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_XN.almPLCFault.ATRM,401788,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_PLC_002_1_ZA.Alarm.ALDL,401614,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_PLC_002_1_ZA.Alarm.ATRM,401616,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_PLC_002_1_ZA.almPLCFault.ALDL,401626,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_PLC_002_1_ZA.almPLCFault.ATRM,401628,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet - Intrusion Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_PLC_002_1_JA.Alarm.ALDL,401654,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_PLC_002_1_JA.Alarm.ATRM,401656,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_PLC_002_1_JA.almPLCFault.ALDL,401666,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_PLC_002_1_JA.almPLCFault.ATRM,401668,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PLC Cabinet DC Power OK: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SPD_0130_1_XA1.Alarm.ALDL,401974,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SPD_0130_1_XA1.Alarm.ATRM,401976,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SPD_0130_1_XA1.almPLCFault.ALDL,401986,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SPD_0130_1_XA1.almPLCFault.ATRM,401988,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building PP-0130-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_BC_0130_1_XA1.Alarm.ALDL,401854,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_BC_0130_1_XA1.Alarm.ATRM,401856,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_BC_0130_1_XA1.almPLCFault.ALDL,401866,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_BC_0130_1_XA1.almPLCFault.ATRM,401868,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Charger Common Trouble Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_BE_0130_2_XA2.Alarm.ALDL,401894,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_BE_0130_2_XA2.Alarm.ATRM,401896,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_BE_0130_2_XA2.almPLCFault.ALDL,401906,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_BE_0130_2_XA2.almPLCFault.ATRM,401908,Float,1,R/W,1000,,,,,,,,,,"RWPS SWG-0130-1 Battery Enclosure Hydrogen Gas Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LL.Alarm.ALDL,402214,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LL.Alarm.ATRM,402216,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LL.almPLCFault.ALDL,402226,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_LL.almPLCFault.ATRM,402228,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Fuel Channel Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_PL.Alarm.ALDL,402254,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_PL.Alarm.ATRM,402256,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_PL.almPLCFault.ALDL,402266,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_PL.almPLCFault.ATRM,402268,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Low Oil Pressure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_SH.Alarm.ALDL,402294,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_SH.Alarm.ATRM,402296,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_SH.almPLCFault.ALDL,402306,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_SH.almPLCFault.ATRM,402308,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Over Speed: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_TH.Alarm.ALDL,402334,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_TH.Alarm.ATRM,402336,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_TH.almPLCFault.ALDL,402346,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_TH.almPLCFault.ATRM,402348,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 High Water Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_XA1.Alarm.ALDL,402374,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_XA1.Alarm.ATRM,402376,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_XA1.almPLCFault.ALDL,402386,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_XA1.almPLCFault.ATRM,402388,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_XA2.Alarm.ALDL,402414,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_XA2.Alarm.ATRM,402416,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_XA2.almPLCFault.ALDL,402426,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_GEN_0130_1_XA2.almPLCFault.ATRM,402428,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Battery System Malfunction: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_BM.Alarm.ALDL,401814,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_BM.Alarm.ATRM,401816,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_NIP_002_1_BM.almPLCFault.ALDL,401826,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_NIP_002_1_BM.almPLCFault.ATRM,401828,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building NIP Cabinet - UPS Bypass: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SD_0130_1_XA.Alarm.ALDL,401934,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SD_0130_1_XA.Alarm.ATRM,401936,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SD_0130_1_XA.almPLCFault.ALDL,401946,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SD_0130_1_XA.almPLCFault.ATRM,401948,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Smoke Detected: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SPD_0130_2_XA2.Alarm.ALDL,402014,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SPD_0130_2_XA2.Alarm.ATRM,402016,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SPD_0130_2_XA2.almPLCFault.ALDL,402026,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SPD_0130_2_XA2.almPLCFault.ATRM,402028,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building LP-0130-1 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SWG_0130_1_XN1.Alarm.ALDL,402054,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SWG_0130_1_XN1.Alarm.ATRM,402056,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SWG_0130_1_XN1.almPLCFault.ALDL,402066,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SWG_0130_1_XN1.almPLCFault.ATRM,402068,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SWG_0130_1_XN2.Alarm.ALDL,402094,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SWG_0130_1_XN2.Alarm.ATRM,402096,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_SWG_0130_1_XN2.almPLCFault.ALDL,402106,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state."
WA3252_SWG_0130_1_XN2.almPLCFault.ATRM,402108,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped"
WA3252_GEN_0130_1_LI.Totalize.VALU,401156,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value"
WA3252_GEN_0130_1_LI.Totalize.VMAX,401158,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value"
WA3252_GEN_0130_1_LI.Totalize.LFCO,401160,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling"
WA3252_GEN_0130_1_LI.Totalize.FTTD,401162,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow"
WA3252_GEN_0130_1_LI.Totalize.FTYD,401164,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow"
WA3252_GEN_0130_1_LI.Totalize.FLOT,401166,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset"
WA3252_GEN_0130_1_LI.Totalize.DayTotal500,401170,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days"
WA3252_GEN_0130_1_LI.Totalize.FTTotal500,401172,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_GEN_0130_1_LI.Totalize.LowFlowCutoff,401174,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units"
WA3252_GEN_0130_1_LI.Totalize.TimeDivider,401182,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled"
WA3252_GEN_0130_1_LI.Totalize.Total2Minute,401184,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute"
WA3252_GEN_0130_1_LI.Totalize.Total5thSec,401186,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second"
WA3252_GEN_0130_1_LI.Totalize.TotalToday,401188,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today"
WA3252_GEN_0130_1_LI.Totalize.TotalTotal,401190,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value"
WA3252_GEN_0130_2_LI.Totalize.VALU,401356,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value"
WA3252_GEN_0130_2_LI.Totalize.VMAX,401358,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value"
WA3252_GEN_0130_2_LI.Totalize.LFCO,401360,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling"
WA3252_GEN_0130_2_LI.Totalize.FTTD,401362,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow"
WA3252_GEN_0130_2_LI.Totalize.FTYD,401364,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow"
WA3252_GEN_0130_2_LI.Totalize.FLOT,401366,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset"
WA3252_GEN_0130_2_LI.Totalize.DayTotal500,401370,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days"
WA3252_GEN_0130_2_LI.Totalize.FTTotal500,401372,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_GEN_0130_2_LI.Totalize.LowFlowCutoff,401374,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units"
WA3252_GEN_0130_2_LI.Totalize.TimeDivider,401382,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled"
WA3252_GEN_0130_2_LI.Totalize.Total2Minute,401384,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute"
WA3252_GEN_0130_2_LI.Totalize.Total5thSec,401386,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second"
WA3252_GEN_0130_2_LI.Totalize.TotalToday,401388,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today"
WA3252_GEN_0130_2_LI.Totalize.TotalTotal,401390,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value"
WA3252_TT_0130_1_TI.Totalize.VALU,401556,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value"
WA3252_TT_0130_1_TI.Totalize.VMAX,401558,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value"
WA3252_TT_0130_1_TI.Totalize.LFCO,401560,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling"
WA3252_TT_0130_1_TI.Totalize.FTTD,401562,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow"
WA3252_TT_0130_1_TI.Totalize.FTYD,401564,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow"
WA3252_TT_0130_1_TI.Totalize.FLOT,401566,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset"
WA3252_TT_0130_1_TI.Totalize.DayTotal500,401570,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days"
WA3252_TT_0130_1_TI.Totalize.FTTotal500,401572,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: "
WA3252_TT_0130_1_TI.Totalize.LowFlowCutoff,401574,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units"
WA3252_TT_0130_1_TI.Totalize.TimeDivider,401582,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled"
WA3252_TT_0130_1_TI.Totalize.Total2Minute,401584,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute"
WA3252_TT_0130_1_TI.Totalize.Total5thSec,401586,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second"
WA3252_TT_0130_1_TI.Totalize.TotalToday,401588,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today"
WA3252_TT_0130_1_TI.Totalize.TotalTotal,401590,Float,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value"
BMENOC0301_4.DEVICE_CNX_HEALTH.[0],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.DEVICE_CNX_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO)
BMENOC0301_4.RESERVED2.[0],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[1],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[2],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[3],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[4],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[5],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[6],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMENOC0301_4.RESERVED2.[7],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[0],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO)
BMEP58_ECPU_EXT.DID_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[8],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[9],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[10],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[11],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[12],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[13],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[14],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[15],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.DID_HEALTH.[16],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name)
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[8],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[9],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[10],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[11],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[12],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[13],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[14],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[15],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[16],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[17],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[18],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[19],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[20],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[21],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[22],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[23],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[24],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_2_17,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 2 to 17
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_18_33,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 18 to 33
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_34_49,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 34 to 49
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_50_65,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 50 to 65
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_66_81,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 66 to 81
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_82_97,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 82 to 97
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_98_113,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 98 to 113
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_114_129,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 114 to 129
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_130_145,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 130 to 145
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_146_161,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 146 to 161
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_162_177,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 162 to 511
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_178_193,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 178 to 193
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_194_209,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 194 to 209
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_210_225,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 210 to 225
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_226_241,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 226 to 241
BMENOC0301_4.DID_HEALTH.DEVICE_CNX_HEALTH_242_257,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 242 to 257
AI_R0_S7.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
AI_R0_S7.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
AI_R0_S7.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning
AI_R0_S7.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel
AI_R0_S7.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone
AI_R0_S7.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone
AI_R0_S7.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error
AI_R0_S7.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error
AI_R0_S7.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error
AI_R0_S7.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error
DI_R0_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S6.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health
DI_R0_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
DI_R0_S6.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[0],401176,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[1],401177,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[2],401178,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[3],401179,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[4],401180,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_1_LI.Totalize.RESTTime.[5],401181,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 1 Fuel Tank Level: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[0],401376,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[1],401377,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[2],401378,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[3],401379,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[4],401380,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_GEN_0130_2_LI.Totalize.RESTTime.[5],401381,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator 2 Fuel Tank Level : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[0],401576,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[1],401577,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[2],401578,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[3],401579,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[4],401580,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
WA3252_TT_0130_1_TI.Totalize.RESTTime.[5],401581,Short,1,R/W,1000,,,,,,,,,,"RWPS Generator Switchgear Building Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset"
AI_R0_S7.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word
AI_R0_S7.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type
AI_R0_S7.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value
AI_R0_S7.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value
AI_R0_S7.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value
AI_R0_S7.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command
AI_R0_S7.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state
AI_R0_S7.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value