1Tag NameAddressData TypeRespect Data TypeClient AccessScan RateScalingRaw LowRaw HighScaled LowScaled HighScaled Data TypeClamp LowClamp HighEng UnitsDescriptionNegate Value
2WA3252_AFD_0103_1.ACKN442040.06Boolean1R/W1000RWPS Pump 1: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB
3WA3252_AFD_0103_1.AKED442041.10Boolean1R/W1000RWPS Pump 1: Acknowledged: At least one alarm has been acknowledged.
4WA3252_AFD_0103_1.almFailToStop.Ack442104.06Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Acknowlege Command to AE Server
5WA3252_AFD_0103_1.almFailToStop.Acked442104.11Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm Acknowledged Status from AE Server
6WA3252_AFD_0103_1.almFailToStop.ACKN442102.09Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Acknowledge Command
7WA3252_AFD_0103_1.almFailToStop.AEShelveTMRDN442103.01Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm and Events Shelve Timer Done
8WA3252_AFD_0103_1.almFailToStop.AKED442102.06Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
9WA3252_AFD_0103_1.almFailToStop.Alarm442104.12Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm Command to AE Server
10WA3252_AFD_0103_1.almFailToStop.AlarmState442102.01Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Value of the Fault input that indicates an alarm condition
11WA3252_AFD_0103_1.almFailToStop.ALRM442102.04Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
12WA3252_AFD_0103_1.almFailToStop.ANUN442102.05Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
13WA3252_AFD_0103_1.almFailToStop.Bad442103.02Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Discrete Input condition indicating a Bad Signal condition
14WA3252_AFD_0103_1.almFailToStop.Disable442104.05Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Disable Alarm Command to AE Server
15WA3252_AFD_0103_1.almFailToStop.Disabled442104.10Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm Disabled Status from AE Server
16WA3252_AFD_0103_1.almFailToStop.Enable442104.04Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Enable Alarm Command to AE Server
17WA3252_AFD_0103_1.almFailToStop.Fault442102.00Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Discrete input condition indicating a faulted state.
18WA3252_AFD_0103_1.almFailToStop.FaultInAlarm442102.03Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Fault Is In Alarm (on longer than the delay)
19WA3252_AFD_0103_1.almFailToStop.GlobalReset442102.02Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Used to reset all alarms in the PLC
20WA3252_AFD_0103_1.almFailToStop.MCmd_Disable442102.12Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Maintenance Command to Disable Alarm
21WA3252_AFD_0103_1.almFailToStop.MCmd_Enable442102.11Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Maintenance Command to Enable Alarm
22WA3252_AFD_0103_1.almFailToStop.OCmd_Shelve442102.13Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Operator Command to Shelve Alarm
23WA3252_AFD_0103_1.almFailToStop.OCmd_Unshelve442102.14Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Operator Command to UnShelve Alarm
24WA3252_AFD_0103_1.almFailToStop.Reset442104.07Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Reset Command to AE Server
25WA3252_AFD_0103_1.almFailToStop.Resetable442102.07Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
26WA3252_AFD_0103_1.almFailToStop.REST442102.08Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Reset this alarm only
27WA3252_AFD_0103_1.almFailToStop.SCmd_Suppress442102.15Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Supervisor Command to Suppress Alarm
28WA3252_AFD_0103_1.almFailToStop.SCmd_UnSuppress442103.00Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Supervisor Command to Unsuppress Alarm
29WA3252_AFD_0103_1.almFailToStop.Shelve442104.02Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Shelve Alarm Command to AE Server
30WA3252_AFD_0103_1.almFailToStop.Shelved442104.09Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm Shelved Status from AE Server
31WA3252_AFD_0103_1.almFailToStop.Suppress442104.00Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Suppress Alarm Command to AE Server
32WA3252_AFD_0103_1.almFailToStop.Suppressed442104.08Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Alarm Suppressed Status from AE Server
33WA3252_AFD_0103_1.almFailToStop.UACK442102.10Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Remove the Acknowledge Status
34WA3252_AFD_0103_1.almFailToStop.UnShelve442104.03Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: Unshelve Alarm Command to AE Server
35WA3252_AFD_0103_1.almFailToStop.UnSuppress442104.01Boolean1R/W1000RWPS Pump 1: Fail to Sop Alarm DDT: UnSuppress Alarm Command to AE Server
36WA3252_AFD_0103_1.almFailToStrt.Ack442092.06Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Acknowlege Command to AE Server
37WA3252_AFD_0103_1.almFailToStrt.Acked442092.11Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm Acknowledged Status from AE Server
38WA3252_AFD_0103_1.almFailToStrt.ACKN442090.09Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Acknowledge Command
39WA3252_AFD_0103_1.almFailToStrt.AEShelveTMRDN442091.01Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm and Events Shelve Timer Done
40WA3252_AFD_0103_1.almFailToStrt.AKED442090.06Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
41WA3252_AFD_0103_1.almFailToStrt.Alarm442092.12Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm Command to AE Server
42WA3252_AFD_0103_1.almFailToStrt.AlarmState442090.01Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Value of the Fault input that indicates an alarm condition
43WA3252_AFD_0103_1.almFailToStrt.ALRM442090.04Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
44WA3252_AFD_0103_1.almFailToStrt.ANUN442090.05Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
45WA3252_AFD_0103_1.almFailToStrt.Bad442091.02Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Discrete Input condition indicating a Bad Signal condition
46WA3252_AFD_0103_1.almFailToStrt.Disable442092.05Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Disable Alarm Command to AE Server
47WA3252_AFD_0103_1.almFailToStrt.Disabled442092.10Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm Disabled Status from AE Server
48WA3252_AFD_0103_1.almFailToStrt.Enable442092.04Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Enable Alarm Command to AE Server
49WA3252_AFD_0103_1.almFailToStrt.Fault442090.00Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Discrete input condition indicating a faulted state.
50WA3252_AFD_0103_1.almFailToStrt.FaultInAlarm442090.03Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Fault Is In Alarm (on longer than the delay)
51WA3252_AFD_0103_1.almFailToStrt.GlobalReset442090.02Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Used to reset all alarms in the PLC
52WA3252_AFD_0103_1.almFailToStrt.MCmd_Disable442090.12Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Maintenance Command to Disable Alarm
53WA3252_AFD_0103_1.almFailToStrt.MCmd_Enable442090.11Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Maintenance Command to Enable Alarm
54WA3252_AFD_0103_1.almFailToStrt.OCmd_Shelve442090.13Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Operator Command to Shelve Alarm
55WA3252_AFD_0103_1.almFailToStrt.OCmd_Unshelve442090.14Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Operator Command to UnShelve Alarm
56WA3252_AFD_0103_1.almFailToStrt.Reset442092.07Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Reset Command to AE Server
57WA3252_AFD_0103_1.almFailToStrt.Resetable442090.07Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
58WA3252_AFD_0103_1.almFailToStrt.REST442090.08Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Reset this alarm only
59WA3252_AFD_0103_1.almFailToStrt.SCmd_Suppress442090.15Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Supervisor Command to Suppress Alarm
60WA3252_AFD_0103_1.almFailToStrt.SCmd_UnSuppress442091.00Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Supervisor Command to Unsuppress Alarm
61WA3252_AFD_0103_1.almFailToStrt.Shelve442092.02Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Shelve Alarm Command to AE Server
62WA3252_AFD_0103_1.almFailToStrt.Shelved442092.09Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm Shelved Status from AE Server
63WA3252_AFD_0103_1.almFailToStrt.Suppress442092.00Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Suppress Alarm Command to AE Server
64WA3252_AFD_0103_1.almFailToStrt.Suppressed442092.08Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Alarm Suppressed Status from AE Server
65WA3252_AFD_0103_1.almFailToStrt.UACK442090.10Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Remove the Acknowledge Status
66WA3252_AFD_0103_1.almFailToStrt.UnShelve442092.03Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: Unshelve Alarm Command to AE Server
67WA3252_AFD_0103_1.almFailToStrt.UnSuppress442092.01Boolean1R/W1000RWPS Pump 1: Fail to Start Alarm DDT: UnSuppress Alarm Command to AE Server
68WA3252_AFD_0103_1.almMotorFailure.Ack442116.06Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Acknowlege Command to AE Server
69WA3252_AFD_0103_1.almMotorFailure.Acked442116.11Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm Acknowledged Status from AE Server
70WA3252_AFD_0103_1.almMotorFailure.ACKN442114.09Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Acknowledge Command
71WA3252_AFD_0103_1.almMotorFailure.AEShelveTMRDN442115.01Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm and Events Shelve Timer Done
72WA3252_AFD_0103_1.almMotorFailure.AKED442114.06Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
73WA3252_AFD_0103_1.almMotorFailure.Alarm442116.12Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm Command to AE Server
74WA3252_AFD_0103_1.almMotorFailure.AlarmState442114.01Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Value of the Fault input that indicates an alarm condition
75WA3252_AFD_0103_1.almMotorFailure.ALRM442114.04Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
76WA3252_AFD_0103_1.almMotorFailure.ANUN442114.05Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
77WA3252_AFD_0103_1.almMotorFailure.Bad442115.02Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Discrete Input condition indicating a Bad Signal condition
78WA3252_AFD_0103_1.almMotorFailure.Disable442116.05Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Disable Alarm Command to AE Server
79WA3252_AFD_0103_1.almMotorFailure.Disabled442116.10Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm Disabled Status from AE Server
80WA3252_AFD_0103_1.almMotorFailure.Enable442116.04Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Enable Alarm Command to AE Server
81WA3252_AFD_0103_1.almMotorFailure.Fault442114.00Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Discrete input condition indicating a faulted state.
82WA3252_AFD_0103_1.almMotorFailure.FaultInAlarm442114.03Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Fault Is In Alarm (on longer than the delay)
83WA3252_AFD_0103_1.almMotorFailure.GlobalReset442114.02Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Used to reset all alarms in the PLC
84WA3252_AFD_0103_1.almMotorFailure.MCmd_Disable442114.12Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Maintenance Command to Disable Alarm
85WA3252_AFD_0103_1.almMotorFailure.MCmd_Enable442114.11Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Maintenance Command to Enable Alarm
86WA3252_AFD_0103_1.almMotorFailure.OCmd_Shelve442114.13Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Operator Command to Shelve Alarm
87WA3252_AFD_0103_1.almMotorFailure.OCmd_Unshelve442114.14Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Operator Command to UnShelve Alarm
88WA3252_AFD_0103_1.almMotorFailure.Reset442116.07Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Reset Command to AE Server
89WA3252_AFD_0103_1.almMotorFailure.Resetable442114.07Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
90WA3252_AFD_0103_1.almMotorFailure.REST442114.08Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Reset this alarm only
91WA3252_AFD_0103_1.almMotorFailure.SCmd_Suppress442114.15Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Supervisor Command to Suppress Alarm
92WA3252_AFD_0103_1.almMotorFailure.SCmd_UnSuppress442115.00Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Supervisor Command to Unsuppress Alarm
93WA3252_AFD_0103_1.almMotorFailure.Shelve442116.02Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Shelve Alarm Command to AE Server
94WA3252_AFD_0103_1.almMotorFailure.Shelved442116.09Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm Shelved Status from AE Server
95WA3252_AFD_0103_1.almMotorFailure.Suppress442116.00Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Suppress Alarm Command to AE Server
96WA3252_AFD_0103_1.almMotorFailure.Suppressed442116.08Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Alarm Suppressed Status from AE Server
97WA3252_AFD_0103_1.almMotorFailure.UACK442114.10Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Remove the Acknowledge Status
98WA3252_AFD_0103_1.almMotorFailure.UnShelve442116.03Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: Unshelve Alarm Command to AE Server
99WA3252_AFD_0103_1.almMotorFailure.UnSuppress442116.01Boolean1R/W1000RWPS Pump 1: Motor Failure Alarm DDT: UnSuppress Alarm Command to AE Server
100WA3252_AFD_0103_1.almPLCFault.Ack442128.06Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Acknowlege Command to AE Server
101WA3252_AFD_0103_1.almPLCFault.Acked442128.11Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
102WA3252_AFD_0103_1.almPLCFault.ACKN442126.09Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Acknowledge Command
103WA3252_AFD_0103_1.almPLCFault.AEShelveTMRDN442127.01Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
104WA3252_AFD_0103_1.almPLCFault.AKED442126.06Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
105WA3252_AFD_0103_1.almPLCFault.Alarm442128.12Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm Command to AE Server
106WA3252_AFD_0103_1.almPLCFault.AlarmState442126.01Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
107WA3252_AFD_0103_1.almPLCFault.ALRM442126.04Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
108WA3252_AFD_0103_1.almPLCFault.ANUN442126.05Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
109WA3252_AFD_0103_1.almPLCFault.Bad442127.02Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
110WA3252_AFD_0103_1.almPLCFault.Disable442128.05Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Disable Alarm Command to AE Server
111WA3252_AFD_0103_1.almPLCFault.Disabled442128.10Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
112WA3252_AFD_0103_1.almPLCFault.Enable442128.04Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Enable Alarm Command to AE Server
113WA3252_AFD_0103_1.almPLCFault.Fault442126.00Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
114WA3252_AFD_0103_1.almPLCFault.FaultInAlarm442126.03Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
115WA3252_AFD_0103_1.almPLCFault.GlobalReset442126.02Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Used to reset all alarms in the PLC
116WA3252_AFD_0103_1.almPLCFault.MCmd_Disable442126.12Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
117WA3252_AFD_0103_1.almPLCFault.MCmd_Enable442126.11Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
118WA3252_AFD_0103_1.almPLCFault.OCmd_Shelve442126.13Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Operator Command to Shelve Alarm
119WA3252_AFD_0103_1.almPLCFault.OCmd_Unshelve442126.14Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
120WA3252_AFD_0103_1.almPLCFault.Reset442128.07Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Reset Command to AE Server
121WA3252_AFD_0103_1.almPLCFault.Resetable442126.07Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
122WA3252_AFD_0103_1.almPLCFault.REST442126.08Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Reset this alarm only
123WA3252_AFD_0103_1.almPLCFault.SCmd_Suppress442126.15Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
124WA3252_AFD_0103_1.almPLCFault.SCmd_UnSuppress442127.00Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
125WA3252_AFD_0103_1.almPLCFault.Shelve442128.02Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
126WA3252_AFD_0103_1.almPLCFault.Shelved442128.09Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
127WA3252_AFD_0103_1.almPLCFault.Suppress442128.00Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
128WA3252_AFD_0103_1.almPLCFault.Suppressed442128.08Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
129WA3252_AFD_0103_1.almPLCFault.UACK442126.10Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Remove the Acknowledge Status
130WA3252_AFD_0103_1.almPLCFault.UnShelve442128.03Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
131WA3252_AFD_0103_1.almPLCFault.UnSuppress442128.01Boolean1R/W1000RWPS Pump 1: PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
132WA3252_AFD_0103_1.almSpeedDeviation.Ack442140.06Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Acknowlege Command to AE Server
133WA3252_AFD_0103_1.almSpeedDeviation.Acked442140.11Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm Acknowledged Status from AE Server
134WA3252_AFD_0103_1.almSpeedDeviation.ACKN442138.09Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Acknowledge Command
135WA3252_AFD_0103_1.almSpeedDeviation.AEShelveTMRDN442139.01Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm and Events Shelve Timer Done
136WA3252_AFD_0103_1.almSpeedDeviation.AKED442138.06Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
137WA3252_AFD_0103_1.almSpeedDeviation.Alarm442140.12Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm Command to AE Server
138WA3252_AFD_0103_1.almSpeedDeviation.AlarmState442138.01Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Value of the Fault input that indicates an alarm condition
139WA3252_AFD_0103_1.almSpeedDeviation.ALRM442138.04Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
140WA3252_AFD_0103_1.almSpeedDeviation.ANUN442138.05Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
141WA3252_AFD_0103_1.almSpeedDeviation.Bad442139.02Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Discrete Input condition indicating a Bad Signal condition
142WA3252_AFD_0103_1.almSpeedDeviation.Disable442140.05Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Disable Alarm Command to AE Server
143WA3252_AFD_0103_1.almSpeedDeviation.Disabled442140.10Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm Disabled Status from AE Server
144WA3252_AFD_0103_1.almSpeedDeviation.Enable442140.04Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Enable Alarm Command to AE Server
145WA3252_AFD_0103_1.almSpeedDeviation.Fault442138.00Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Discrete input condition indicating a faulted state.
146WA3252_AFD_0103_1.almSpeedDeviation.FaultInAlarm442138.03Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Fault Is In Alarm (on longer than the delay)
147WA3252_AFD_0103_1.almSpeedDeviation.GlobalReset442138.02Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Used to reset all alarms in the PLC
148WA3252_AFD_0103_1.almSpeedDeviation.MCmd_Disable442138.12Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Maintenance Command to Disable Alarm
149WA3252_AFD_0103_1.almSpeedDeviation.MCmd_Enable442138.11Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Maintenance Command to Enable Alarm
150WA3252_AFD_0103_1.almSpeedDeviation.OCmd_Shelve442138.13Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Operator Command to Shelve Alarm
151WA3252_AFD_0103_1.almSpeedDeviation.OCmd_Unshelve442138.14Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Operator Command to UnShelve Alarm
152WA3252_AFD_0103_1.almSpeedDeviation.Reset442140.07Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Reset Command to AE Server
153WA3252_AFD_0103_1.almSpeedDeviation.Resetable442138.07Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
154WA3252_AFD_0103_1.almSpeedDeviation.REST442138.08Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Reset this alarm only
155WA3252_AFD_0103_1.almSpeedDeviation.SCmd_Suppress442138.15Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Supervisor Command to Suppress Alarm
156WA3252_AFD_0103_1.almSpeedDeviation.SCmd_UnSuppress442139.00Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Supervisor Command to Unsuppress Alarm
157WA3252_AFD_0103_1.almSpeedDeviation.Shelve442140.02Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Shelve Alarm Command to AE Server
158WA3252_AFD_0103_1.almSpeedDeviation.Shelved442140.09Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm Shelved Status from AE Server
159WA3252_AFD_0103_1.almSpeedDeviation.Suppress442140.00Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Suppress Alarm Command to AE Server
160WA3252_AFD_0103_1.almSpeedDeviation.Suppressed442140.08Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Alarm Suppressed Status from AE Server
161WA3252_AFD_0103_1.almSpeedDeviation.UACK442138.10Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Remove the Acknowledge Status
162WA3252_AFD_0103_1.almSpeedDeviation.UnShelve442140.03Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: Unshelve Alarm Command to AE Server
163WA3252_AFD_0103_1.almSpeedDeviation.UnSuppress442140.01Boolean1R/W1000RWPS Pump 1: Speed Deviation Alarm DDT: UnSuppress Alarm Command to AE Server
164WA3252_AFD_0103_1.ALRM442041.09Boolean1R/W1000RWPS Pump 1: At least one alarm on this device is active.
165WA3252_AFD_0103_1.ANUN442041.11Boolean1R/W1000RWPS Pump 1: At least one alarm in Device is annunciating (flash the device symbol)
166WA3252_AFD_0103_1.AUTO442040.15Boolean1R/W1000RWPS Pump 1: Set by HMI 0 = Device in Manual 1 Device in Auto
167WA3252_AFD_0103_1.AutoEnable442040.11Boolean1R/W1000RWPS Pump 1: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI
168WA3252_AFD_0103_1.AutoRdy442041.15Boolean1R/W1000RWPS Pump 1: Device is ready for auto control
169WA3252_AFD_0103_1.AutoStop442041.03Boolean1R/W1000RWPS Pump 1: Auto Stop from Auto Logic
170WA3252_AFD_0103_1.AutoStrt442041.02Boolean1R/W1000RWPS Pump 1: Auto Start from Auto Logic
171WA3252_AFD_0103_1.DevFault442042.05Boolean1R/W1000RWPS Pump 1: Deviation fault is active, this is not the delayed alarm
172WA3252_AFD_0103_1.Deviation442042.04Boolean1R/W1000RWPS Pump 1: Deviation Alarm from Logic
173WA3252_AFD_0103_1.FAIL442041.13Boolean1R/W1000RWPS Pump 1: Fail to Start, Fail to Stop or Motor Failure alarm is active
174WA3252_AFD_0103_1.FailToStop442041.07Boolean1R/W1000RWPS Pump 1: Device Failed to Stop
175WA3252_AFD_0103_1.FailToStrt442041.06Boolean1R/W1000RWPS Pump 1: Device Failed to Start
176WA3252_AFD_0103_1.GlobalReset442040.14Boolean1R/W1000RWPS Pump 1: Used to reset all alarms in the DFB
177WA3252_AFD_0103_1.HzEnable442040.12Boolean1R/W1000RWPS Pump 1: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)
178WA3252_AFD_0103_1.INFO442040.02Boolean1R/W1000RWPS Pump 1: True indicates blue flag should be displayed.
179WA3252_AFD_0103_1.INTK442041.00Boolean1R/W1000RWPS Pump 1: Locked by program (ESD)
180WA3252_AFD_0103_1.IR442040.07Boolean1R/W1000RWPS Pump 1: Remote: 1 = Device In Remote 0 = Device In Local
181WA3252_AFD_0103_1.ManDisable442040.13Boolean1R/W1000RWPS Pump 1: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual
182WA3252_AFD_0103_1.MD442041.14Boolean1R/W1000RWPS Pump 1: Device Run Command
183WA3252_AFD_0103_1.MF442040.09Boolean1R/W1000RWPS Pump 1: Motor Fail Status from Motor Controller
184WA3252_AFD_0103_1.MN442040.08Boolean1R/W1000RWPS Pump 1: Device Running Status
185WA3252_AFD_0103_1.MotorFailure442041.08Boolean1R/W1000RWPS Pump 1: General Failure Alarm from Motor Drive
186WA3252_AFD_0103_1.PCSuppress442042.08Boolean1R/W1000RWPS Pump 1: Suppress Alarm from Program Control
187WA3252_AFD_0103_1.PCUnShelve442042.10Boolean1R/W1000RWPS Pump 1: Unshelve Alarm from Program Control
188WA3252_AFD_0103_1.PCUnSuppress442042.09Boolean1R/W1000RWPS Pump 1: UnSuppress Alarm from Program Control
189WA3252_AFD_0103_1.PLCFault442042.00Boolean1R/W1000RWPS Pump 1: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
190WA3252_AFD_0103_1.PLCIOFault442042.01Boolean1R/W1000RWPS Pump 1: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
191WA3252_AFD_0103_1.RemoteEnable442040.10Boolean1R/W1000RWPS Pump 1: 1 remote/local input wired 0 = not wired
192WA3252_AFD_0103_1.Resetable442041.12Boolean1R/W1000RWPS Pump 1: All Alarms can be reset
193WA3252_AFD_0103_1.REST442040.05Boolean1R/W1000RWPS Pump 1: Reset: Command from HMI to Reset all alarms on this device.
194WA3252_AFD_0103_1.RSRT442041.04Boolean1R/W1000RWPS Pump 1: Reset Runtime Command from HMI
195WA3252_AFD_0103_1.RSST442041.05Boolean1R/W1000RWPS Pump 1: Reset Count of Starts Command from HMI
196WA3252_AFD_0103_1.Shelve442042.06Boolean1R/W1000RWPS Pump 1: Shelve Command from HMI
197WA3252_AFD_0103_1.Shelved442042.02Boolean1R/W1000RWPS Pump 1: General Alarm Shelved State
198WA3252_AFD_0103_1.STOP442040.01Boolean1R/W1000RWPS Pump 1: Stop Command from HMI
199WA3252_AFD_0103_1.StopFault442040.04Boolean1R/W1000RWPS Pump 1: Stop fault is active, this is not the delayed alarm
200WA3252_AFD_0103_1.STRT442040.00Boolean1R/W1000RWPS Pump 1: Start Command from HMI
201WA3252_AFD_0103_1.StrtFault442040.03Boolean1R/W1000RWPS Pump 1: Start fault is active, this is not the delayed alarm
202WA3252_AFD_0103_1.Suppress442042.07Boolean1R/W1000RWPS Pump 1: Suppress Command from HMI
203WA3252_AFD_0103_1.Suppressed442042.03Boolean1R/W1000RWPS Pump 1: General Alarm Suppressed State
204WA3252_AFD_0103_1.TAGR442041.01Boolean1R/W1000RWPS Pump 1: Tagged Out of Service
205WA3252_AFD_0103_1_BM459002.15Boolean1R/W1000RWPS Pump 1 Bypass Mode Command
206WA3252_AFD_0103_1_BM1459013.03Boolean1R/W1000RWPS Pump 1 In Bypass Mode
207WA3252_AFD_0103_1_BM1_raw459013.03Boolean1R/W1000RWPS Pump 1 In Bypass Mode
208WA3252_AFD_0103_1_BM2459014.14Boolean1R/W1000RWPS Pump 1 In Discharge Pressure Bypass Mode
209WA3252_AFD_0103_1_BM2_raw459014.14Boolean1R/W1000RWPS Pump 1 Discharge Pressure Bypass Mode
210WA3252_AFD_0103_1_BM3459013.13Boolean1R/W1000RWPS Pump 1 PCV Throttle Bypass Enabled
211WA3252_AFD_0103_1_FA.ACKN419000.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Acknowledge Alarm
212WA3252_AFD_0103_1_FA.AKED419000.11Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : At Least One Alarm is Acknowledged
213WA3252_AFD_0103_1_FA.Alarm.Ack419008.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
214WA3252_AFD_0103_1_FA.Alarm.Acked419008.11Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
215WA3252_AFD_0103_1_FA.Alarm.ACKN419006.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowledge Command
216WA3252_AFD_0103_1_FA.Alarm.AEShelveTMRDN419007.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
217WA3252_AFD_0103_1_FA.Alarm.AKED419006.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
218WA3252_AFD_0103_1_FA.Alarm.Alarm419008.12Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Command to AE Server
219WA3252_AFD_0103_1_FA.Alarm.AlarmState419006.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
220WA3252_AFD_0103_1_FA.Alarm.ALRM419006.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
221WA3252_AFD_0103_1_FA.Alarm.ANUN419006.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
222WA3252_AFD_0103_1_FA.Alarm.Bad419007.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
223WA3252_AFD_0103_1_FA.Alarm.Disable419008.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
224WA3252_AFD_0103_1_FA.Alarm.Disabled419008.10Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
225WA3252_AFD_0103_1_FA.Alarm.Enable419008.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
226WA3252_AFD_0103_1_FA.Alarm.Fault419006.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
227WA3252_AFD_0103_1_FA.Alarm.FaultInAlarm419006.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
228WA3252_AFD_0103_1_FA.Alarm.GlobalReset419006.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
229WA3252_AFD_0103_1_FA.Alarm.MCmd_Disable419006.12Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
230WA3252_AFD_0103_1_FA.Alarm.MCmd_Enable419006.11Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
231WA3252_AFD_0103_1_FA.Alarm.OCmd_Shelve419006.13Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
232WA3252_AFD_0103_1_FA.Alarm.OCmd_Unshelve419006.14Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
233WA3252_AFD_0103_1_FA.Alarm.Reset419008.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Reset Command to AE Server
234WA3252_AFD_0103_1_FA.Alarm.Resetable419006.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
235WA3252_AFD_0103_1_FA.Alarm.REST419006.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Reset this alarm only
236WA3252_AFD_0103_1_FA.Alarm.SCmd_Suppress419006.15Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
237WA3252_AFD_0103_1_FA.Alarm.SCmd_UnSuppress419007.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
238WA3252_AFD_0103_1_FA.Alarm.Shelve419008.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
239WA3252_AFD_0103_1_FA.Alarm.Shelved419008.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
240WA3252_AFD_0103_1_FA.Alarm.Suppress419008.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
241WA3252_AFD_0103_1_FA.Alarm.Suppressed419008.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
242WA3252_AFD_0103_1_FA.Alarm.UACK419006.10Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Remove the Acknowledge Status
243WA3252_AFD_0103_1_FA.Alarm.UnShelve419008.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
244WA3252_AFD_0103_1_FA.Alarm.UnSuppress419008.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
245WA3252_AFD_0103_1_FA.Alarm_EN419000.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : 0 = enable alarm
246WA3252_AFD_0103_1_FA.Alarm_Fault419001.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Alarm is in fault
247WA3252_AFD_0103_1_FA.AlarmState419000.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Input value signifying alarm
248WA3252_AFD_0103_1_FA.almPLCFault.Ack419020.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowlege Command to AE Server
249WA3252_AFD_0103_1_FA.almPLCFault.Acked419020.11Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
250WA3252_AFD_0103_1_FA.almPLCFault.ACKN419018.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowledge Command
251WA3252_AFD_0103_1_FA.almPLCFault.AEShelveTMRDN419019.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
252WA3252_AFD_0103_1_FA.almPLCFault.AKED419018.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
253WA3252_AFD_0103_1_FA.almPLCFault.Alarm419020.12Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Command to AE Server
254WA3252_AFD_0103_1_FA.almPLCFault.AlarmState419018.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
255WA3252_AFD_0103_1_FA.almPLCFault.ALRM419018.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
256WA3252_AFD_0103_1_FA.almPLCFault.ANUN419018.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
257WA3252_AFD_0103_1_FA.almPLCFault.Bad419019.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
258WA3252_AFD_0103_1_FA.almPLCFault.Disable419020.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
259WA3252_AFD_0103_1_FA.almPLCFault.Disabled419020.10Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
260WA3252_AFD_0103_1_FA.almPLCFault.Enable419020.04Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
261WA3252_AFD_0103_1_FA.almPLCFault.Fault419018.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
262WA3252_AFD_0103_1_FA.almPLCFault.FaultInAlarm419018.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
263WA3252_AFD_0103_1_FA.almPLCFault.GlobalReset419018.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
264WA3252_AFD_0103_1_FA.almPLCFault.MCmd_Disable419018.12Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
265WA3252_AFD_0103_1_FA.almPLCFault.MCmd_Enable419018.11Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
266WA3252_AFD_0103_1_FA.almPLCFault.OCmd_Shelve419018.13Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
267WA3252_AFD_0103_1_FA.almPLCFault.OCmd_Unshelve419018.14Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
268WA3252_AFD_0103_1_FA.almPLCFault.Reset419020.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Reset Command to AE Server
269WA3252_AFD_0103_1_FA.almPLCFault.Resetable419018.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
270WA3252_AFD_0103_1_FA.almPLCFault.REST419018.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Reset this alarm only
271WA3252_AFD_0103_1_FA.almPLCFault.SCmd_Suppress419018.15Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
272WA3252_AFD_0103_1_FA.almPLCFault.SCmd_UnSuppress419019.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
273WA3252_AFD_0103_1_FA.almPLCFault.Shelve419020.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
274WA3252_AFD_0103_1_FA.almPLCFault.Shelved419020.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
275WA3252_AFD_0103_1_FA.almPLCFault.Suppress419020.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
276WA3252_AFD_0103_1_FA.almPLCFault.Suppressed419020.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
277WA3252_AFD_0103_1_FA.almPLCFault.UACK419018.10Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Remove the Acknowledge Status
278WA3252_AFD_0103_1_FA.almPLCFault.UnShelve419020.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
279WA3252_AFD_0103_1_FA.almPLCFault.UnSuppress419020.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
280WA3252_AFD_0103_1_FA.ALRM419000.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : At Least One Alarm is Active
281WA3252_AFD_0103_1_FA.ANUN419000.10Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : At Least One Alarm is Annunciating
282WA3252_AFD_0103_1_FA.Fault419000.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Input tag to monitor for alarm
283WA3252_AFD_0103_1_FA.Faulted419000.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Input is in fault
284WA3252_AFD_0103_1_FA.FaultInAlarm419000.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Fault Is In Alarm (on longer than the delay)
285WA3252_AFD_0103_1_FA.GlobalReset419001.00Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Reset all Alarms On this PLC
286WA3252_AFD_0103_1_FA.InputAlarm419000.15Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure :
287WA3252_AFD_0103_1_FA.MCmd_Disable419000.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Maintenance Command to Disable Alarm
288WA3252_AFD_0103_1_FA.MCmd_Enable419000.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Maintenance Command to Enable Alarm
289WA3252_AFD_0103_1_FA.PCSuppress419001.01Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Suppress Alarm from Program Control
290WA3252_AFD_0103_1_FA.PCUnshelve419001.03Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Unshelve Alarm from Program Control
291WA3252_AFD_0103_1_FA.PCUnSuppress419001.02Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : UnSuppress Alarm from Program Control
292WA3252_AFD_0103_1_FA.PLCF419001.08Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
293WA3252_AFD_0103_1_FA.PLCIOFault419001.07Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
294WA3252_AFD_0103_1_FA.Resetable419000.12Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : At least one alarm is latched and all latched alarms are resetable
295WA3252_AFD_0103_1_FA.REST419000.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Reset Alarm
296WA3252_AFD_0103_1_FA.Shelve419000.13Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Shelve Command from HMI
297WA3252_AFD_0103_1_FA.Shelved419001.05Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Shelved Status
298WA3252_AFD_0103_1_FA.Suppress419000.14Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Suppress Command from HMI
299WA3252_AFD_0103_1_FA.Suppressed419001.06Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Suppressed Status
300WA3252_AFD_0103_1_FA.TAGR419001.09Boolean1R/W1000RWPS Pump 1 Cooling Water Flow Failure : Tagged Out of Service
301WA3252_AFD_0103_1_HS459002.14Boolean1R/W1000RWPS Pump 1 Scada Lockout
302WA3252_AFD_0103_1_IR459003.04Boolean1R/W1000RWPS Pump 1 Scada Enabled
303WA3252_AFD_0103_1_LOCKOUT459011.02Boolean1R/W1000RWPS Pump 1 HMI Lockout Command
304WA3252_AFD_0103_1_LOCKOUTRST459011.03Boolean1R/W1000RWPS Pump 1 HMI Lockout Reset
305WA3252_AFD_0103_1_MB459002.13Boolean1R/W1000RWPS Pump 1 Scada Stop
306WA3252_AFD_0103_1_MBU459014.10Boolean1R/W1000RWPS Pump 1 Scada Unplanned Stop
307WA3252_AFD_0103_1_MD459002.12Boolean1R/W1000RWPS Pump 1 Scada Start
308WA3252_AFD_0103_1_MF.ACKN460696.06Boolean1R/W1000Pump 1 Motor Seal Leak: Acknowledge Alarm
309WA3252_AFD_0103_1_MF.AKED460696.11Boolean1R/W1000Pump 1 Motor Seal Leak: At Least One Alarm is Acknowledged
310WA3252_AFD_0103_1_MF.Alarm.Ack460704.06Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowlege Command to AE Server
311WA3252_AFD_0103_1_MF.Alarm.Acked460704.11Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
312WA3252_AFD_0103_1_MF.Alarm.ACKN460702.09Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowledge Command
313WA3252_AFD_0103_1_MF.Alarm.AEShelveTMRDN460703.01Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
314WA3252_AFD_0103_1_MF.Alarm.AKED460702.06Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
315WA3252_AFD_0103_1_MF.Alarm.Alarm460704.12Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Command to AE Server
316WA3252_AFD_0103_1_MF.Alarm.AlarmState460702.01Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
317WA3252_AFD_0103_1_MF.Alarm.ALRM460702.04Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
318WA3252_AFD_0103_1_MF.Alarm.ANUN460702.05Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
319WA3252_AFD_0103_1_MF.Alarm.Bad460703.02Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
320WA3252_AFD_0103_1_MF.Alarm.Disable460704.05Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
321WA3252_AFD_0103_1_MF.Alarm.Disabled460704.10Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
322WA3252_AFD_0103_1_MF.Alarm.Enable460704.04Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
323WA3252_AFD_0103_1_MF.Alarm.Fault460702.00Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
324WA3252_AFD_0103_1_MF.Alarm.FaultInAlarm460702.03Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
325WA3252_AFD_0103_1_MF.Alarm.GlobalReset460702.02Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
326WA3252_AFD_0103_1_MF.Alarm.MCmd_Disable460702.12Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
327WA3252_AFD_0103_1_MF.Alarm.MCmd_Enable460702.11Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
328WA3252_AFD_0103_1_MF.Alarm.OCmd_Shelve460702.13Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
329WA3252_AFD_0103_1_MF.Alarm.OCmd_Unshelve460702.14Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
330WA3252_AFD_0103_1_MF.Alarm.Reset460704.07Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Reset Command to AE Server
331WA3252_AFD_0103_1_MF.Alarm.Resetable460702.07Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
332WA3252_AFD_0103_1_MF.Alarm.REST460702.08Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Reset this alarm only
333WA3252_AFD_0103_1_MF.Alarm.SCmd_Suppress460702.15Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
334WA3252_AFD_0103_1_MF.Alarm.SCmd_UnSuppress460703.00Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
335WA3252_AFD_0103_1_MF.Alarm.Shelve460704.02Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
336WA3252_AFD_0103_1_MF.Alarm.Shelved460704.09Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
337WA3252_AFD_0103_1_MF.Alarm.Suppress460704.00Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
338WA3252_AFD_0103_1_MF.Alarm.Suppressed460704.08Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
339WA3252_AFD_0103_1_MF.Alarm.UACK460702.10Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Remove the Acknowledge Status
340WA3252_AFD_0103_1_MF.Alarm.UnShelve460704.03Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
341WA3252_AFD_0103_1_MF.Alarm.UnSuppress460704.01Boolean1R/W1000Pump 1 Motor Seal Leak: ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
342WA3252_AFD_0103_1_MF.Alarm_EN460696.04Boolean1R/W1000Pump 1 Motor Seal Leak: 0 = enable alarm
343WA3252_AFD_0103_1_MF.Alarm_Fault460697.04Boolean1R/W1000Pump 1 Motor Seal Leak: Alarm is in fault
344WA3252_AFD_0103_1_MF.AlarmState460696.02Boolean1R/W1000Pump 1 Motor Seal Leak: Input value signifying alarm
345WA3252_AFD_0103_1_MF.almPLCFault.Ack460716.06Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Acknowlege Command to AE Server
346WA3252_AFD_0103_1_MF.almPLCFault.Acked460716.11Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
347WA3252_AFD_0103_1_MF.almPLCFault.ACKN460714.09Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Acknowledge Command
348WA3252_AFD_0103_1_MF.almPLCFault.AEShelveTMRDN460715.01Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
349WA3252_AFD_0103_1_MF.almPLCFault.AKED460714.06Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
350WA3252_AFD_0103_1_MF.almPLCFault.Alarm460716.12Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Command to AE Server
351WA3252_AFD_0103_1_MF.almPLCFault.AlarmState460714.01Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
352WA3252_AFD_0103_1_MF.almPLCFault.ALRM460714.04Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
353WA3252_AFD_0103_1_MF.almPLCFault.ANUN460714.05Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
354WA3252_AFD_0103_1_MF.almPLCFault.Bad460715.02Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
355WA3252_AFD_0103_1_MF.almPLCFault.Disable460716.05Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Disable Alarm Command to AE Server
356WA3252_AFD_0103_1_MF.almPLCFault.Disabled460716.10Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
357WA3252_AFD_0103_1_MF.almPLCFault.Enable460716.04Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Enable Alarm Command to AE Server
358WA3252_AFD_0103_1_MF.almPLCFault.Fault460714.00Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
359WA3252_AFD_0103_1_MF.almPLCFault.FaultInAlarm460714.03Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
360WA3252_AFD_0103_1_MF.almPLCFault.GlobalReset460714.02Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Used to reset all alarms in the PLC
361WA3252_AFD_0103_1_MF.almPLCFault.MCmd_Disable460714.12Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
362WA3252_AFD_0103_1_MF.almPLCFault.MCmd_Enable460714.11Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
363WA3252_AFD_0103_1_MF.almPLCFault.OCmd_Shelve460714.13Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Operator Command to Shelve Alarm
364WA3252_AFD_0103_1_MF.almPLCFault.OCmd_Unshelve460714.14Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
365WA3252_AFD_0103_1_MF.almPLCFault.Reset460716.07Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Reset Command to AE Server
366WA3252_AFD_0103_1_MF.almPLCFault.Resetable460714.07Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
367WA3252_AFD_0103_1_MF.almPLCFault.REST460714.08Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Reset this alarm only
368WA3252_AFD_0103_1_MF.almPLCFault.SCmd_Suppress460714.15Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
369WA3252_AFD_0103_1_MF.almPLCFault.SCmd_UnSuppress460715.00Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
370WA3252_AFD_0103_1_MF.almPLCFault.Shelve460716.02Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
371WA3252_AFD_0103_1_MF.almPLCFault.Shelved460716.09Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
372WA3252_AFD_0103_1_MF.almPLCFault.Suppress460716.00Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
373WA3252_AFD_0103_1_MF.almPLCFault.Suppressed460716.08Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
374WA3252_AFD_0103_1_MF.almPLCFault.UACK460714.10Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Remove the Acknowledge Status
375WA3252_AFD_0103_1_MF.almPLCFault.UnShelve460716.03Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
376WA3252_AFD_0103_1_MF.almPLCFault.UnSuppress460716.01Boolean1R/W1000Pump 1 Motor Seal Leak: PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
377WA3252_AFD_0103_1_MF.ALRM460696.09Boolean1R/W1000Pump 1 Motor Seal Leak: At Least One Alarm is Active
378WA3252_AFD_0103_1_MF.ANUN460696.10Boolean1R/W1000Pump 1 Motor Seal Leak: At Least One Alarm is Annunciating
379WA3252_AFD_0103_1_MF.Fault460696.00Boolean1R/W1000Pump 1 Motor Seal Leak: Input tag to monitor for alarm
380WA3252_AFD_0103_1_MF.Faulted460696.01Boolean1R/W1000Pump 1 Motor Seal Leak: Input is in fault
381WA3252_AFD_0103_1_MF.FaultInAlarm460696.03Boolean1R/W1000Pump 1 Motor Seal Leak: Fault Is In Alarm (on longer than the delay)
382WA3252_AFD_0103_1_MF.GlobalReset460697.00Boolean1R/W1000Pump 1 Motor Seal Leak: Reset all Alarms On this PLC
383WA3252_AFD_0103_1_MF.InputAlarm460696.15Boolean1R/W1000Pump 1 Motor Seal Leak:
384WA3252_AFD_0103_1_MF.MCmd_Disable460696.08Boolean1R/W1000Pump 1 Motor Seal Leak: Maintenance Command to Disable Alarm
385WA3252_AFD_0103_1_MF.MCmd_Enable460696.07Boolean1R/W1000Pump 1 Motor Seal Leak: Maintenance Command to Enable Alarm
386WA3252_AFD_0103_1_MF.PCSuppress460697.01Boolean1R/W1000Pump 1 Motor Seal Leak: Suppress Alarm from Program Control
387WA3252_AFD_0103_1_MF.PCUnshelve460697.03Boolean1R/W1000Pump 1 Motor Seal Leak: Unshelve Alarm from Program Control
388WA3252_AFD_0103_1_MF.PCUnSuppress460697.02Boolean1R/W1000Pump 1 Motor Seal Leak: UnSuppress Alarm from Program Control
389WA3252_AFD_0103_1_MF.PLCF460697.08Boolean1R/W1000Pump 1 Motor Seal Leak: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
390WA3252_AFD_0103_1_MF.PLCIOFault460697.07Boolean1R/W1000Pump 1 Motor Seal Leak: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
391WA3252_AFD_0103_1_MF.Resetable460696.12Boolean1R/W1000Pump 1 Motor Seal Leak: At least one alarm is latched and all latched alarms are resetable
392WA3252_AFD_0103_1_MF.REST460696.05Boolean1R/W1000Pump 1 Motor Seal Leak: Reset Alarm
393WA3252_AFD_0103_1_MF.Shelve460696.13Boolean1R/W1000Pump 1 Motor Seal Leak: Shelve Command from HMI
394WA3252_AFD_0103_1_MF.Shelved460697.05Boolean1R/W1000Pump 1 Motor Seal Leak: Shelved Status
395WA3252_AFD_0103_1_MF.Suppress460696.14Boolean1R/W1000Pump 1 Motor Seal Leak: Suppress Command from HMI
396WA3252_AFD_0103_1_MF.Suppressed460697.06Boolean1R/W1000Pump 1 Motor Seal Leak: Suppressed Status
397WA3252_AFD_0103_1_MF.TAGR460697.09Boolean1R/W1000Pump 1 Motor Seal Leak: Tagged Out of Service
398WA3252_AFD_0103_1_ML459003.05Boolean1R/W1000RWPS Pump 1 Ready
399WA3252_AFD_0103_1_MN459003.06Boolean1R/W1000RWPS Pump 1 Run Status
400WA3252_AFD_0103_1_MY.ACKN419120.06Boolean1R/W1000RWPS Pump 1 E. Stop : Acknowledge Alarm
401WA3252_AFD_0103_1_MY.AKED419120.11Boolean1R/W1000RWPS Pump 1 E. Stop : At Least One Alarm is Acknowledged
402WA3252_AFD_0103_1_MY.Alarm.Ack419128.06Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
403WA3252_AFD_0103_1_MY.Alarm.Acked419128.11Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
404WA3252_AFD_0103_1_MY.Alarm.ACKN419126.09Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Acknowledge Command
405WA3252_AFD_0103_1_MY.Alarm.AEShelveTMRDN419127.01Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
406WA3252_AFD_0103_1_MY.Alarm.AKED419126.06Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
407WA3252_AFD_0103_1_MY.Alarm.Alarm419128.12Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm Command to AE Server
408WA3252_AFD_0103_1_MY.Alarm.AlarmState419126.01Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
409WA3252_AFD_0103_1_MY.Alarm.ALRM419126.04Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
410WA3252_AFD_0103_1_MY.Alarm.ANUN419126.05Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
411WA3252_AFD_0103_1_MY.Alarm.Bad419127.02Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
412WA3252_AFD_0103_1_MY.Alarm.Disable419128.05Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
413WA3252_AFD_0103_1_MY.Alarm.Disabled419128.10Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
414WA3252_AFD_0103_1_MY.Alarm.Enable419128.04Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
415WA3252_AFD_0103_1_MY.Alarm.Fault419126.00Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
416WA3252_AFD_0103_1_MY.Alarm.FaultInAlarm419126.03Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
417WA3252_AFD_0103_1_MY.Alarm.GlobalReset419126.02Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
418WA3252_AFD_0103_1_MY.Alarm.MCmd_Disable419126.12Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
419WA3252_AFD_0103_1_MY.Alarm.MCmd_Enable419126.11Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
420WA3252_AFD_0103_1_MY.Alarm.OCmd_Shelve419126.13Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
421WA3252_AFD_0103_1_MY.Alarm.OCmd_Unshelve419126.14Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
422WA3252_AFD_0103_1_MY.Alarm.Reset419128.07Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Reset Command to AE Server
423WA3252_AFD_0103_1_MY.Alarm.Resetable419126.07Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
424WA3252_AFD_0103_1_MY.Alarm.REST419126.08Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Reset this alarm only
425WA3252_AFD_0103_1_MY.Alarm.SCmd_Suppress419126.15Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
426WA3252_AFD_0103_1_MY.Alarm.SCmd_UnSuppress419127.00Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
427WA3252_AFD_0103_1_MY.Alarm.Shelve419128.02Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
428WA3252_AFD_0103_1_MY.Alarm.Shelved419128.09Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
429WA3252_AFD_0103_1_MY.Alarm.Suppress419128.00Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
430WA3252_AFD_0103_1_MY.Alarm.Suppressed419128.08Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
431WA3252_AFD_0103_1_MY.Alarm.UACK419126.10Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Remove the Acknowledge Status
432WA3252_AFD_0103_1_MY.Alarm.UnShelve419128.03Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
433WA3252_AFD_0103_1_MY.Alarm.UnSuppress419128.01Boolean1R/W1000RWPS Pump 1 E. Stop : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
434WA3252_AFD_0103_1_MY.Alarm_EN419120.04Boolean1R/W1000RWPS Pump 1 E. Stop : 0 = enable alarm
435WA3252_AFD_0103_1_MY.Alarm_Fault419121.04Boolean1R/W1000RWPS Pump 1 E. Stop : Alarm is in fault
436WA3252_AFD_0103_1_MY.AlarmState419120.02Boolean1R/W1000RWPS Pump 1 E. Stop : Input value signifying alarm
437WA3252_AFD_0103_1_MY.almPLCFault.Ack419140.06Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Acknowlege Command to AE Server
438WA3252_AFD_0103_1_MY.almPLCFault.Acked419140.11Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
439WA3252_AFD_0103_1_MY.almPLCFault.ACKN419138.09Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Acknowledge Command
440WA3252_AFD_0103_1_MY.almPLCFault.AEShelveTMRDN419139.01Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
441WA3252_AFD_0103_1_MY.almPLCFault.AKED419138.06Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
442WA3252_AFD_0103_1_MY.almPLCFault.Alarm419140.12Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm Command to AE Server
443WA3252_AFD_0103_1_MY.almPLCFault.AlarmState419138.01Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
444WA3252_AFD_0103_1_MY.almPLCFault.ALRM419138.04Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
445WA3252_AFD_0103_1_MY.almPLCFault.ANUN419138.05Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
446WA3252_AFD_0103_1_MY.almPLCFault.Bad419139.02Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
447WA3252_AFD_0103_1_MY.almPLCFault.Disable419140.05Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
448WA3252_AFD_0103_1_MY.almPLCFault.Disabled419140.10Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
449WA3252_AFD_0103_1_MY.almPLCFault.Enable419140.04Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
450WA3252_AFD_0103_1_MY.almPLCFault.Fault419138.00Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
451WA3252_AFD_0103_1_MY.almPLCFault.FaultInAlarm419138.03Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
452WA3252_AFD_0103_1_MY.almPLCFault.GlobalReset419138.02Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
453WA3252_AFD_0103_1_MY.almPLCFault.MCmd_Disable419138.12Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
454WA3252_AFD_0103_1_MY.almPLCFault.MCmd_Enable419138.11Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
455WA3252_AFD_0103_1_MY.almPLCFault.OCmd_Shelve419138.13Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
456WA3252_AFD_0103_1_MY.almPLCFault.OCmd_Unshelve419138.14Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
457WA3252_AFD_0103_1_MY.almPLCFault.Reset419140.07Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Reset Command to AE Server
458WA3252_AFD_0103_1_MY.almPLCFault.Resetable419138.07Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
459WA3252_AFD_0103_1_MY.almPLCFault.REST419138.08Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Reset this alarm only
460WA3252_AFD_0103_1_MY.almPLCFault.SCmd_Suppress419138.15Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
461WA3252_AFD_0103_1_MY.almPLCFault.SCmd_UnSuppress419139.00Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
462WA3252_AFD_0103_1_MY.almPLCFault.Shelve419140.02Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
463WA3252_AFD_0103_1_MY.almPLCFault.Shelved419140.09Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
464WA3252_AFD_0103_1_MY.almPLCFault.Suppress419140.00Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
465WA3252_AFD_0103_1_MY.almPLCFault.Suppressed419140.08Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
466WA3252_AFD_0103_1_MY.almPLCFault.UACK419138.10Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Remove the Acknowledge Status
467WA3252_AFD_0103_1_MY.almPLCFault.UnShelve419140.03Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
468WA3252_AFD_0103_1_MY.almPLCFault.UnSuppress419140.01Boolean1R/W1000RWPS Pump 1 E. Stop : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
469WA3252_AFD_0103_1_MY.ALRM419120.09Boolean1R/W1000RWPS Pump 1 E. Stop : At Least One Alarm is Active
470WA3252_AFD_0103_1_MY.ANUN419120.10Boolean1R/W1000RWPS Pump 1 E. Stop : At Least One Alarm is Annunciating
471WA3252_AFD_0103_1_MY.Fault419120.00Boolean1R/W1000RWPS Pump 1 E. Stop : Input tag to monitor for alarm
472WA3252_AFD_0103_1_MY.Faulted419120.01Boolean1R/W1000RWPS Pump 1 E. Stop : Input is in fault
473WA3252_AFD_0103_1_MY.FaultInAlarm419120.03Boolean1R/W1000RWPS Pump 1 E. Stop : Fault Is In Alarm (on longer than the delay)
474WA3252_AFD_0103_1_MY.GlobalReset419121.00Boolean1R/W1000RWPS Pump 1 E. Stop : Reset all Alarms On this PLC
475WA3252_AFD_0103_1_MY.InputAlarm419120.15Boolean1R/W1000RWPS Pump 1 E. Stop :
476WA3252_AFD_0103_1_MY.MCmd_Disable419120.08Boolean1R/W1000RWPS Pump 1 E. Stop : Maintenance Command to Disable Alarm
477WA3252_AFD_0103_1_MY.MCmd_Enable419120.07Boolean1R/W1000RWPS Pump 1 E. Stop : Maintenance Command to Enable Alarm
478WA3252_AFD_0103_1_MY.PCSuppress419121.01Boolean1R/W1000RWPS Pump 1 E. Stop : Suppress Alarm from Program Control
479WA3252_AFD_0103_1_MY.PCUnshelve419121.03Boolean1R/W1000RWPS Pump 1 E. Stop : Unshelve Alarm from Program Control
480WA3252_AFD_0103_1_MY.PCUnSuppress419121.02Boolean1R/W1000RWPS Pump 1 E. Stop : UnSuppress Alarm from Program Control
481WA3252_AFD_0103_1_MY.PLCF419121.08Boolean1R/W1000RWPS Pump 1 E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
482WA3252_AFD_0103_1_MY.PLCIOFault419121.07Boolean1R/W1000RWPS Pump 1 E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
483WA3252_AFD_0103_1_MY.Resetable419120.12Boolean1R/W1000RWPS Pump 1 E. Stop : At least one alarm is latched and all latched alarms are resetable
484WA3252_AFD_0103_1_MY.REST419120.05Boolean1R/W1000RWPS Pump 1 E. Stop : Reset Alarm
485WA3252_AFD_0103_1_MY.Shelve419120.13Boolean1R/W1000RWPS Pump 1 E. Stop : Shelve Command from HMI
486WA3252_AFD_0103_1_MY.Shelved419121.05Boolean1R/W1000RWPS Pump 1 E. Stop : Shelved Status
487WA3252_AFD_0103_1_MY.Suppress419120.14Boolean1R/W1000RWPS Pump 1 E. Stop : Suppress Command from HMI
488WA3252_AFD_0103_1_MY.Suppressed419121.06Boolean1R/W1000RWPS Pump 1 E. Stop : Suppressed Status
489WA3252_AFD_0103_1_MY.TAGR419121.09Boolean1R/W1000RWPS Pump 1 E. Stop : Tagged Out of Service
490WA3252_AFD_0103_1_SI.ACKN401002.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Acknowledge Command from Logic to Acknowledge All Alarms in this DFB
491WA3252_AFD_0103_1_SI.AKED401001.07Boolean1R/W1000RWPS AFD Pump 1 Speed : At Least One Alarm is Acknowledged
492WA3252_AFD_0103_1_SI.almBrokenLoop.Ack401090.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Acknowlege Command to AE Server
493WA3252_AFD_0103_1_SI.almBrokenLoop.Acked401090.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm Acknowledged Status from AE Server
494WA3252_AFD_0103_1_SI.almBrokenLoop.ACKN401088.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Acknowledge Command
495WA3252_AFD_0103_1_SI.almBrokenLoop.AEShelveTMRDN401089.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm and Events Shelve Timer Done
496WA3252_AFD_0103_1_SI.almBrokenLoop.AKED401088.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
497WA3252_AFD_0103_1_SI.almBrokenLoop.Alarm401090.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm Command to AE Server
498WA3252_AFD_0103_1_SI.almBrokenLoop.AlarmState401088.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Value of the Fault input that indicates an alarm condition
499WA3252_AFD_0103_1_SI.almBrokenLoop.ALRM401088.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
500WA3252_AFD_0103_1_SI.almBrokenLoop.ANUN401088.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
501WA3252_AFD_0103_1_SI.almBrokenLoop.Bad401089.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Discrete Input condition indicating a Bad Signal condition
502WA3252_AFD_0103_1_SI.almBrokenLoop.Disable401090.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Disable Alarm Command to AE Server
503WA3252_AFD_0103_1_SI.almBrokenLoop.Disabled401090.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm Disabled Status from AE Server
504WA3252_AFD_0103_1_SI.almBrokenLoop.Enable401090.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Enable Alarm Command to AE Server
505WA3252_AFD_0103_1_SI.almBrokenLoop.Fault401088.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Discrete input condition indicating a faulted state.
506WA3252_AFD_0103_1_SI.almBrokenLoop.FaultInAlarm401088.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Fault Is In Alarm (on longer than the delay)
507WA3252_AFD_0103_1_SI.almBrokenLoop.GlobalReset401088.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Used to reset all alarms in the PLC
508WA3252_AFD_0103_1_SI.almBrokenLoop.MCmd_Disable401088.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Maintenance Command to Disable Alarm
509WA3252_AFD_0103_1_SI.almBrokenLoop.MCmd_Enable401088.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Maintenance Command to Enable Alarm
510WA3252_AFD_0103_1_SI.almBrokenLoop.OCmd_Shelve401088.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Operator Command to Shelve Alarm
511WA3252_AFD_0103_1_SI.almBrokenLoop.OCmd_Unshelve401088.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Operator Command to UnShelve Alarm
512WA3252_AFD_0103_1_SI.almBrokenLoop.Reset401090.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Reset Command to AE Server
513WA3252_AFD_0103_1_SI.almBrokenLoop.Resetable401088.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
514WA3252_AFD_0103_1_SI.almBrokenLoop.REST401088.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Reset this alarm only
515WA3252_AFD_0103_1_SI.almBrokenLoop.SCmd_Suppress401088.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Supervisor Command to Suppress Alarm
516WA3252_AFD_0103_1_SI.almBrokenLoop.SCmd_UnSuppress401089.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Supervisor Command to Unsuppress Alarm
517WA3252_AFD_0103_1_SI.almBrokenLoop.Shelve401090.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Shelve Alarm Command to AE Server
518WA3252_AFD_0103_1_SI.almBrokenLoop.Shelved401090.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm Shelved Status from AE Server
519WA3252_AFD_0103_1_SI.almBrokenLoop.Suppress401090.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Suppress Alarm Command to AE Server
520WA3252_AFD_0103_1_SI.almBrokenLoop.Suppressed401090.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Alarm Suppressed Status from AE Server
521WA3252_AFD_0103_1_SI.almBrokenLoop.UACK401088.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Remove the Acknowledge Status
522WA3252_AFD_0103_1_SI.almBrokenLoop.UnShelve401090.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: Unshelve Alarm Command to AE Server
523WA3252_AFD_0103_1_SI.almBrokenLoop.UnSuppress401090.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm DDT: UnSuppress Alarm Command to AE Server
524WA3252_AFD_0103_1_SI.almHigh.Ack401054.06Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Acknowlege Command to AE Server
525WA3252_AFD_0103_1_SI.almHigh.Acked401054.11Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm Acknowledged Status from AE Server
526WA3252_AFD_0103_1_SI.almHigh.ACKN401052.09Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Acknowledge Command
527WA3252_AFD_0103_1_SI.almHigh.AEShelveTMRDN401053.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm and Events Shelve Timer Done
528WA3252_AFD_0103_1_SI.almHigh.AKED401052.06Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
529WA3252_AFD_0103_1_SI.almHigh.Alarm401054.12Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm Command to AE Server
530WA3252_AFD_0103_1_SI.almHigh.AlarmState401052.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Value of the Fault input that indicates an alarm condition
531WA3252_AFD_0103_1_SI.almHigh.ALRM401052.04Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
532WA3252_AFD_0103_1_SI.almHigh.ANUN401052.05Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
533WA3252_AFD_0103_1_SI.almHigh.Bad401053.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Discrete Input condition indicating a Bad Signal condition
534WA3252_AFD_0103_1_SI.almHigh.Disable401054.05Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Disable Alarm Command to AE Server
535WA3252_AFD_0103_1_SI.almHigh.Disabled401054.10Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm Disabled Status from AE Server
536WA3252_AFD_0103_1_SI.almHigh.Enable401054.04Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Enable Alarm Command to AE Server
537WA3252_AFD_0103_1_SI.almHigh.Fault401052.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Discrete input condition indicating a faulted state.
538WA3252_AFD_0103_1_SI.almHigh.FaultInAlarm401052.03Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Fault Is In Alarm (on longer than the delay)
539WA3252_AFD_0103_1_SI.almHigh.GlobalReset401052.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Used to reset all alarms in the PLC
540WA3252_AFD_0103_1_SI.almHigh.MCmd_Disable401052.12Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Maintenance Command to Disable Alarm
541WA3252_AFD_0103_1_SI.almHigh.MCmd_Enable401052.11Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Maintenance Command to Enable Alarm
542WA3252_AFD_0103_1_SI.almHigh.OCmd_Shelve401052.13Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Operator Command to Shelve Alarm
543WA3252_AFD_0103_1_SI.almHigh.OCmd_Unshelve401052.14Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Operator Command to UnShelve Alarm
544WA3252_AFD_0103_1_SI.almHigh.Reset401054.07Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Reset Command to AE Server
545WA3252_AFD_0103_1_SI.almHigh.Resetable401052.07Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
546WA3252_AFD_0103_1_SI.almHigh.REST401052.08Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Reset this alarm only
547WA3252_AFD_0103_1_SI.almHigh.SCmd_Suppress401052.15Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Supervisor Command to Suppress Alarm
548WA3252_AFD_0103_1_SI.almHigh.SCmd_UnSuppress401053.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Supervisor Command to Unsuppress Alarm
549WA3252_AFD_0103_1_SI.almHigh.Shelve401054.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Shelve Alarm Command to AE Server
550WA3252_AFD_0103_1_SI.almHigh.Shelved401054.09Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm Shelved Status from AE Server
551WA3252_AFD_0103_1_SI.almHigh.Suppress401054.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Suppress Alarm Command to AE Server
552WA3252_AFD_0103_1_SI.almHigh.Suppressed401054.08Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Alarm Suppressed Status from AE Server
553WA3252_AFD_0103_1_SI.almHigh.UACK401052.10Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Remove the Acknowledge Status
554WA3252_AFD_0103_1_SI.almHigh.UnShelve401054.03Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: Unshelve Alarm Command to AE Server
555WA3252_AFD_0103_1_SI.almHigh.UnSuppress401054.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm DDT: UnSuppress Alarm Command to AE Server
556WA3252_AFD_0103_1_SI.almHighHigh.Ack401042.06Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Acknowlege Command to AE Server
557WA3252_AFD_0103_1_SI.almHighHigh.Acked401042.11Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm Acknowledged Status from AE Server
558WA3252_AFD_0103_1_SI.almHighHigh.ACKN401040.09Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Acknowledge Command
559WA3252_AFD_0103_1_SI.almHighHigh.AEShelveTMRDN401041.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm and Events Shelve Timer Done
560WA3252_AFD_0103_1_SI.almHighHigh.AKED401040.06Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
561WA3252_AFD_0103_1_SI.almHighHigh.Alarm401042.12Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm Command to AE Server
562WA3252_AFD_0103_1_SI.almHighHigh.AlarmState401040.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Value of the Fault input that indicates an alarm condition
563WA3252_AFD_0103_1_SI.almHighHigh.ALRM401040.04Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
564WA3252_AFD_0103_1_SI.almHighHigh.ANUN401040.05Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
565WA3252_AFD_0103_1_SI.almHighHigh.Bad401041.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Discrete Input condition indicating a Bad Signal condition
566WA3252_AFD_0103_1_SI.almHighHigh.Disable401042.05Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Disable Alarm Command to AE Server
567WA3252_AFD_0103_1_SI.almHighHigh.Disabled401042.10Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm Disabled Status from AE Server
568WA3252_AFD_0103_1_SI.almHighHigh.Enable401042.04Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Enable Alarm Command to AE Server
569WA3252_AFD_0103_1_SI.almHighHigh.Fault401040.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Discrete input condition indicating a faulted state.
570WA3252_AFD_0103_1_SI.almHighHigh.FaultInAlarm401040.03Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Fault Is In Alarm (on longer than the delay)
571WA3252_AFD_0103_1_SI.almHighHigh.GlobalReset401040.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Used to reset all alarms in the PLC
572WA3252_AFD_0103_1_SI.almHighHigh.MCmd_Disable401040.12Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Maintenance Command to Disable Alarm
573WA3252_AFD_0103_1_SI.almHighHigh.MCmd_Enable401040.11Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Maintenance Command to Enable Alarm
574WA3252_AFD_0103_1_SI.almHighHigh.OCmd_Shelve401040.13Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Operator Command to Shelve Alarm
575WA3252_AFD_0103_1_SI.almHighHigh.OCmd_Unshelve401040.14Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Operator Command to UnShelve Alarm
576WA3252_AFD_0103_1_SI.almHighHigh.Reset401042.07Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Reset Command to AE Server
577WA3252_AFD_0103_1_SI.almHighHigh.Resetable401040.07Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
578WA3252_AFD_0103_1_SI.almHighHigh.REST401040.08Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Reset this alarm only
579WA3252_AFD_0103_1_SI.almHighHigh.SCmd_Suppress401040.15Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Supervisor Command to Suppress Alarm
580WA3252_AFD_0103_1_SI.almHighHigh.SCmd_UnSuppress401041.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Supervisor Command to Unsuppress Alarm
581WA3252_AFD_0103_1_SI.almHighHigh.Shelve401042.02Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Shelve Alarm Command to AE Server
582WA3252_AFD_0103_1_SI.almHighHigh.Shelved401042.09Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm Shelved Status from AE Server
583WA3252_AFD_0103_1_SI.almHighHigh.Suppress401042.00Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Suppress Alarm Command to AE Server
584WA3252_AFD_0103_1_SI.almHighHigh.Suppressed401042.08Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Alarm Suppressed Status from AE Server
585WA3252_AFD_0103_1_SI.almHighHigh.UACK401040.10Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Remove the Acknowledge Status
586WA3252_AFD_0103_1_SI.almHighHigh.UnShelve401042.03Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: Unshelve Alarm Command to AE Server
587WA3252_AFD_0103_1_SI.almHighHigh.UnSuppress401042.01Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm DDT: UnSuppress Alarm Command to AE Server
588WA3252_AFD_0103_1_SI.almLow.Ack401066.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Acknowlege Command to AE Server
589WA3252_AFD_0103_1_SI.almLow.Acked401066.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm Acknowledged Status from AE Server
590WA3252_AFD_0103_1_SI.almLow.ACKN401064.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Acknowledge Command
591WA3252_AFD_0103_1_SI.almLow.AEShelveTMRDN401065.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm and Events Shelve Timer Done
592WA3252_AFD_0103_1_SI.almLow.AKED401064.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
593WA3252_AFD_0103_1_SI.almLow.Alarm401066.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm Command to AE Server
594WA3252_AFD_0103_1_SI.almLow.AlarmState401064.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Value of the Fault input that indicates an alarm condition
595WA3252_AFD_0103_1_SI.almLow.ALRM401064.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
596WA3252_AFD_0103_1_SI.almLow.ANUN401064.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
597WA3252_AFD_0103_1_SI.almLow.Bad401065.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Discrete Input condition indicating a Bad Signal condition
598WA3252_AFD_0103_1_SI.almLow.Disable401066.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Disable Alarm Command to AE Server
599WA3252_AFD_0103_1_SI.almLow.Disabled401066.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm Disabled Status from AE Server
600WA3252_AFD_0103_1_SI.almLow.Enable401066.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Enable Alarm Command to AE Server
601WA3252_AFD_0103_1_SI.almLow.Fault401064.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Discrete input condition indicating a faulted state.
602WA3252_AFD_0103_1_SI.almLow.FaultInAlarm401064.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Fault Is In Alarm (on longer than the delay)
603WA3252_AFD_0103_1_SI.almLow.GlobalReset401064.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Used to reset all alarms in the PLC
604WA3252_AFD_0103_1_SI.almLow.MCmd_Disable401064.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Maintenance Command to Disable Alarm
605WA3252_AFD_0103_1_SI.almLow.MCmd_Enable401064.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Maintenance Command to Enable Alarm
606WA3252_AFD_0103_1_SI.almLow.OCmd_Shelve401064.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Operator Command to Shelve Alarm
607WA3252_AFD_0103_1_SI.almLow.OCmd_Unshelve401064.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Operator Command to UnShelve Alarm
608WA3252_AFD_0103_1_SI.almLow.Reset401066.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Reset Command to AE Server
609WA3252_AFD_0103_1_SI.almLow.Resetable401064.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
610WA3252_AFD_0103_1_SI.almLow.REST401064.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Reset this alarm only
611WA3252_AFD_0103_1_SI.almLow.SCmd_Suppress401064.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Supervisor Command to Suppress Alarm
612WA3252_AFD_0103_1_SI.almLow.SCmd_UnSuppress401065.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Supervisor Command to Unsuppress Alarm
613WA3252_AFD_0103_1_SI.almLow.Shelve401066.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Shelve Alarm Command to AE Server
614WA3252_AFD_0103_1_SI.almLow.Shelved401066.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm Shelved Status from AE Server
615WA3252_AFD_0103_1_SI.almLow.Suppress401066.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Suppress Alarm Command to AE Server
616WA3252_AFD_0103_1_SI.almLow.Suppressed401066.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Alarm Suppressed Status from AE Server
617WA3252_AFD_0103_1_SI.almLow.UACK401064.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Remove the Acknowledge Status
618WA3252_AFD_0103_1_SI.almLow.UnShelve401066.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: Unshelve Alarm Command to AE Server
619WA3252_AFD_0103_1_SI.almLow.UnSuppress401066.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm DDT: UnSuppress Alarm Command to AE Server
620WA3252_AFD_0103_1_SI.almLowLow.Ack401078.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Acknowlege Command to AE Server
621WA3252_AFD_0103_1_SI.almLowLow.Acked401078.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm Acknowledged Status from AE Server
622WA3252_AFD_0103_1_SI.almLowLow.ACKN401076.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Acknowledge Command
623WA3252_AFD_0103_1_SI.almLowLow.AEShelveTMRDN401077.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm and Events Shelve Timer Done
624WA3252_AFD_0103_1_SI.almLowLow.AKED401076.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
625WA3252_AFD_0103_1_SI.almLowLow.Alarm401078.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm Command to AE Server
626WA3252_AFD_0103_1_SI.almLowLow.AlarmState401076.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Value of the Fault input that indicates an alarm condition
627WA3252_AFD_0103_1_SI.almLowLow.ALRM401076.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
628WA3252_AFD_0103_1_SI.almLowLow.ANUN401076.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
629WA3252_AFD_0103_1_SI.almLowLow.Bad401077.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Discrete Input condition indicating a Bad Signal condition
630WA3252_AFD_0103_1_SI.almLowLow.Disable401078.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Disable Alarm Command to AE Server
631WA3252_AFD_0103_1_SI.almLowLow.Disabled401078.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm Disabled Status from AE Server
632WA3252_AFD_0103_1_SI.almLowLow.Enable401078.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Enable Alarm Command to AE Server
633WA3252_AFD_0103_1_SI.almLowLow.Fault401076.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Discrete input condition indicating a faulted state.
634WA3252_AFD_0103_1_SI.almLowLow.FaultInAlarm401076.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Fault Is In Alarm (on longer than the delay)
635WA3252_AFD_0103_1_SI.almLowLow.GlobalReset401076.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Used to reset all alarms in the PLC
636WA3252_AFD_0103_1_SI.almLowLow.MCmd_Disable401076.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Maintenance Command to Disable Alarm
637WA3252_AFD_0103_1_SI.almLowLow.MCmd_Enable401076.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Maintenance Command to Enable Alarm
638WA3252_AFD_0103_1_SI.almLowLow.OCmd_Shelve401076.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Operator Command to Shelve Alarm
639WA3252_AFD_0103_1_SI.almLowLow.OCmd_Unshelve401076.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Operator Command to UnShelve Alarm
640WA3252_AFD_0103_1_SI.almLowLow.Reset401078.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Reset Command to AE Server
641WA3252_AFD_0103_1_SI.almLowLow.Resetable401076.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
642WA3252_AFD_0103_1_SI.almLowLow.REST401076.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Reset this alarm only
643WA3252_AFD_0103_1_SI.almLowLow.SCmd_Suppress401076.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Supervisor Command to Suppress Alarm
644WA3252_AFD_0103_1_SI.almLowLow.SCmd_UnSuppress401077.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Supervisor Command to Unsuppress Alarm
645WA3252_AFD_0103_1_SI.almLowLow.Shelve401078.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Shelve Alarm Command to AE Server
646WA3252_AFD_0103_1_SI.almLowLow.Shelved401078.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm Shelved Status from AE Server
647WA3252_AFD_0103_1_SI.almLowLow.Suppress401078.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Suppress Alarm Command to AE Server
648WA3252_AFD_0103_1_SI.almLowLow.Suppressed401078.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Alarm Suppressed Status from AE Server
649WA3252_AFD_0103_1_SI.almLowLow.UACK401076.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Remove the Acknowledge Status
650WA3252_AFD_0103_1_SI.almLowLow.UnShelve401078.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: Unshelve Alarm Command to AE Server
651WA3252_AFD_0103_1_SI.almLowLow.UnSuppress401078.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm DDT: UnSuppress Alarm Command to AE Server
652WA3252_AFD_0103_1_SI.almOverRange.Ack401102.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Acknowlege Command to AE Server
653WA3252_AFD_0103_1_SI.almOverRange.Acked401102.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm Acknowledged Status from AE Server
654WA3252_AFD_0103_1_SI.almOverRange.ACKN401100.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Acknowledge Command
655WA3252_AFD_0103_1_SI.almOverRange.AEShelveTMRDN401101.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm and Events Shelve Timer Done
656WA3252_AFD_0103_1_SI.almOverRange.AKED401100.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
657WA3252_AFD_0103_1_SI.almOverRange.Alarm401102.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm Command to AE Server
658WA3252_AFD_0103_1_SI.almOverRange.AlarmState401100.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Value of the Fault input that indicates an alarm condition
659WA3252_AFD_0103_1_SI.almOverRange.ALRM401100.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
660WA3252_AFD_0103_1_SI.almOverRange.ANUN401100.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
661WA3252_AFD_0103_1_SI.almOverRange.Bad401101.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Discrete Input condition indicating a Bad Signal condition
662WA3252_AFD_0103_1_SI.almOverRange.Disable401102.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Disable Alarm Command to AE Server
663WA3252_AFD_0103_1_SI.almOverRange.Disabled401102.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm Disabled Status from AE Server
664WA3252_AFD_0103_1_SI.almOverRange.Enable401102.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Enable Alarm Command to AE Server
665WA3252_AFD_0103_1_SI.almOverRange.Fault401100.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Discrete input condition indicating a faulted state.
666WA3252_AFD_0103_1_SI.almOverRange.FaultInAlarm401100.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Fault Is In Alarm (on longer than the delay)
667WA3252_AFD_0103_1_SI.almOverRange.GlobalReset401100.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Used to reset all alarms in the PLC
668WA3252_AFD_0103_1_SI.almOverRange.MCmd_Disable401100.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Maintenance Command to Disable Alarm
669WA3252_AFD_0103_1_SI.almOverRange.MCmd_Enable401100.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Maintenance Command to Enable Alarm
670WA3252_AFD_0103_1_SI.almOverRange.OCmd_Shelve401100.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Operator Command to Shelve Alarm
671WA3252_AFD_0103_1_SI.almOverRange.OCmd_Unshelve401100.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Operator Command to UnShelve Alarm
672WA3252_AFD_0103_1_SI.almOverRange.Reset401102.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Reset Command to AE Server
673WA3252_AFD_0103_1_SI.almOverRange.Resetable401100.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
674WA3252_AFD_0103_1_SI.almOverRange.REST401100.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Reset this alarm only
675WA3252_AFD_0103_1_SI.almOverRange.SCmd_Suppress401100.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Supervisor Command to Suppress Alarm
676WA3252_AFD_0103_1_SI.almOverRange.SCmd_UnSuppress401101.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Supervisor Command to Unsuppress Alarm
677WA3252_AFD_0103_1_SI.almOverRange.Shelve401102.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Shelve Alarm Command to AE Server
678WA3252_AFD_0103_1_SI.almOverRange.Shelved401102.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm Shelved Status from AE Server
679WA3252_AFD_0103_1_SI.almOverRange.Suppress401102.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Suppress Alarm Command to AE Server
680WA3252_AFD_0103_1_SI.almOverRange.Suppressed401102.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Alarm Suppressed Status from AE Server
681WA3252_AFD_0103_1_SI.almOverRange.UACK401100.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Remove the Acknowledge Status
682WA3252_AFD_0103_1_SI.almOverRange.UnShelve401102.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: Unshelve Alarm Command to AE Server
683WA3252_AFD_0103_1_SI.almOverRange.UnSuppress401102.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm DDT: UnSuppress Alarm Command to AE Server
684WA3252_AFD_0103_1_SI.almPLCFault.Ack401138.06Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Acknowlege Command to AE Server
685WA3252_AFD_0103_1_SI.almPLCFault.Acked401138.11Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm Acknowledged Status from AE Server
686WA3252_AFD_0103_1_SI.almPLCFault.ACKN401136.09Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Acknowledge Command
687WA3252_AFD_0103_1_SI.almPLCFault.AEShelveTMRDN401137.01Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm and Events Shelve Timer Done
688WA3252_AFD_0103_1_SI.almPLCFault.AKED401136.06Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
689WA3252_AFD_0103_1_SI.almPLCFault.Alarm401138.12Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm Command to AE Server
690WA3252_AFD_0103_1_SI.almPLCFault.AlarmState401136.01Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
691WA3252_AFD_0103_1_SI.almPLCFault.ALRM401136.04Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
692WA3252_AFD_0103_1_SI.almPLCFault.ANUN401136.05Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
693WA3252_AFD_0103_1_SI.almPLCFault.Bad401137.02Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
694WA3252_AFD_0103_1_SI.almPLCFault.Disable401138.05Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Disable Alarm Command to AE Server
695WA3252_AFD_0103_1_SI.almPLCFault.Disabled401138.10Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm Disabled Status from AE Server
696WA3252_AFD_0103_1_SI.almPLCFault.Enable401138.04Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Enable Alarm Command to AE Server
697WA3252_AFD_0103_1_SI.almPLCFault.Fault401136.00Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Discrete input condition indicating a faulted state.
698WA3252_AFD_0103_1_SI.almPLCFault.FaultInAlarm401136.03Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
699WA3252_AFD_0103_1_SI.almPLCFault.GlobalReset401136.02Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Used to reset all alarms in the PLC
700WA3252_AFD_0103_1_SI.almPLCFault.MCmd_Disable401136.12Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Maintenance Command to Disable Alarm
701WA3252_AFD_0103_1_SI.almPLCFault.MCmd_Enable401136.11Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Maintenance Command to Enable Alarm
702WA3252_AFD_0103_1_SI.almPLCFault.OCmd_Shelve401136.13Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Operator Command to Shelve Alarm
703WA3252_AFD_0103_1_SI.almPLCFault.OCmd_Unshelve401136.14Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Operator Command to UnShelve Alarm
704WA3252_AFD_0103_1_SI.almPLCFault.Reset401138.07Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Reset Command to AE Server
705WA3252_AFD_0103_1_SI.almPLCFault.Resetable401136.07Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
706WA3252_AFD_0103_1_SI.almPLCFault.REST401136.08Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Reset this alarm only
707WA3252_AFD_0103_1_SI.almPLCFault.SCmd_Suppress401136.15Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Supervisor Command to Suppress Alarm
708WA3252_AFD_0103_1_SI.almPLCFault.SCmd_UnSuppress401137.00Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
709WA3252_AFD_0103_1_SI.almPLCFault.Shelve401138.02Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Shelve Alarm Command to AE Server
710WA3252_AFD_0103_1_SI.almPLCFault.Shelved401138.09Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm Shelved Status from AE Server
711WA3252_AFD_0103_1_SI.almPLCFault.Suppress401138.00Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Suppress Alarm Command to AE Server
712WA3252_AFD_0103_1_SI.almPLCFault.Suppressed401138.08Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Alarm Suppressed Status from AE Server
713WA3252_AFD_0103_1_SI.almPLCFault.UACK401136.10Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Remove the Acknowledge Status
714WA3252_AFD_0103_1_SI.almPLCFault.UnShelve401138.03Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: Unshelve Alarm Command to AE Server
715WA3252_AFD_0103_1_SI.almPLCFault.UnSuppress401138.01Boolean1R/W1000RWPS AFD Pump 1 Speed : PLC IO Fault Alarm DDT: UnSuppress Alarm Command to AE Server
716WA3252_AFD_0103_1_SI.almRateOfChange.Ack401126.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Acknowlege Command to AE Server
717WA3252_AFD_0103_1_SI.almRateOfChange.Acked401126.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm Acknowledged Status from AE Server
718WA3252_AFD_0103_1_SI.almRateOfChange.ACKN401124.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Acknowledge Command
719WA3252_AFD_0103_1_SI.almRateOfChange.AEShelveTMRDN401125.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm and Events Shelve Timer Done
720WA3252_AFD_0103_1_SI.almRateOfChange.AKED401124.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
721WA3252_AFD_0103_1_SI.almRateOfChange.Alarm401126.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm Command to AE Server
722WA3252_AFD_0103_1_SI.almRateOfChange.AlarmState401124.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Value of the Fault input that indicates an alarm condition
723WA3252_AFD_0103_1_SI.almRateOfChange.ALRM401124.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
724WA3252_AFD_0103_1_SI.almRateOfChange.ANUN401124.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
725WA3252_AFD_0103_1_SI.almRateOfChange.Bad401125.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Discrete Input condition indicating a Bad Signal condition
726WA3252_AFD_0103_1_SI.almRateOfChange.Disable401126.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Disable Alarm Command to AE Server
727WA3252_AFD_0103_1_SI.almRateOfChange.Disabled401126.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm Disabled Status from AE Server
728WA3252_AFD_0103_1_SI.almRateOfChange.Enable401126.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Enable Alarm Command to AE Server
729WA3252_AFD_0103_1_SI.almRateOfChange.Fault401124.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Discrete input condition indicating a faulted state.
730WA3252_AFD_0103_1_SI.almRateOfChange.FaultInAlarm401124.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Fault Is In Alarm (on longer than the delay)
731WA3252_AFD_0103_1_SI.almRateOfChange.GlobalReset401124.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Used to reset all alarms in the PLC
732WA3252_AFD_0103_1_SI.almRateOfChange.MCmd_Disable401124.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Maintenance Command to Disable Alarm
733WA3252_AFD_0103_1_SI.almRateOfChange.MCmd_Enable401124.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Maintenance Command to Enable Alarm
734WA3252_AFD_0103_1_SI.almRateOfChange.OCmd_Shelve401124.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Operator Command to Shelve Alarm
735WA3252_AFD_0103_1_SI.almRateOfChange.OCmd_Unshelve401124.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Operator Command to UnShelve Alarm
736WA3252_AFD_0103_1_SI.almRateOfChange.Reset401126.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Reset Command to AE Server
737WA3252_AFD_0103_1_SI.almRateOfChange.Resetable401124.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
738WA3252_AFD_0103_1_SI.almRateOfChange.REST401124.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Reset this alarm only
739WA3252_AFD_0103_1_SI.almRateOfChange.SCmd_Suppress401124.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Supervisor Command to Suppress Alarm
740WA3252_AFD_0103_1_SI.almRateOfChange.SCmd_UnSuppress401125.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Supervisor Command to Unsuppress Alarm
741WA3252_AFD_0103_1_SI.almRateOfChange.Shelve401126.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Shelve Alarm Command to AE Server
742WA3252_AFD_0103_1_SI.almRateOfChange.Shelved401126.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm Shelved Status from AE Server
743WA3252_AFD_0103_1_SI.almRateOfChange.Suppress401126.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Suppress Alarm Command to AE Server
744WA3252_AFD_0103_1_SI.almRateOfChange.Suppressed401126.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Alarm Suppressed Status from AE Server
745WA3252_AFD_0103_1_SI.almRateOfChange.UACK401124.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Remove the Acknowledge Status
746WA3252_AFD_0103_1_SI.almRateOfChange.UnShelve401126.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: Unshelve Alarm Command to AE Server
747WA3252_AFD_0103_1_SI.almRateOfChange.UnSuppress401126.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate Of Change Alarm DDT: UnSuppress Alarm Command to AE Server
748WA3252_AFD_0103_1_SI.almUnderRange.Ack401114.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Acknowlege Command to AE Server
749WA3252_AFD_0103_1_SI.almUnderRange.Acked401114.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm Acknowledged Status from AE Server
750WA3252_AFD_0103_1_SI.almUnderRange.ACKN401112.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Acknowledge Command
751WA3252_AFD_0103_1_SI.almUnderRange.AEShelveTMRDN401113.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm and Events Shelve Timer Done
752WA3252_AFD_0103_1_SI.almUnderRange.AKED401112.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
753WA3252_AFD_0103_1_SI.almUnderRange.Alarm401114.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm Command to AE Server
754WA3252_AFD_0103_1_SI.almUnderRange.AlarmState401112.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Value of the Fault input that indicates an alarm condition
755WA3252_AFD_0103_1_SI.almUnderRange.ALRM401112.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
756WA3252_AFD_0103_1_SI.almUnderRange.ANUN401112.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
757WA3252_AFD_0103_1_SI.almUnderRange.Bad401113.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Discrete Input condition indicating a Bad Signal condition
758WA3252_AFD_0103_1_SI.almUnderRange.Disable401114.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Disable Alarm Command to AE Server
759WA3252_AFD_0103_1_SI.almUnderRange.Disabled401114.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm Disabled Status from AE Server
760WA3252_AFD_0103_1_SI.almUnderRange.Enable401114.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Enable Alarm Command to AE Server
761WA3252_AFD_0103_1_SI.almUnderRange.Fault401112.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Discrete input condition indicating a faulted state.
762WA3252_AFD_0103_1_SI.almUnderRange.FaultInAlarm401112.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Fault Is In Alarm (on longer than the delay)
763WA3252_AFD_0103_1_SI.almUnderRange.GlobalReset401112.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Used to reset all alarms in the PLC
764WA3252_AFD_0103_1_SI.almUnderRange.MCmd_Disable401112.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Maintenance Command to Disable Alarm
765WA3252_AFD_0103_1_SI.almUnderRange.MCmd_Enable401112.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Maintenance Command to Enable Alarm
766WA3252_AFD_0103_1_SI.almUnderRange.OCmd_Shelve401112.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Operator Command to Shelve Alarm
767WA3252_AFD_0103_1_SI.almUnderRange.OCmd_Unshelve401112.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Operator Command to UnShelve Alarm
768WA3252_AFD_0103_1_SI.almUnderRange.Reset401114.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Reset Command to AE Server
769WA3252_AFD_0103_1_SI.almUnderRange.Resetable401112.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
770WA3252_AFD_0103_1_SI.almUnderRange.REST401112.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Reset this alarm only
771WA3252_AFD_0103_1_SI.almUnderRange.SCmd_Suppress401112.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Supervisor Command to Suppress Alarm
772WA3252_AFD_0103_1_SI.almUnderRange.SCmd_UnSuppress401113.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Supervisor Command to Unsuppress Alarm
773WA3252_AFD_0103_1_SI.almUnderRange.Shelve401114.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Shelve Alarm Command to AE Server
774WA3252_AFD_0103_1_SI.almUnderRange.Shelved401114.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm Shelved Status from AE Server
775WA3252_AFD_0103_1_SI.almUnderRange.Suppress401114.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Suppress Alarm Command to AE Server
776WA3252_AFD_0103_1_SI.almUnderRange.Suppressed401114.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Alarm Suppressed Status from AE Server
777WA3252_AFD_0103_1_SI.almUnderRange.UACK401112.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Remove the Acknowledge Status
778WA3252_AFD_0103_1_SI.almUnderRange.UnShelve401114.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: Unshelve Alarm Command to AE Server
779WA3252_AFD_0103_1_SI.almUnderRange.UnSuppress401114.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm DDT: UnSuppress Alarm Command to AE Server
780WA3252_AFD_0103_1_SI.ALRM401001.05Boolean1R/W1000RWPS AFD Pump 1 Speed : At Least One Alarm is Active
781WA3252_AFD_0103_1_SI.ANUN401001.06Boolean1R/W1000RWPS AFD Pump 1 Speed : At Least One Alarm is Annunciating
782WA3252_AFD_0103_1_SI.BL_Alarm401001.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Alarm
783WA3252_AFD_0103_1_SI.BL_Fault401001.13Boolean1R/W1000RWPS AFD Pump 1 Speed : Broken Loop Fault
784WA3252_AFD_0103_1_SI.BLEN401000.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Broken Loop Alarm
785WA3252_AFD_0103_1_SI.ConfigError401000.11Boolean1R/W1000RWPS AFD Pump 1 Speed : RawMin = RawMax: Causes division by zero
786WA3252_AFD_0103_1_SI.GlobalReset401000.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Reset all Alarms On this PLC
787WA3252_AFD_0103_1_SI.H_Alarm401000.13Boolean1R/W1000RWPS AFD Pump 1 Speed : High Alarm
788WA3252_AFD_0103_1_SI.H_EN401000.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable High Alarm
789WA3252_AFD_0103_1_SI.H_Fault401001.10Boolean1R/W1000RWPS AFD Pump 1 Speed : High Fault
790WA3252_AFD_0103_1_SI.HH_Alarm401000.12Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Alarm
791WA3252_AFD_0103_1_SI.HH_EN401000.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable High High Alarm
792WA3252_AFD_0103_1_SI.HH_Fault401001.09Boolean1R/W1000RWPS AFD Pump 1 Speed : High High Fault
793WA3252_AFD_0103_1_SI.INTK401002.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Locked by program (ESD)
794WA3252_AFD_0103_1_SI.INTK_EN401002.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Interlock Alarm
795WA3252_AFD_0103_1_SI.L_Alarm401000.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Alarm
796WA3252_AFD_0103_1_SI.L_EN401000.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Low Alarm
797WA3252_AFD_0103_1_SI.L_Fault401001.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Fault
798WA3252_AFD_0103_1_SI.LL_Alarm401000.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Alarm
799WA3252_AFD_0103_1_SI.LL_EN401000.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Low Low Alarm
800WA3252_AFD_0103_1_SI.LL_Fault401001.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Low Low Fault
801WA3252_AFD_0103_1_SI.OR_Alarm401001.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Alarm
802WA3252_AFD_0103_1_SI.OR_EN401000.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Over Range Alarm
803WA3252_AFD_0103_1_SI.OR_Fault401001.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Over Range Fault
804WA3252_AFD_0103_1_SI.PCSuppress401002.12Boolean1R/W1000RWPS AFD Pump 1 Speed : Suppress Alarm from Program Control
805WA3252_AFD_0103_1_SI.PCUnshelve401002.14Boolean1R/W1000RWPS AFD Pump 1 Speed : Unshelve Alarm from Program Control
806WA3252_AFD_0103_1_SI.PCUnSuppress401002.13Boolean1R/W1000RWPS AFD Pump 1 Speed : UnSuppress Alarm from Program Control
807WA3252_AFD_0103_1_SI.PLCFault401002.05Boolean1R/W1000RWPS AFD Pump 1 Speed : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
808WA3252_AFD_0103_1_SI.PLCIOFault401002.06Boolean1R/W1000RWPS AFD Pump 1 Speed : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
809WA3252_AFD_0103_1_SI.RC_EN401000.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Rate of Change Alarm
810WA3252_AFD_0103_1_SI.Resetable401001.08Boolean1R/W1000RWPS AFD Pump 1 Speed : At least one alarm is latched and all latched alarms are resetable
811WA3252_AFD_0103_1_SI.REST401001.04Boolean1R/W1000RWPS AFD Pump 1 Speed : Reset all Alarms in this DFB
812WA3252_AFD_0103_1_SI.ROC_Alarm401001.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate of Change Alarm
813WA3252_AFD_0103_1_SI.ROC_Fault401002.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Rate of Change Fault
814WA3252_AFD_0103_1_SI.Shelve401002.08Boolean1R/W1000RWPS AFD Pump 1 Speed : Shelve Command from HMI
815WA3252_AFD_0103_1_SI.Shelved401002.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Shelved Status
816WA3252_AFD_0103_1_SI.Suppress401002.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Suppress Command from HMI
817WA3252_AFD_0103_1_SI.SuppressAA401000.09Boolean1R/W1000RWPS AFD Pump 1 Speed : Suppress All Alarms
818WA3252_AFD_0103_1_SI.Suppressed401002.11Boolean1R/W1000RWPS AFD Pump 1 Speed : Suppressed Status
819WA3252_AFD_0103_1_SI.SuppressLA401000.10Boolean1R/W1000RWPS AFD Pump 1 Speed : Suppress Level Alarms (LL, L, H, HH, & ROC)
820WA3252_AFD_0103_1_SI.TAGR401002.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Tagged Out of Service
821WA3252_AFD_0103_1_SI.Tot_EN401002.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Set true to totalize flow.
822WA3252_AFD_0103_1_SI.Totalize.EnableTot401148.01Boolean1R/W1000RWPS AFD Pump 1 Speed : Totalizer DDT: Start Totalizing becasue flow is above the minimum
823WA3252_AFD_0103_1_SI.Totalize.First_Scan401148.00Boolean1R/W1000RWPS AFD Pump 1 Speed : Totalizer DDT: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:
824WA3252_AFD_0103_1_SI.Totalize.REST401148.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Totalizer DDT: HMI Command to Reset Flow Totals
825WA3252_AFD_0103_1_SI.Totalize.RollDay401148.03Boolean1R/W1000RWPS AFD Pump 1 Speed : Totalizer DDT:
826WA3252_AFD_0103_1_SI.UR_Alarm401001.02Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Alarm
827WA3252_AFD_0103_1_SI.UR_Fault401001.15Boolean1R/W1000RWPS AFD Pump 1 Speed : Under Range Fault
828WA3252_AFD_0103_1_SI.UREN401000.07Boolean1R/W1000RWPS AFD Pump 1 Speed : Enable Under Range Alarm
829WA3252_AFD_0103_1_UA.ACKN419240.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : Acknowledge Alarm
830WA3252_AFD_0103_1_UA.AKED419240.11Boolean1R/W1000RWPS Pump 1 MPR Alarm : At Least One Alarm is Acknowledged
831WA3252_AFD_0103_1_UA.Alarm.Ack419248.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
832WA3252_AFD_0103_1_UA.Alarm.Acked419248.11Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
833WA3252_AFD_0103_1_UA.Alarm.ACKN419246.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Acknowledge Command
834WA3252_AFD_0103_1_UA.Alarm.AEShelveTMRDN419247.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
835WA3252_AFD_0103_1_UA.Alarm.AKED419246.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
836WA3252_AFD_0103_1_UA.Alarm.Alarm419248.12Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm Command to AE Server
837WA3252_AFD_0103_1_UA.Alarm.AlarmState419246.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
838WA3252_AFD_0103_1_UA.Alarm.ALRM419246.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
839WA3252_AFD_0103_1_UA.Alarm.ANUN419246.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
840WA3252_AFD_0103_1_UA.Alarm.Bad419247.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
841WA3252_AFD_0103_1_UA.Alarm.Disable419248.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
842WA3252_AFD_0103_1_UA.Alarm.Disabled419248.10Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
843WA3252_AFD_0103_1_UA.Alarm.Enable419248.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
844WA3252_AFD_0103_1_UA.Alarm.Fault419246.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
845WA3252_AFD_0103_1_UA.Alarm.FaultInAlarm419246.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
846WA3252_AFD_0103_1_UA.Alarm.GlobalReset419246.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
847WA3252_AFD_0103_1_UA.Alarm.MCmd_Disable419246.12Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
848WA3252_AFD_0103_1_UA.Alarm.MCmd_Enable419246.11Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
849WA3252_AFD_0103_1_UA.Alarm.OCmd_Shelve419246.13Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
850WA3252_AFD_0103_1_UA.Alarm.OCmd_Unshelve419246.14Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
851WA3252_AFD_0103_1_UA.Alarm.Reset419248.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Reset Command to AE Server
852WA3252_AFD_0103_1_UA.Alarm.Resetable419246.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
853WA3252_AFD_0103_1_UA.Alarm.REST419246.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Reset this alarm only
854WA3252_AFD_0103_1_UA.Alarm.SCmd_Suppress419246.15Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
855WA3252_AFD_0103_1_UA.Alarm.SCmd_UnSuppress419247.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
856WA3252_AFD_0103_1_UA.Alarm.Shelve419248.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
857WA3252_AFD_0103_1_UA.Alarm.Shelved419248.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
858WA3252_AFD_0103_1_UA.Alarm.Suppress419248.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
859WA3252_AFD_0103_1_UA.Alarm.Suppressed419248.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
860WA3252_AFD_0103_1_UA.Alarm.UACK419246.10Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Remove the Acknowledge Status
861WA3252_AFD_0103_1_UA.Alarm.UnShelve419248.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
862WA3252_AFD_0103_1_UA.Alarm.UnSuppress419248.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
863WA3252_AFD_0103_1_UA.Alarm_EN419240.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : 0 = enable alarm
864WA3252_AFD_0103_1_UA.Alarm_Fault419241.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : Alarm is in fault
865WA3252_AFD_0103_1_UA.AlarmState419240.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : Input value signifying alarm
866WA3252_AFD_0103_1_UA.almPLCFault.Ack419260.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Acknowlege Command to AE Server
867WA3252_AFD_0103_1_UA.almPLCFault.Acked419260.11Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
868WA3252_AFD_0103_1_UA.almPLCFault.ACKN419258.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Acknowledge Command
869WA3252_AFD_0103_1_UA.almPLCFault.AEShelveTMRDN419259.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
870WA3252_AFD_0103_1_UA.almPLCFault.AKED419258.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
871WA3252_AFD_0103_1_UA.almPLCFault.Alarm419260.12Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm Command to AE Server
872WA3252_AFD_0103_1_UA.almPLCFault.AlarmState419258.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
873WA3252_AFD_0103_1_UA.almPLCFault.ALRM419258.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
874WA3252_AFD_0103_1_UA.almPLCFault.ANUN419258.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
875WA3252_AFD_0103_1_UA.almPLCFault.Bad419259.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
876WA3252_AFD_0103_1_UA.almPLCFault.Disable419260.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
877WA3252_AFD_0103_1_UA.almPLCFault.Disabled419260.10Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
878WA3252_AFD_0103_1_UA.almPLCFault.Enable419260.04Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
879WA3252_AFD_0103_1_UA.almPLCFault.Fault419258.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
880WA3252_AFD_0103_1_UA.almPLCFault.FaultInAlarm419258.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
881WA3252_AFD_0103_1_UA.almPLCFault.GlobalReset419258.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
882WA3252_AFD_0103_1_UA.almPLCFault.MCmd_Disable419258.12Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
883WA3252_AFD_0103_1_UA.almPLCFault.MCmd_Enable419258.11Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
884WA3252_AFD_0103_1_UA.almPLCFault.OCmd_Shelve419258.13Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
885WA3252_AFD_0103_1_UA.almPLCFault.OCmd_Unshelve419258.14Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
886WA3252_AFD_0103_1_UA.almPLCFault.Reset419260.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Reset Command to AE Server
887WA3252_AFD_0103_1_UA.almPLCFault.Resetable419258.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
888WA3252_AFD_0103_1_UA.almPLCFault.REST419258.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Reset this alarm only
889WA3252_AFD_0103_1_UA.almPLCFault.SCmd_Suppress419258.15Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
890WA3252_AFD_0103_1_UA.almPLCFault.SCmd_UnSuppress419259.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
891WA3252_AFD_0103_1_UA.almPLCFault.Shelve419260.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
892WA3252_AFD_0103_1_UA.almPLCFault.Shelved419260.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
893WA3252_AFD_0103_1_UA.almPLCFault.Suppress419260.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
894WA3252_AFD_0103_1_UA.almPLCFault.Suppressed419260.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
895WA3252_AFD_0103_1_UA.almPLCFault.UACK419258.10Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Remove the Acknowledge Status
896WA3252_AFD_0103_1_UA.almPLCFault.UnShelve419260.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
897WA3252_AFD_0103_1_UA.almPLCFault.UnSuppress419260.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
898WA3252_AFD_0103_1_UA.ALRM419240.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : At Least One Alarm is Active
899WA3252_AFD_0103_1_UA.ANUN419240.10Boolean1R/W1000RWPS Pump 1 MPR Alarm : At Least One Alarm is Annunciating
900WA3252_AFD_0103_1_UA.Fault419240.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : Input tag to monitor for alarm
901WA3252_AFD_0103_1_UA.Faulted419240.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : Input is in fault
902WA3252_AFD_0103_1_UA.FaultInAlarm419240.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : Fault Is In Alarm (on longer than the delay)
903WA3252_AFD_0103_1_UA.GlobalReset419241.00Boolean1R/W1000RWPS Pump 1 MPR Alarm : Reset all Alarms On this PLC
904WA3252_AFD_0103_1_UA.InputAlarm419240.15Boolean1R/W1000RWPS Pump 1 MPR Alarm :
905WA3252_AFD_0103_1_UA.MCmd_Disable419240.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : Maintenance Command to Disable Alarm
906WA3252_AFD_0103_1_UA.MCmd_Enable419240.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : Maintenance Command to Enable Alarm
907WA3252_AFD_0103_1_UA.PCSuppress419241.01Boolean1R/W1000RWPS Pump 1 MPR Alarm : Suppress Alarm from Program Control
908WA3252_AFD_0103_1_UA.PCUnshelve419241.03Boolean1R/W1000RWPS Pump 1 MPR Alarm : Unshelve Alarm from Program Control
909WA3252_AFD_0103_1_UA.PCUnSuppress419241.02Boolean1R/W1000RWPS Pump 1 MPR Alarm : UnSuppress Alarm from Program Control
910WA3252_AFD_0103_1_UA.PLCF419241.08Boolean1R/W1000RWPS Pump 1 MPR Alarm : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
911WA3252_AFD_0103_1_UA.PLCIOFault419241.07Boolean1R/W1000RWPS Pump 1 MPR Alarm : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
912WA3252_AFD_0103_1_UA.Resetable419240.12Boolean1R/W1000RWPS Pump 1 MPR Alarm : At least one alarm is latched and all latched alarms are resetable
913WA3252_AFD_0103_1_UA.REST419240.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : Reset Alarm
914WA3252_AFD_0103_1_UA.Shelve419240.13Boolean1R/W1000RWPS Pump 1 MPR Alarm : Shelve Command from HMI
915WA3252_AFD_0103_1_UA.Shelved419241.05Boolean1R/W1000RWPS Pump 1 MPR Alarm : Shelved Status
916WA3252_AFD_0103_1_UA.Suppress419240.14Boolean1R/W1000RWPS Pump 1 MPR Alarm : Suppress Command from HMI
917WA3252_AFD_0103_1_UA.Suppressed419241.06Boolean1R/W1000RWPS Pump 1 MPR Alarm : Suppressed Status
918WA3252_AFD_0103_1_UA.TAGR419241.09Boolean1R/W1000RWPS Pump 1 MPR Alarm : Tagged Out of Service
919WA3252_AFD_0103_1_UH.ACKN419360.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Acknowledge Alarm
920WA3252_AFD_0103_1_UH.AKED419360.11Boolean1R/W1000RWPS Pump 1 High Rtd Temp : At Least One Alarm is Acknowledged
921WA3252_AFD_0103_1_UH.Alarm.Ack419368.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
922WA3252_AFD_0103_1_UH.Alarm.Acked419368.11Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
923WA3252_AFD_0103_1_UH.Alarm.ACKN419366.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Acknowledge Command
924WA3252_AFD_0103_1_UH.Alarm.AEShelveTMRDN419367.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
925WA3252_AFD_0103_1_UH.Alarm.AKED419366.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
926WA3252_AFD_0103_1_UH.Alarm.Alarm419368.12Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Command to AE Server
927WA3252_AFD_0103_1_UH.Alarm.AlarmState419366.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
928WA3252_AFD_0103_1_UH.Alarm.ALRM419366.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
929WA3252_AFD_0103_1_UH.Alarm.ANUN419366.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
930WA3252_AFD_0103_1_UH.Alarm.Bad419367.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
931WA3252_AFD_0103_1_UH.Alarm.Disable419368.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
932WA3252_AFD_0103_1_UH.Alarm.Disabled419368.10Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
933WA3252_AFD_0103_1_UH.Alarm.Enable419368.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
934WA3252_AFD_0103_1_UH.Alarm.Fault419366.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
935WA3252_AFD_0103_1_UH.Alarm.FaultInAlarm419366.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
936WA3252_AFD_0103_1_UH.Alarm.GlobalReset419366.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
937WA3252_AFD_0103_1_UH.Alarm.MCmd_Disable419366.12Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
938WA3252_AFD_0103_1_UH.Alarm.MCmd_Enable419366.11Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
939WA3252_AFD_0103_1_UH.Alarm.OCmd_Shelve419366.13Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
940WA3252_AFD_0103_1_UH.Alarm.OCmd_Unshelve419366.14Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
941WA3252_AFD_0103_1_UH.Alarm.Reset419368.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Reset Command to AE Server
942WA3252_AFD_0103_1_UH.Alarm.Resetable419366.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
943WA3252_AFD_0103_1_UH.Alarm.REST419366.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Reset this alarm only
944WA3252_AFD_0103_1_UH.Alarm.SCmd_Suppress419366.15Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
945WA3252_AFD_0103_1_UH.Alarm.SCmd_UnSuppress419367.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
946WA3252_AFD_0103_1_UH.Alarm.Shelve419368.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
947WA3252_AFD_0103_1_UH.Alarm.Shelved419368.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
948WA3252_AFD_0103_1_UH.Alarm.Suppress419368.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
949WA3252_AFD_0103_1_UH.Alarm.Suppressed419368.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
950WA3252_AFD_0103_1_UH.Alarm.UACK419366.10Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Remove the Acknowledge Status
951WA3252_AFD_0103_1_UH.Alarm.UnShelve419368.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
952WA3252_AFD_0103_1_UH.Alarm.UnSuppress419368.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
953WA3252_AFD_0103_1_UH.Alarm_EN419360.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : 0 = enable alarm
954WA3252_AFD_0103_1_UH.Alarm_Fault419361.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Alarm is in fault
955WA3252_AFD_0103_1_UH.AlarmState419360.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Input value signifying alarm
956WA3252_AFD_0103_1_UH.almPLCFault.Ack419380.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Acknowlege Command to AE Server
957WA3252_AFD_0103_1_UH.almPLCFault.Acked419380.11Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
958WA3252_AFD_0103_1_UH.almPLCFault.ACKN419378.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Acknowledge Command
959WA3252_AFD_0103_1_UH.almPLCFault.AEShelveTMRDN419379.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
960WA3252_AFD_0103_1_UH.almPLCFault.AKED419378.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
961WA3252_AFD_0103_1_UH.almPLCFault.Alarm419380.12Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm Command to AE Server
962WA3252_AFD_0103_1_UH.almPLCFault.AlarmState419378.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
963WA3252_AFD_0103_1_UH.almPLCFault.ALRM419378.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
964WA3252_AFD_0103_1_UH.almPLCFault.ANUN419378.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
965WA3252_AFD_0103_1_UH.almPLCFault.Bad419379.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
966WA3252_AFD_0103_1_UH.almPLCFault.Disable419380.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
967WA3252_AFD_0103_1_UH.almPLCFault.Disabled419380.10Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
968WA3252_AFD_0103_1_UH.almPLCFault.Enable419380.04Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
969WA3252_AFD_0103_1_UH.almPLCFault.Fault419378.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
970WA3252_AFD_0103_1_UH.almPLCFault.FaultInAlarm419378.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
971WA3252_AFD_0103_1_UH.almPLCFault.GlobalReset419378.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
972WA3252_AFD_0103_1_UH.almPLCFault.MCmd_Disable419378.12Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
973WA3252_AFD_0103_1_UH.almPLCFault.MCmd_Enable419378.11Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
974WA3252_AFD_0103_1_UH.almPLCFault.OCmd_Shelve419378.13Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
975WA3252_AFD_0103_1_UH.almPLCFault.OCmd_Unshelve419378.14Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
976WA3252_AFD_0103_1_UH.almPLCFault.Reset419380.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Reset Command to AE Server
977WA3252_AFD_0103_1_UH.almPLCFault.Resetable419378.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
978WA3252_AFD_0103_1_UH.almPLCFault.REST419378.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Reset this alarm only
979WA3252_AFD_0103_1_UH.almPLCFault.SCmd_Suppress419378.15Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
980WA3252_AFD_0103_1_UH.almPLCFault.SCmd_UnSuppress419379.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
981WA3252_AFD_0103_1_UH.almPLCFault.Shelve419380.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
982WA3252_AFD_0103_1_UH.almPLCFault.Shelved419380.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
983WA3252_AFD_0103_1_UH.almPLCFault.Suppress419380.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
984WA3252_AFD_0103_1_UH.almPLCFault.Suppressed419380.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
985WA3252_AFD_0103_1_UH.almPLCFault.UACK419378.10Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Remove the Acknowledge Status
986WA3252_AFD_0103_1_UH.almPLCFault.UnShelve419380.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
987WA3252_AFD_0103_1_UH.almPLCFault.UnSuppress419380.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
988WA3252_AFD_0103_1_UH.ALRM419360.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : At Least One Alarm is Active
989WA3252_AFD_0103_1_UH.ANUN419360.10Boolean1R/W1000RWPS Pump 1 High Rtd Temp : At Least One Alarm is Annunciating
990WA3252_AFD_0103_1_UH.Fault419360.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Input tag to monitor for alarm
991WA3252_AFD_0103_1_UH.Faulted419360.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Input is in fault
992WA3252_AFD_0103_1_UH.FaultInAlarm419360.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Fault Is In Alarm (on longer than the delay)
993WA3252_AFD_0103_1_UH.GlobalReset419361.00Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Reset all Alarms On this PLC
994WA3252_AFD_0103_1_UH.InputAlarm419360.15Boolean1R/W1000RWPS Pump 1 High Rtd Temp :
995WA3252_AFD_0103_1_UH.MCmd_Disable419360.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Maintenance Command to Disable Alarm
996WA3252_AFD_0103_1_UH.MCmd_Enable419360.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Maintenance Command to Enable Alarm
997WA3252_AFD_0103_1_UH.PCSuppress419361.01Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Suppress Alarm from Program Control
998WA3252_AFD_0103_1_UH.PCUnshelve419361.03Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Unshelve Alarm from Program Control
999WA3252_AFD_0103_1_UH.PCUnSuppress419361.02Boolean1R/W1000RWPS Pump 1 High Rtd Temp : UnSuppress Alarm from Program Control
1000WA3252_AFD_0103_1_UH.PLCF419361.08Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1001WA3252_AFD_0103_1_UH.PLCIOFault419361.07Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1002WA3252_AFD_0103_1_UH.Resetable419360.12Boolean1R/W1000RWPS Pump 1 High Rtd Temp : At least one alarm is latched and all latched alarms are resetable
1003WA3252_AFD_0103_1_UH.REST419360.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Reset Alarm
1004WA3252_AFD_0103_1_UH.Shelve419360.13Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Shelve Command from HMI
1005WA3252_AFD_0103_1_UH.Shelved419361.05Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Shelved Status
1006WA3252_AFD_0103_1_UH.Suppress419360.14Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Suppress Command from HMI
1007WA3252_AFD_0103_1_UH.Suppressed419361.06Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Suppressed Status
1008WA3252_AFD_0103_1_UH.TAGR419361.09Boolean1R/W1000RWPS Pump 1 High Rtd Temp : Tagged Out of Service
1009WA3252_AFD_0103_1_UY.ACKN419480.06Boolean1R/W1000RWPS Pump 1 MPR Trip : Acknowledge Alarm
1010WA3252_AFD_0103_1_UY.AKED419480.11Boolean1R/W1000RWPS Pump 1 MPR Trip : At Least One Alarm is Acknowledged
1011WA3252_AFD_0103_1_UY.Alarm.Ack419488.06Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1012WA3252_AFD_0103_1_UY.Alarm.Acked419488.11Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1013WA3252_AFD_0103_1_UY.Alarm.ACKN419486.09Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Acknowledge Command
1014WA3252_AFD_0103_1_UY.Alarm.AEShelveTMRDN419487.01Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1015WA3252_AFD_0103_1_UY.Alarm.AKED419486.06Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1016WA3252_AFD_0103_1_UY.Alarm.Alarm419488.12Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm Command to AE Server
1017WA3252_AFD_0103_1_UY.Alarm.AlarmState419486.01Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1018WA3252_AFD_0103_1_UY.Alarm.ALRM419486.04Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1019WA3252_AFD_0103_1_UY.Alarm.ANUN419486.05Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1020WA3252_AFD_0103_1_UY.Alarm.Bad419487.02Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1021WA3252_AFD_0103_1_UY.Alarm.Disable419488.05Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1022WA3252_AFD_0103_1_UY.Alarm.Disabled419488.10Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1023WA3252_AFD_0103_1_UY.Alarm.Enable419488.04Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1024WA3252_AFD_0103_1_UY.Alarm.Fault419486.00Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1025WA3252_AFD_0103_1_UY.Alarm.FaultInAlarm419486.03Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1026WA3252_AFD_0103_1_UY.Alarm.GlobalReset419486.02Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1027WA3252_AFD_0103_1_UY.Alarm.MCmd_Disable419486.12Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1028WA3252_AFD_0103_1_UY.Alarm.MCmd_Enable419486.11Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1029WA3252_AFD_0103_1_UY.Alarm.OCmd_Shelve419486.13Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1030WA3252_AFD_0103_1_UY.Alarm.OCmd_Unshelve419486.14Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1031WA3252_AFD_0103_1_UY.Alarm.Reset419488.07Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Reset Command to AE Server
1032WA3252_AFD_0103_1_UY.Alarm.Resetable419486.07Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1033WA3252_AFD_0103_1_UY.Alarm.REST419486.08Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Reset this alarm only
1034WA3252_AFD_0103_1_UY.Alarm.SCmd_Suppress419486.15Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1035WA3252_AFD_0103_1_UY.Alarm.SCmd_UnSuppress419487.00Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1036WA3252_AFD_0103_1_UY.Alarm.Shelve419488.02Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1037WA3252_AFD_0103_1_UY.Alarm.Shelved419488.09Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1038WA3252_AFD_0103_1_UY.Alarm.Suppress419488.00Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1039WA3252_AFD_0103_1_UY.Alarm.Suppressed419488.08Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1040WA3252_AFD_0103_1_UY.Alarm.UACK419486.10Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Remove the Acknowledge Status
1041WA3252_AFD_0103_1_UY.Alarm.UnShelve419488.03Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1042WA3252_AFD_0103_1_UY.Alarm.UnSuppress419488.01Boolean1R/W1000RWPS Pump 1 MPR Trip : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1043WA3252_AFD_0103_1_UY.Alarm_EN419480.04Boolean1R/W1000RWPS Pump 1 MPR Trip : 0 = enable alarm
1044WA3252_AFD_0103_1_UY.Alarm_Fault419481.04Boolean1R/W1000RWPS Pump 1 MPR Trip : Alarm is in fault
1045WA3252_AFD_0103_1_UY.AlarmState419480.02Boolean1R/W1000RWPS Pump 1 MPR Trip : Input value signifying alarm
1046WA3252_AFD_0103_1_UY.almPLCFault.Ack419500.06Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Acknowlege Command to AE Server
1047WA3252_AFD_0103_1_UY.almPLCFault.Acked419500.11Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1048WA3252_AFD_0103_1_UY.almPLCFault.ACKN419498.09Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Acknowledge Command
1049WA3252_AFD_0103_1_UY.almPLCFault.AEShelveTMRDN419499.01Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1050WA3252_AFD_0103_1_UY.almPLCFault.AKED419498.06Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1051WA3252_AFD_0103_1_UY.almPLCFault.Alarm419500.12Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm Command to AE Server
1052WA3252_AFD_0103_1_UY.almPLCFault.AlarmState419498.01Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1053WA3252_AFD_0103_1_UY.almPLCFault.ALRM419498.04Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1054WA3252_AFD_0103_1_UY.almPLCFault.ANUN419498.05Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1055WA3252_AFD_0103_1_UY.almPLCFault.Bad419499.02Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1056WA3252_AFD_0103_1_UY.almPLCFault.Disable419500.05Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1057WA3252_AFD_0103_1_UY.almPLCFault.Disabled419500.10Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1058WA3252_AFD_0103_1_UY.almPLCFault.Enable419500.04Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1059WA3252_AFD_0103_1_UY.almPLCFault.Fault419498.00Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1060WA3252_AFD_0103_1_UY.almPLCFault.FaultInAlarm419498.03Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1061WA3252_AFD_0103_1_UY.almPLCFault.GlobalReset419498.02Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1062WA3252_AFD_0103_1_UY.almPLCFault.MCmd_Disable419498.12Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1063WA3252_AFD_0103_1_UY.almPLCFault.MCmd_Enable419498.11Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1064WA3252_AFD_0103_1_UY.almPLCFault.OCmd_Shelve419498.13Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1065WA3252_AFD_0103_1_UY.almPLCFault.OCmd_Unshelve419498.14Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1066WA3252_AFD_0103_1_UY.almPLCFault.Reset419500.07Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Reset Command to AE Server
1067WA3252_AFD_0103_1_UY.almPLCFault.Resetable419498.07Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1068WA3252_AFD_0103_1_UY.almPLCFault.REST419498.08Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Reset this alarm only
1069WA3252_AFD_0103_1_UY.almPLCFault.SCmd_Suppress419498.15Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1070WA3252_AFD_0103_1_UY.almPLCFault.SCmd_UnSuppress419499.00Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1071WA3252_AFD_0103_1_UY.almPLCFault.Shelve419500.02Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1072WA3252_AFD_0103_1_UY.almPLCFault.Shelved419500.09Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1073WA3252_AFD_0103_1_UY.almPLCFault.Suppress419500.00Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1074WA3252_AFD_0103_1_UY.almPLCFault.Suppressed419500.08Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1075WA3252_AFD_0103_1_UY.almPLCFault.UACK419498.10Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Remove the Acknowledge Status
1076WA3252_AFD_0103_1_UY.almPLCFault.UnShelve419500.03Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1077WA3252_AFD_0103_1_UY.almPLCFault.UnSuppress419500.01Boolean1R/W1000RWPS Pump 1 MPR Trip : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1078WA3252_AFD_0103_1_UY.ALRM419480.09Boolean1R/W1000RWPS Pump 1 MPR Trip : At Least One Alarm is Active
1079WA3252_AFD_0103_1_UY.ANUN419480.10Boolean1R/W1000RWPS Pump 1 MPR Trip : At Least One Alarm is Annunciating
1080WA3252_AFD_0103_1_UY.Fault419480.00Boolean1R/W1000RWPS Pump 1 MPR Trip : Input tag to monitor for alarm
1081WA3252_AFD_0103_1_UY.Faulted419480.01Boolean1R/W1000RWPS Pump 1 MPR Trip : Input is in fault
1082WA3252_AFD_0103_1_UY.FaultInAlarm419480.03Boolean1R/W1000RWPS Pump 1 MPR Trip : Fault Is In Alarm (on longer than the delay)
1083WA3252_AFD_0103_1_UY.GlobalReset419481.00Boolean1R/W1000RWPS Pump 1 MPR Trip : Reset all Alarms On this PLC
1084WA3252_AFD_0103_1_UY.InputAlarm419480.15Boolean1R/W1000RWPS Pump 1 MPR Trip :
1085WA3252_AFD_0103_1_UY.MCmd_Disable419480.08Boolean1R/W1000RWPS Pump 1 MPR Trip : Maintenance Command to Disable Alarm
1086WA3252_AFD_0103_1_UY.MCmd_Enable419480.07Boolean1R/W1000RWPS Pump 1 MPR Trip : Maintenance Command to Enable Alarm
1087WA3252_AFD_0103_1_UY.PCSuppress419481.01Boolean1R/W1000RWPS Pump 1 MPR Trip : Suppress Alarm from Program Control
1088WA3252_AFD_0103_1_UY.PCUnshelve419481.03Boolean1R/W1000RWPS Pump 1 MPR Trip : Unshelve Alarm from Program Control
1089WA3252_AFD_0103_1_UY.PCUnSuppress419481.02Boolean1R/W1000RWPS Pump 1 MPR Trip : UnSuppress Alarm from Program Control
1090WA3252_AFD_0103_1_UY.PLCF419481.08Boolean1R/W1000RWPS Pump 1 MPR Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1091WA3252_AFD_0103_1_UY.PLCIOFault419481.07Boolean1R/W1000RWPS Pump 1 MPR Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1092WA3252_AFD_0103_1_UY.Resetable419480.12Boolean1R/W1000RWPS Pump 1 MPR Trip : At least one alarm is latched and all latched alarms are resetable
1093WA3252_AFD_0103_1_UY.REST419480.05Boolean1R/W1000RWPS Pump 1 MPR Trip : Reset Alarm
1094WA3252_AFD_0103_1_UY.Shelve419480.13Boolean1R/W1000RWPS Pump 1 MPR Trip : Shelve Command from HMI
1095WA3252_AFD_0103_1_UY.Shelved419481.05Boolean1R/W1000RWPS Pump 1 MPR Trip : Shelved Status
1096WA3252_AFD_0103_1_UY.Suppress419480.14Boolean1R/W1000RWPS Pump 1 MPR Trip : Suppress Command from HMI
1097WA3252_AFD_0103_1_UY.Suppressed419481.06Boolean1R/W1000RWPS Pump 1 MPR Trip : Suppressed Status
1098WA3252_AFD_0103_1_UY.TAGR419481.09Boolean1R/W1000RWPS Pump 1 MPR Trip : Tagged Out of Service
1099WA3252_AFD_0103_1_VA459013.13Boolean1R/W1000RWPS Pump 1 PFCC Online
1100WA3252_AFD_0103_1_XF.ACKN419600.06Boolean1R/W1000RWPS Pump 1 AFD Trip : Acknowledge Alarm
1101WA3252_AFD_0103_1_XF.AKED419600.11Boolean1R/W1000RWPS Pump 1 AFD Trip : At Least One Alarm is Acknowledged
1102WA3252_AFD_0103_1_XF.Alarm.Ack419608.06Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1103WA3252_AFD_0103_1_XF.Alarm.Acked419608.11Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1104WA3252_AFD_0103_1_XF.Alarm.ACKN419606.09Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Acknowledge Command
1105WA3252_AFD_0103_1_XF.Alarm.AEShelveTMRDN419607.01Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1106WA3252_AFD_0103_1_XF.Alarm.AKED419606.06Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1107WA3252_AFD_0103_1_XF.Alarm.Alarm419608.12Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm Command to AE Server
1108WA3252_AFD_0103_1_XF.Alarm.AlarmState419606.01Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1109WA3252_AFD_0103_1_XF.Alarm.ALRM419606.04Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1110WA3252_AFD_0103_1_XF.Alarm.ANUN419606.05Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1111WA3252_AFD_0103_1_XF.Alarm.Bad419607.02Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1112WA3252_AFD_0103_1_XF.Alarm.Disable419608.05Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1113WA3252_AFD_0103_1_XF.Alarm.Disabled419608.10Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1114WA3252_AFD_0103_1_XF.Alarm.Enable419608.04Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1115WA3252_AFD_0103_1_XF.Alarm.Fault419606.00Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1116WA3252_AFD_0103_1_XF.Alarm.FaultInAlarm419606.03Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1117WA3252_AFD_0103_1_XF.Alarm.GlobalReset419606.02Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1118WA3252_AFD_0103_1_XF.Alarm.MCmd_Disable419606.12Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1119WA3252_AFD_0103_1_XF.Alarm.MCmd_Enable419606.11Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1120WA3252_AFD_0103_1_XF.Alarm.OCmd_Shelve419606.13Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1121WA3252_AFD_0103_1_XF.Alarm.OCmd_Unshelve419606.14Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1122WA3252_AFD_0103_1_XF.Alarm.Reset419608.07Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Reset Command to AE Server
1123WA3252_AFD_0103_1_XF.Alarm.Resetable419606.07Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1124WA3252_AFD_0103_1_XF.Alarm.REST419606.08Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Reset this alarm only
1125WA3252_AFD_0103_1_XF.Alarm.SCmd_Suppress419606.15Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1126WA3252_AFD_0103_1_XF.Alarm.SCmd_UnSuppress419607.00Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1127WA3252_AFD_0103_1_XF.Alarm.Shelve419608.02Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1128WA3252_AFD_0103_1_XF.Alarm.Shelved419608.09Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1129WA3252_AFD_0103_1_XF.Alarm.Suppress419608.00Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1130WA3252_AFD_0103_1_XF.Alarm.Suppressed419608.08Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1131WA3252_AFD_0103_1_XF.Alarm.UACK419606.10Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Remove the Acknowledge Status
1132WA3252_AFD_0103_1_XF.Alarm.UnShelve419608.03Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1133WA3252_AFD_0103_1_XF.Alarm.UnSuppress419608.01Boolean1R/W1000RWPS Pump 1 AFD Trip : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1134WA3252_AFD_0103_1_XF.Alarm_EN419600.04Boolean1R/W1000RWPS Pump 1 AFD Trip : 0 = enable alarm
1135WA3252_AFD_0103_1_XF.Alarm_Fault419601.04Boolean1R/W1000RWPS Pump 1 AFD Trip : Alarm is in fault
1136WA3252_AFD_0103_1_XF.AlarmState419600.02Boolean1R/W1000RWPS Pump 1 AFD Trip : Input value signifying alarm
1137WA3252_AFD_0103_1_XF.almPLCFault.Ack419620.06Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Acknowlege Command to AE Server
1138WA3252_AFD_0103_1_XF.almPLCFault.Acked419620.11Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1139WA3252_AFD_0103_1_XF.almPLCFault.ACKN419618.09Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Acknowledge Command
1140WA3252_AFD_0103_1_XF.almPLCFault.AEShelveTMRDN419619.01Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1141WA3252_AFD_0103_1_XF.almPLCFault.AKED419618.06Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1142WA3252_AFD_0103_1_XF.almPLCFault.Alarm419620.12Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm Command to AE Server
1143WA3252_AFD_0103_1_XF.almPLCFault.AlarmState419618.01Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1144WA3252_AFD_0103_1_XF.almPLCFault.ALRM419618.04Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1145WA3252_AFD_0103_1_XF.almPLCFault.ANUN419618.05Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1146WA3252_AFD_0103_1_XF.almPLCFault.Bad419619.02Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1147WA3252_AFD_0103_1_XF.almPLCFault.Disable419620.05Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1148WA3252_AFD_0103_1_XF.almPLCFault.Disabled419620.10Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1149WA3252_AFD_0103_1_XF.almPLCFault.Enable419620.04Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1150WA3252_AFD_0103_1_XF.almPLCFault.Fault419618.00Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1151WA3252_AFD_0103_1_XF.almPLCFault.FaultInAlarm419618.03Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1152WA3252_AFD_0103_1_XF.almPLCFault.GlobalReset419618.02Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1153WA3252_AFD_0103_1_XF.almPLCFault.MCmd_Disable419618.12Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1154WA3252_AFD_0103_1_XF.almPLCFault.MCmd_Enable419618.11Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1155WA3252_AFD_0103_1_XF.almPLCFault.OCmd_Shelve419618.13Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1156WA3252_AFD_0103_1_XF.almPLCFault.OCmd_Unshelve419618.14Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1157WA3252_AFD_0103_1_XF.almPLCFault.Reset419620.07Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Reset Command to AE Server
1158WA3252_AFD_0103_1_XF.almPLCFault.Resetable419618.07Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1159WA3252_AFD_0103_1_XF.almPLCFault.REST419618.08Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Reset this alarm only
1160WA3252_AFD_0103_1_XF.almPLCFault.SCmd_Suppress419618.15Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1161WA3252_AFD_0103_1_XF.almPLCFault.SCmd_UnSuppress419619.00Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1162WA3252_AFD_0103_1_XF.almPLCFault.Shelve419620.02Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1163WA3252_AFD_0103_1_XF.almPLCFault.Shelved419620.09Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1164WA3252_AFD_0103_1_XF.almPLCFault.Suppress419620.00Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1165WA3252_AFD_0103_1_XF.almPLCFault.Suppressed419620.08Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1166WA3252_AFD_0103_1_XF.almPLCFault.UACK419618.10Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Remove the Acknowledge Status
1167WA3252_AFD_0103_1_XF.almPLCFault.UnShelve419620.03Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1168WA3252_AFD_0103_1_XF.almPLCFault.UnSuppress419620.01Boolean1R/W1000RWPS Pump 1 AFD Trip : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1169WA3252_AFD_0103_1_XF.ALRM419600.09Boolean1R/W1000RWPS Pump 1 AFD Trip : At Least One Alarm is Active
1170WA3252_AFD_0103_1_XF.ANUN419600.10Boolean1R/W1000RWPS Pump 1 AFD Trip : At Least One Alarm is Annunciating
1171WA3252_AFD_0103_1_XF.Fault419600.00Boolean1R/W1000RWPS Pump 1 AFD Trip : Input tag to monitor for alarm
1172WA3252_AFD_0103_1_XF.Faulted419600.01Boolean1R/W1000RWPS Pump 1 AFD Trip : Input is in fault
1173WA3252_AFD_0103_1_XF.FaultInAlarm419600.03Boolean1R/W1000RWPS Pump 1 AFD Trip : Fault Is In Alarm (on longer than the delay)
1174WA3252_AFD_0103_1_XF.GlobalReset419601.00Boolean1R/W1000RWPS Pump 1 AFD Trip : Reset all Alarms On this PLC
1175WA3252_AFD_0103_1_XF.InputAlarm419600.15Boolean1R/W1000RWPS Pump 1 AFD Trip :
1176WA3252_AFD_0103_1_XF.MCmd_Disable419600.08Boolean1R/W1000RWPS Pump 1 AFD Trip : Maintenance Command to Disable Alarm
1177WA3252_AFD_0103_1_XF.MCmd_Enable419600.07Boolean1R/W1000RWPS Pump 1 AFD Trip : Maintenance Command to Enable Alarm
1178WA3252_AFD_0103_1_XF.PCSuppress419601.01Boolean1R/W1000RWPS Pump 1 AFD Trip : Suppress Alarm from Program Control
1179WA3252_AFD_0103_1_XF.PCUnshelve419601.03Boolean1R/W1000RWPS Pump 1 AFD Trip : Unshelve Alarm from Program Control
1180WA3252_AFD_0103_1_XF.PCUnSuppress419601.02Boolean1R/W1000RWPS Pump 1 AFD Trip : UnSuppress Alarm from Program Control
1181WA3252_AFD_0103_1_XF.PLCF419601.08Boolean1R/W1000RWPS Pump 1 AFD Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1182WA3252_AFD_0103_1_XF.PLCIOFault419601.07Boolean1R/W1000RWPS Pump 1 AFD Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1183WA3252_AFD_0103_1_XF.Resetable419600.12Boolean1R/W1000RWPS Pump 1 AFD Trip : At least one alarm is latched and all latched alarms are resetable
1184WA3252_AFD_0103_1_XF.REST419600.05Boolean1R/W1000RWPS Pump 1 AFD Trip : Reset Alarm
1185WA3252_AFD_0103_1_XF.Shelve419600.13Boolean1R/W1000RWPS Pump 1 AFD Trip : Shelve Command from HMI
1186WA3252_AFD_0103_1_XF.Shelved419601.05Boolean1R/W1000RWPS Pump 1 AFD Trip : Shelved Status
1187WA3252_AFD_0103_1_XF.Suppress419600.14Boolean1R/W1000RWPS Pump 1 AFD Trip : Suppress Command from HMI
1188WA3252_AFD_0103_1_XF.Suppressed419601.06Boolean1R/W1000RWPS Pump 1 AFD Trip : Suppressed Status
1189WA3252_AFD_0103_1_XF.TAGR419601.09Boolean1R/W1000RWPS Pump 1 AFD Trip : Tagged Out of Service
1190WA3252_AFD_0103_1_YA.ACKN419720.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Acknowledge Alarm
1191WA3252_AFD_0103_1_YA.AKED419720.11Boolean1R/W1000RWPS Pump 1 AFD E. Stop : At Least One Alarm is Acknowledged
1192WA3252_AFD_0103_1_YA.Alarm.Ack419728.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1193WA3252_AFD_0103_1_YA.Alarm.Acked419728.11Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1194WA3252_AFD_0103_1_YA.Alarm.ACKN419726.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Acknowledge Command
1195WA3252_AFD_0103_1_YA.Alarm.AEShelveTMRDN419727.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1196WA3252_AFD_0103_1_YA.Alarm.AKED419726.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1197WA3252_AFD_0103_1_YA.Alarm.Alarm419728.12Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Command to AE Server
1198WA3252_AFD_0103_1_YA.Alarm.AlarmState419726.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1199WA3252_AFD_0103_1_YA.Alarm.ALRM419726.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1200WA3252_AFD_0103_1_YA.Alarm.ANUN419726.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1201WA3252_AFD_0103_1_YA.Alarm.Bad419727.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1202WA3252_AFD_0103_1_YA.Alarm.Disable419728.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1203WA3252_AFD_0103_1_YA.Alarm.Disabled419728.10Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1204WA3252_AFD_0103_1_YA.Alarm.Enable419728.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1205WA3252_AFD_0103_1_YA.Alarm.Fault419726.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1206WA3252_AFD_0103_1_YA.Alarm.FaultInAlarm419726.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1207WA3252_AFD_0103_1_YA.Alarm.GlobalReset419726.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1208WA3252_AFD_0103_1_YA.Alarm.MCmd_Disable419726.12Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1209WA3252_AFD_0103_1_YA.Alarm.MCmd_Enable419726.11Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1210WA3252_AFD_0103_1_YA.Alarm.OCmd_Shelve419726.13Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1211WA3252_AFD_0103_1_YA.Alarm.OCmd_Unshelve419726.14Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1212WA3252_AFD_0103_1_YA.Alarm.Reset419728.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Reset Command to AE Server
1213WA3252_AFD_0103_1_YA.Alarm.Resetable419726.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1214WA3252_AFD_0103_1_YA.Alarm.REST419726.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Reset this alarm only
1215WA3252_AFD_0103_1_YA.Alarm.SCmd_Suppress419726.15Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1216WA3252_AFD_0103_1_YA.Alarm.SCmd_UnSuppress419727.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1217WA3252_AFD_0103_1_YA.Alarm.Shelve419728.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1218WA3252_AFD_0103_1_YA.Alarm.Shelved419728.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1219WA3252_AFD_0103_1_YA.Alarm.Suppress419728.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1220WA3252_AFD_0103_1_YA.Alarm.Suppressed419728.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1221WA3252_AFD_0103_1_YA.Alarm.UACK419726.10Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Remove the Acknowledge Status
1222WA3252_AFD_0103_1_YA.Alarm.UnShelve419728.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1223WA3252_AFD_0103_1_YA.Alarm.UnSuppress419728.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1224WA3252_AFD_0103_1_YA.Alarm_EN419720.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : 0 = enable alarm
1225WA3252_AFD_0103_1_YA.Alarm_Fault419721.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Alarm is in fault
1226WA3252_AFD_0103_1_YA.AlarmState419720.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Input value signifying alarm
1227WA3252_AFD_0103_1_YA.almPLCFault.Ack419740.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Acknowlege Command to AE Server
1228WA3252_AFD_0103_1_YA.almPLCFault.Acked419740.11Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1229WA3252_AFD_0103_1_YA.almPLCFault.ACKN419738.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Acknowledge Command
1230WA3252_AFD_0103_1_YA.almPLCFault.AEShelveTMRDN419739.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1231WA3252_AFD_0103_1_YA.almPLCFault.AKED419738.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1232WA3252_AFD_0103_1_YA.almPLCFault.Alarm419740.12Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm Command to AE Server
1233WA3252_AFD_0103_1_YA.almPLCFault.AlarmState419738.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1234WA3252_AFD_0103_1_YA.almPLCFault.ALRM419738.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1235WA3252_AFD_0103_1_YA.almPLCFault.ANUN419738.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1236WA3252_AFD_0103_1_YA.almPLCFault.Bad419739.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1237WA3252_AFD_0103_1_YA.almPLCFault.Disable419740.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1238WA3252_AFD_0103_1_YA.almPLCFault.Disabled419740.10Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1239WA3252_AFD_0103_1_YA.almPLCFault.Enable419740.04Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1240WA3252_AFD_0103_1_YA.almPLCFault.Fault419738.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1241WA3252_AFD_0103_1_YA.almPLCFault.FaultInAlarm419738.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1242WA3252_AFD_0103_1_YA.almPLCFault.GlobalReset419738.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1243WA3252_AFD_0103_1_YA.almPLCFault.MCmd_Disable419738.12Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1244WA3252_AFD_0103_1_YA.almPLCFault.MCmd_Enable419738.11Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1245WA3252_AFD_0103_1_YA.almPLCFault.OCmd_Shelve419738.13Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1246WA3252_AFD_0103_1_YA.almPLCFault.OCmd_Unshelve419738.14Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1247WA3252_AFD_0103_1_YA.almPLCFault.Reset419740.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Reset Command to AE Server
1248WA3252_AFD_0103_1_YA.almPLCFault.Resetable419738.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1249WA3252_AFD_0103_1_YA.almPLCFault.REST419738.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Reset this alarm only
1250WA3252_AFD_0103_1_YA.almPLCFault.SCmd_Suppress419738.15Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1251WA3252_AFD_0103_1_YA.almPLCFault.SCmd_UnSuppress419739.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1252WA3252_AFD_0103_1_YA.almPLCFault.Shelve419740.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1253WA3252_AFD_0103_1_YA.almPLCFault.Shelved419740.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1254WA3252_AFD_0103_1_YA.almPLCFault.Suppress419740.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1255WA3252_AFD_0103_1_YA.almPLCFault.Suppressed419740.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1256WA3252_AFD_0103_1_YA.almPLCFault.UACK419738.10Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Remove the Acknowledge Status
1257WA3252_AFD_0103_1_YA.almPLCFault.UnShelve419740.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1258WA3252_AFD_0103_1_YA.almPLCFault.UnSuppress419740.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1259WA3252_AFD_0103_1_YA.ALRM419720.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : At Least One Alarm is Active
1260WA3252_AFD_0103_1_YA.ANUN419720.10Boolean1R/W1000RWPS Pump 1 AFD E. Stop : At Least One Alarm is Annunciating
1261WA3252_AFD_0103_1_YA.Fault419720.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Input tag to monitor for alarm
1262WA3252_AFD_0103_1_YA.Faulted419720.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Input is in fault
1263WA3252_AFD_0103_1_YA.FaultInAlarm419720.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Fault Is In Alarm (on longer than the delay)
1264WA3252_AFD_0103_1_YA.GlobalReset419721.00Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Reset all Alarms On this PLC
1265WA3252_AFD_0103_1_YA.InputAlarm419720.15Boolean1R/W1000RWPS Pump 1 AFD E. Stop :
1266WA3252_AFD_0103_1_YA.MCmd_Disable419720.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Maintenance Command to Disable Alarm
1267WA3252_AFD_0103_1_YA.MCmd_Enable419720.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Maintenance Command to Enable Alarm
1268WA3252_AFD_0103_1_YA.PCSuppress419721.01Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Suppress Alarm from Program Control
1269WA3252_AFD_0103_1_YA.PCUnshelve419721.03Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Unshelve Alarm from Program Control
1270WA3252_AFD_0103_1_YA.PCUnSuppress419721.02Boolean1R/W1000RWPS Pump 1 AFD E. Stop : UnSuppress Alarm from Program Control
1271WA3252_AFD_0103_1_YA.PLCF419721.08Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1272WA3252_AFD_0103_1_YA.PLCIOFault419721.07Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1273WA3252_AFD_0103_1_YA.Resetable419720.12Boolean1R/W1000RWPS Pump 1 AFD E. Stop : At least one alarm is latched and all latched alarms are resetable
1274WA3252_AFD_0103_1_YA.REST419720.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Reset Alarm
1275WA3252_AFD_0103_1_YA.Shelve419720.13Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Shelve Command from HMI
1276WA3252_AFD_0103_1_YA.Shelved419721.05Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Shelved Status
1277WA3252_AFD_0103_1_YA.Suppress419720.14Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Suppress Command from HMI
1278WA3252_AFD_0103_1_YA.Suppressed419721.06Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Suppressed Status
1279WA3252_AFD_0103_1_YA.TAGR419721.09Boolean1R/W1000RWPS Pump 1 AFD E. Stop : Tagged Out of Service
1280WA3252_AFD_0103_1_YL1459013.00Boolean1R/W1000RWPS Pump 1 Bypass Mode Enabled
1281WA3252_AFD_0103_1_YL1_raw459013.00Boolean1R/W1000RWPS Pump 1 Bypass Mode Enabled
1282WA3252_AFD_0103_1_YL2459013.12Boolean1R/W1000RWPS Pump 1 Isolation Valve Bypass Mode
1283WA3252_AFD_0103_2.ACKN442574.06Boolean1R/W1000RWPS Pump 2: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB
1284WA3252_AFD_0103_2.AKED442575.10Boolean1R/W1000RWPS Pump 2: Acknowledged: At least one alarm has been acknowledged.
1285WA3252_AFD_0103_2.almFailToStop.Ack442638.06Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Acknowlege Command to AE Server
1286WA3252_AFD_0103_2.almFailToStop.Acked442638.11Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm Acknowledged Status from AE Server
1287WA3252_AFD_0103_2.almFailToStop.ACKN442636.09Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Acknowledge Command
1288WA3252_AFD_0103_2.almFailToStop.AEShelveTMRDN442637.01Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm and Events Shelve Timer Done
1289WA3252_AFD_0103_2.almFailToStop.AKED442636.06Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1290WA3252_AFD_0103_2.almFailToStop.Alarm442638.12Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm Command to AE Server
1291WA3252_AFD_0103_2.almFailToStop.AlarmState442636.01Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Value of the Fault input that indicates an alarm condition
1292WA3252_AFD_0103_2.almFailToStop.ALRM442636.04Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1293WA3252_AFD_0103_2.almFailToStop.ANUN442636.05Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1294WA3252_AFD_0103_2.almFailToStop.Bad442637.02Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1295WA3252_AFD_0103_2.almFailToStop.Disable442638.05Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Disable Alarm Command to AE Server
1296WA3252_AFD_0103_2.almFailToStop.Disabled442638.10Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm Disabled Status from AE Server
1297WA3252_AFD_0103_2.almFailToStop.Enable442638.04Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Enable Alarm Command to AE Server
1298WA3252_AFD_0103_2.almFailToStop.Fault442636.00Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Discrete input condition indicating a faulted state.
1299WA3252_AFD_0103_2.almFailToStop.FaultInAlarm442636.03Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Fault Is In Alarm (on longer than the delay)
1300WA3252_AFD_0103_2.almFailToStop.GlobalReset442636.02Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Used to reset all alarms in the PLC
1301WA3252_AFD_0103_2.almFailToStop.MCmd_Disable442636.12Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Maintenance Command to Disable Alarm
1302WA3252_AFD_0103_2.almFailToStop.MCmd_Enable442636.11Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Maintenance Command to Enable Alarm
1303WA3252_AFD_0103_2.almFailToStop.OCmd_Shelve442636.13Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Operator Command to Shelve Alarm
1304WA3252_AFD_0103_2.almFailToStop.OCmd_Unshelve442636.14Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Operator Command to UnShelve Alarm
1305WA3252_AFD_0103_2.almFailToStop.Reset442638.07Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Reset Command to AE Server
1306WA3252_AFD_0103_2.almFailToStop.Resetable442636.07Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1307WA3252_AFD_0103_2.almFailToStop.REST442636.08Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Reset this alarm only
1308WA3252_AFD_0103_2.almFailToStop.SCmd_Suppress442636.15Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Supervisor Command to Suppress Alarm
1309WA3252_AFD_0103_2.almFailToStop.SCmd_UnSuppress442637.00Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Supervisor Command to Unsuppress Alarm
1310WA3252_AFD_0103_2.almFailToStop.Shelve442638.02Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Shelve Alarm Command to AE Server
1311WA3252_AFD_0103_2.almFailToStop.Shelved442638.09Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm Shelved Status from AE Server
1312WA3252_AFD_0103_2.almFailToStop.Suppress442638.00Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Suppress Alarm Command to AE Server
1313WA3252_AFD_0103_2.almFailToStop.Suppressed442638.08Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Alarm Suppressed Status from AE Server
1314WA3252_AFD_0103_2.almFailToStop.UACK442636.10Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Remove the Acknowledge Status
1315WA3252_AFD_0103_2.almFailToStop.UnShelve442638.03Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: Unshelve Alarm Command to AE Server
1316WA3252_AFD_0103_2.almFailToStop.UnSuppress442638.01Boolean1R/W1000RWPS Pump 2: Fail to Sop Alarm DDT: UnSuppress Alarm Command to AE Server
1317WA3252_AFD_0103_2.almFailToStrt.Ack442626.06Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Acknowlege Command to AE Server
1318WA3252_AFD_0103_2.almFailToStrt.Acked442626.11Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm Acknowledged Status from AE Server
1319WA3252_AFD_0103_2.almFailToStrt.ACKN442624.09Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Acknowledge Command
1320WA3252_AFD_0103_2.almFailToStrt.AEShelveTMRDN442625.01Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm and Events Shelve Timer Done
1321WA3252_AFD_0103_2.almFailToStrt.AKED442624.06Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1322WA3252_AFD_0103_2.almFailToStrt.Alarm442626.12Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm Command to AE Server
1323WA3252_AFD_0103_2.almFailToStrt.AlarmState442624.01Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Value of the Fault input that indicates an alarm condition
1324WA3252_AFD_0103_2.almFailToStrt.ALRM442624.04Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1325WA3252_AFD_0103_2.almFailToStrt.ANUN442624.05Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1326WA3252_AFD_0103_2.almFailToStrt.Bad442625.02Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1327WA3252_AFD_0103_2.almFailToStrt.Disable442626.05Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Disable Alarm Command to AE Server
1328WA3252_AFD_0103_2.almFailToStrt.Disabled442626.10Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm Disabled Status from AE Server
1329WA3252_AFD_0103_2.almFailToStrt.Enable442626.04Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Enable Alarm Command to AE Server
1330WA3252_AFD_0103_2.almFailToStrt.Fault442624.00Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Discrete input condition indicating a faulted state.
1331WA3252_AFD_0103_2.almFailToStrt.FaultInAlarm442624.03Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Fault Is In Alarm (on longer than the delay)
1332WA3252_AFD_0103_2.almFailToStrt.GlobalReset442624.02Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Used to reset all alarms in the PLC
1333WA3252_AFD_0103_2.almFailToStrt.MCmd_Disable442624.12Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Maintenance Command to Disable Alarm
1334WA3252_AFD_0103_2.almFailToStrt.MCmd_Enable442624.11Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Maintenance Command to Enable Alarm
1335WA3252_AFD_0103_2.almFailToStrt.OCmd_Shelve442624.13Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Operator Command to Shelve Alarm
1336WA3252_AFD_0103_2.almFailToStrt.OCmd_Unshelve442624.14Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Operator Command to UnShelve Alarm
1337WA3252_AFD_0103_2.almFailToStrt.Reset442626.07Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Reset Command to AE Server
1338WA3252_AFD_0103_2.almFailToStrt.Resetable442624.07Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1339WA3252_AFD_0103_2.almFailToStrt.REST442624.08Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Reset this alarm only
1340WA3252_AFD_0103_2.almFailToStrt.SCmd_Suppress442624.15Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Supervisor Command to Suppress Alarm
1341WA3252_AFD_0103_2.almFailToStrt.SCmd_UnSuppress442625.00Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Supervisor Command to Unsuppress Alarm
1342WA3252_AFD_0103_2.almFailToStrt.Shelve442626.02Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Shelve Alarm Command to AE Server
1343WA3252_AFD_0103_2.almFailToStrt.Shelved442626.09Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm Shelved Status from AE Server
1344WA3252_AFD_0103_2.almFailToStrt.Suppress442626.00Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Suppress Alarm Command to AE Server
1345WA3252_AFD_0103_2.almFailToStrt.Suppressed442626.08Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Alarm Suppressed Status from AE Server
1346WA3252_AFD_0103_2.almFailToStrt.UACK442624.10Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Remove the Acknowledge Status
1347WA3252_AFD_0103_2.almFailToStrt.UnShelve442626.03Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: Unshelve Alarm Command to AE Server
1348WA3252_AFD_0103_2.almFailToStrt.UnSuppress442626.01Boolean1R/W1000RWPS Pump 2: Fail to Start Alarm DDT: UnSuppress Alarm Command to AE Server
1349WA3252_AFD_0103_2.almMotorFailure.Ack442650.06Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Acknowlege Command to AE Server
1350WA3252_AFD_0103_2.almMotorFailure.Acked442650.11Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm Acknowledged Status from AE Server
1351WA3252_AFD_0103_2.almMotorFailure.ACKN442648.09Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Acknowledge Command
1352WA3252_AFD_0103_2.almMotorFailure.AEShelveTMRDN442649.01Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm and Events Shelve Timer Done
1353WA3252_AFD_0103_2.almMotorFailure.AKED442648.06Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1354WA3252_AFD_0103_2.almMotorFailure.Alarm442650.12Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm Command to AE Server
1355WA3252_AFD_0103_2.almMotorFailure.AlarmState442648.01Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Value of the Fault input that indicates an alarm condition
1356WA3252_AFD_0103_2.almMotorFailure.ALRM442648.04Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1357WA3252_AFD_0103_2.almMotorFailure.ANUN442648.05Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1358WA3252_AFD_0103_2.almMotorFailure.Bad442649.02Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1359WA3252_AFD_0103_2.almMotorFailure.Disable442650.05Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Disable Alarm Command to AE Server
1360WA3252_AFD_0103_2.almMotorFailure.Disabled442650.10Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm Disabled Status from AE Server
1361WA3252_AFD_0103_2.almMotorFailure.Enable442650.04Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Enable Alarm Command to AE Server
1362WA3252_AFD_0103_2.almMotorFailure.Fault442648.00Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Discrete input condition indicating a faulted state.
1363WA3252_AFD_0103_2.almMotorFailure.FaultInAlarm442648.03Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Fault Is In Alarm (on longer than the delay)
1364WA3252_AFD_0103_2.almMotorFailure.GlobalReset442648.02Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Used to reset all alarms in the PLC
1365WA3252_AFD_0103_2.almMotorFailure.MCmd_Disable442648.12Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Maintenance Command to Disable Alarm
1366WA3252_AFD_0103_2.almMotorFailure.MCmd_Enable442648.11Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Maintenance Command to Enable Alarm
1367WA3252_AFD_0103_2.almMotorFailure.OCmd_Shelve442648.13Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Operator Command to Shelve Alarm
1368WA3252_AFD_0103_2.almMotorFailure.OCmd_Unshelve442648.14Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Operator Command to UnShelve Alarm
1369WA3252_AFD_0103_2.almMotorFailure.Reset442650.07Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Reset Command to AE Server
1370WA3252_AFD_0103_2.almMotorFailure.Resetable442648.07Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1371WA3252_AFD_0103_2.almMotorFailure.REST442648.08Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Reset this alarm only
1372WA3252_AFD_0103_2.almMotorFailure.SCmd_Suppress442648.15Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Supervisor Command to Suppress Alarm
1373WA3252_AFD_0103_2.almMotorFailure.SCmd_UnSuppress442649.00Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Supervisor Command to Unsuppress Alarm
1374WA3252_AFD_0103_2.almMotorFailure.Shelve442650.02Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Shelve Alarm Command to AE Server
1375WA3252_AFD_0103_2.almMotorFailure.Shelved442650.09Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm Shelved Status from AE Server
1376WA3252_AFD_0103_2.almMotorFailure.Suppress442650.00Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Suppress Alarm Command to AE Server
1377WA3252_AFD_0103_2.almMotorFailure.Suppressed442650.08Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Alarm Suppressed Status from AE Server
1378WA3252_AFD_0103_2.almMotorFailure.UACK442648.10Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Remove the Acknowledge Status
1379WA3252_AFD_0103_2.almMotorFailure.UnShelve442650.03Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: Unshelve Alarm Command to AE Server
1380WA3252_AFD_0103_2.almMotorFailure.UnSuppress442650.01Boolean1R/W1000RWPS Pump 2: Motor Failure Alarm DDT: UnSuppress Alarm Command to AE Server
1381WA3252_AFD_0103_2.almPLCFault.Ack442662.06Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Acknowlege Command to AE Server
1382WA3252_AFD_0103_2.almPLCFault.Acked442662.11Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1383WA3252_AFD_0103_2.almPLCFault.ACKN442660.09Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Acknowledge Command
1384WA3252_AFD_0103_2.almPLCFault.AEShelveTMRDN442661.01Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1385WA3252_AFD_0103_2.almPLCFault.AKED442660.06Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1386WA3252_AFD_0103_2.almPLCFault.Alarm442662.12Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm Command to AE Server
1387WA3252_AFD_0103_2.almPLCFault.AlarmState442660.01Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1388WA3252_AFD_0103_2.almPLCFault.ALRM442660.04Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1389WA3252_AFD_0103_2.almPLCFault.ANUN442660.05Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1390WA3252_AFD_0103_2.almPLCFault.Bad442661.02Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1391WA3252_AFD_0103_2.almPLCFault.Disable442662.05Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1392WA3252_AFD_0103_2.almPLCFault.Disabled442662.10Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1393WA3252_AFD_0103_2.almPLCFault.Enable442662.04Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1394WA3252_AFD_0103_2.almPLCFault.Fault442660.00Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1395WA3252_AFD_0103_2.almPLCFault.FaultInAlarm442660.03Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1396WA3252_AFD_0103_2.almPLCFault.GlobalReset442660.02Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1397WA3252_AFD_0103_2.almPLCFault.MCmd_Disable442660.12Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1398WA3252_AFD_0103_2.almPLCFault.MCmd_Enable442660.11Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1399WA3252_AFD_0103_2.almPLCFault.OCmd_Shelve442660.13Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1400WA3252_AFD_0103_2.almPLCFault.OCmd_Unshelve442660.14Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1401WA3252_AFD_0103_2.almPLCFault.Reset442662.07Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Reset Command to AE Server
1402WA3252_AFD_0103_2.almPLCFault.Resetable442660.07Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1403WA3252_AFD_0103_2.almPLCFault.REST442660.08Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Reset this alarm only
1404WA3252_AFD_0103_2.almPLCFault.SCmd_Suppress442660.15Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1405WA3252_AFD_0103_2.almPLCFault.SCmd_UnSuppress442661.00Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1406WA3252_AFD_0103_2.almPLCFault.Shelve442662.02Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1407WA3252_AFD_0103_2.almPLCFault.Shelved442662.09Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1408WA3252_AFD_0103_2.almPLCFault.Suppress442662.00Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1409WA3252_AFD_0103_2.almPLCFault.Suppressed442662.08Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1410WA3252_AFD_0103_2.almPLCFault.UACK442660.10Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Remove the Acknowledge Status
1411WA3252_AFD_0103_2.almPLCFault.UnShelve442662.03Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1412WA3252_AFD_0103_2.almPLCFault.UnSuppress442662.01Boolean1R/W1000RWPS Pump 2: PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1413WA3252_AFD_0103_2.almSpeedDeviation.Ack442674.06Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Acknowlege Command to AE Server
1414WA3252_AFD_0103_2.almSpeedDeviation.Acked442674.11Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm Acknowledged Status from AE Server
1415WA3252_AFD_0103_2.almSpeedDeviation.ACKN442672.09Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Acknowledge Command
1416WA3252_AFD_0103_2.almSpeedDeviation.AEShelveTMRDN442673.01Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm and Events Shelve Timer Done
1417WA3252_AFD_0103_2.almSpeedDeviation.AKED442672.06Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1418WA3252_AFD_0103_2.almSpeedDeviation.Alarm442674.12Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm Command to AE Server
1419WA3252_AFD_0103_2.almSpeedDeviation.AlarmState442672.01Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Value of the Fault input that indicates an alarm condition
1420WA3252_AFD_0103_2.almSpeedDeviation.ALRM442672.04Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1421WA3252_AFD_0103_2.almSpeedDeviation.ANUN442672.05Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1422WA3252_AFD_0103_2.almSpeedDeviation.Bad442673.02Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1423WA3252_AFD_0103_2.almSpeedDeviation.Disable442674.05Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Disable Alarm Command to AE Server
1424WA3252_AFD_0103_2.almSpeedDeviation.Disabled442674.10Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm Disabled Status from AE Server
1425WA3252_AFD_0103_2.almSpeedDeviation.Enable442674.04Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Enable Alarm Command to AE Server
1426WA3252_AFD_0103_2.almSpeedDeviation.Fault442672.00Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Discrete input condition indicating a faulted state.
1427WA3252_AFD_0103_2.almSpeedDeviation.FaultInAlarm442672.03Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Fault Is In Alarm (on longer than the delay)
1428WA3252_AFD_0103_2.almSpeedDeviation.GlobalReset442672.02Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Used to reset all alarms in the PLC
1429WA3252_AFD_0103_2.almSpeedDeviation.MCmd_Disable442672.12Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Maintenance Command to Disable Alarm
1430WA3252_AFD_0103_2.almSpeedDeviation.MCmd_Enable442672.11Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Maintenance Command to Enable Alarm
1431WA3252_AFD_0103_2.almSpeedDeviation.OCmd_Shelve442672.13Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Operator Command to Shelve Alarm
1432WA3252_AFD_0103_2.almSpeedDeviation.OCmd_Unshelve442672.14Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Operator Command to UnShelve Alarm
1433WA3252_AFD_0103_2.almSpeedDeviation.Reset442674.07Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Reset Command to AE Server
1434WA3252_AFD_0103_2.almSpeedDeviation.Resetable442672.07Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1435WA3252_AFD_0103_2.almSpeedDeviation.REST442672.08Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Reset this alarm only
1436WA3252_AFD_0103_2.almSpeedDeviation.SCmd_Suppress442672.15Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Supervisor Command to Suppress Alarm
1437WA3252_AFD_0103_2.almSpeedDeviation.SCmd_UnSuppress442673.00Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Supervisor Command to Unsuppress Alarm
1438WA3252_AFD_0103_2.almSpeedDeviation.Shelve442674.02Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Shelve Alarm Command to AE Server
1439WA3252_AFD_0103_2.almSpeedDeviation.Shelved442674.09Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm Shelved Status from AE Server
1440WA3252_AFD_0103_2.almSpeedDeviation.Suppress442674.00Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Suppress Alarm Command to AE Server
1441WA3252_AFD_0103_2.almSpeedDeviation.Suppressed442674.08Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Alarm Suppressed Status from AE Server
1442WA3252_AFD_0103_2.almSpeedDeviation.UACK442672.10Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Remove the Acknowledge Status
1443WA3252_AFD_0103_2.almSpeedDeviation.UnShelve442674.03Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: Unshelve Alarm Command to AE Server
1444WA3252_AFD_0103_2.almSpeedDeviation.UnSuppress442674.01Boolean1R/W1000RWPS Pump 2: Speed Deviation Alarm DDT: UnSuppress Alarm Command to AE Server
1445WA3252_AFD_0103_2.ALRM442575.09Boolean1R/W1000RWPS Pump 2: At least one alarm on this device is active.
1446WA3252_AFD_0103_2.ANUN442575.11Boolean1R/W1000RWPS Pump 2: At least one alarm in Device is annunciating (flash the device symbol)
1447WA3252_AFD_0103_2.AUTO442574.15Boolean1R/W1000RWPS Pump 2: Set by HMI 0 = Device in Manual 1 Device in Auto
1448WA3252_AFD_0103_2.AutoEnable442574.11Boolean1R/W1000RWPS Pump 2: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI
1449WA3252_AFD_0103_2.AutoRdy442575.15Boolean1R/W1000RWPS Pump 2: Device is ready for auto control
1450WA3252_AFD_0103_2.AutoStop442575.03Boolean1R/W1000RWPS Pump 2: Auto Stop from Auto Logic
1451WA3252_AFD_0103_2.AutoStrt442575.02Boolean1R/W1000RWPS Pump 2: Auto Start from Auto Logic
1452WA3252_AFD_0103_2.DevFault442576.05Boolean1R/W1000RWPS Pump 2: Deviation fault is active, this is not the delayed alarm
1453WA3252_AFD_0103_2.Deviation442576.04Boolean1R/W1000RWPS Pump 2: Deviation Alarm from Logic
1454WA3252_AFD_0103_2.FAIL442575.13Boolean1R/W1000RWPS Pump 2: Fail to Start, Fail to Stop or Motor Failure alarm is active
1455WA3252_AFD_0103_2.FailToStop442575.07Boolean1R/W1000RWPS Pump 2: Device Failed to Stop
1456WA3252_AFD_0103_2.FailToStrt442575.06Boolean1R/W1000RWPS Pump 2: Device Failed to Start
1457WA3252_AFD_0103_2.GlobalReset442574.14Boolean1R/W1000RWPS Pump 2: Used to reset all alarms in the DFB
1458WA3252_AFD_0103_2.HzEnable442574.12Boolean1R/W1000RWPS Pump 2: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)
1459WA3252_AFD_0103_2.INFO442574.02Boolean1R/W1000RWPS Pump 2: True indicates blue flag should be displayed.
1460WA3252_AFD_0103_2.INTK442575.00Boolean1R/W1000RWPS Pump 2: Locked by program (ESD)
1461WA3252_AFD_0103_2.IR442574.07Boolean1R/W1000RWPS Pump 2: Remote: 1 = Device In Remote 0 = Device In Local
1462WA3252_AFD_0103_2.ManDisable442574.13Boolean1R/W1000RWPS Pump 2: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual
1463WA3252_AFD_0103_2.MD442575.14Boolean1R/W1000RWPS Pump 2: Device Run Command
1464WA3252_AFD_0103_2.MF442574.09Boolean1R/W1000RWPS Pump 2: Motor Fail Status from Motor Controller
1465WA3252_AFD_0103_2.MN442574.08Boolean1R/W1000RWPS Pump 2: Device Running Status
1466WA3252_AFD_0103_2.MotorFailure442575.08Boolean1R/W1000RWPS Pump 2: General Failure Alarm from Motor Drive
1467WA3252_AFD_0103_2.PCSuppress442576.08Boolean1R/W1000RWPS Pump 2: Suppress Alarm from Program Control
1468WA3252_AFD_0103_2.PCUnShelve442576.10Boolean1R/W1000RWPS Pump 2: Unshelve Alarm from Program Control
1469WA3252_AFD_0103_2.PCUnSuppress442576.09Boolean1R/W1000RWPS Pump 2: UnSuppress Alarm from Program Control
1470WA3252_AFD_0103_2.PLCFault442576.00Boolean1R/W1000RWPS Pump 2: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1471WA3252_AFD_0103_2.PLCIOFault442576.01Boolean1R/W1000RWPS Pump 2: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1472WA3252_AFD_0103_2.RemoteEnable442574.10Boolean1R/W1000RWPS Pump 2: 1 remote/local input wired 0 = not wired
1473WA3252_AFD_0103_2.Resetable442575.12Boolean1R/W1000RWPS Pump 2: All Alarms can be reset
1474WA3252_AFD_0103_2.REST442574.05Boolean1R/W1000RWPS Pump 2: Reset: Command from HMI to Reset all alarms on this device.
1475WA3252_AFD_0103_2.RSRT442575.04Boolean1R/W1000RWPS Pump 2: Reset Runtime Command from HMI
1476WA3252_AFD_0103_2.RSST442575.05Boolean1R/W1000RWPS Pump 2: Reset Count of Starts Command from HMI
1477WA3252_AFD_0103_2.Shelve442576.06Boolean1R/W1000RWPS Pump 2: Shelve Command from HMI
1478WA3252_AFD_0103_2.Shelved442576.02Boolean1R/W1000RWPS Pump 2: General Alarm Shelved State
1479WA3252_AFD_0103_2.STOP442574.01Boolean1R/W1000RWPS Pump 2: Stop Command from HMI
1480WA3252_AFD_0103_2.StopFault442574.04Boolean1R/W1000RWPS Pump 2: Stop fault is active, this is not the delayed alarm
1481WA3252_AFD_0103_2.STRT442574.00Boolean1R/W1000RWPS Pump 2: Start Command from HMI
1482WA3252_AFD_0103_2.StrtFault442574.03Boolean1R/W1000RWPS Pump 2: Start fault is active, this is not the delayed alarm
1483WA3252_AFD_0103_2.Suppress442576.07Boolean1R/W1000RWPS Pump 2: Suppress Command from HMI
1484WA3252_AFD_0103_2.Suppressed442576.03Boolean1R/W1000RWPS Pump 2: General Alarm Suppressed State
1485WA3252_AFD_0103_2.TAGR442575.01Boolean1R/W1000RWPS Pump 2: Tagged Out of Service
1486WA3252_AFD_0103_2_BM459011.04Boolean1R/W1000RWPS Pump 2 Bypass Mode Command
1487WA3252_AFD_0103_2_BM1459013.11Boolean1R/W1000RWPS Pump 2 In Bypass Mode
1488WA3252_AFD_0103_2_BM1_raw459013.11Boolean1R/W1000RWPS Pump 2 In Bypass Mode
1489WA3252_AFD_0103_2_BM2459013.04Boolean1R/W1000RWPS Pump 2 Discharge Pressure Bypass Mode
1490WA3252_AFD_0103_2_BM3459004.05Boolean1R/W1000RWPS Pump 2 PCV Throttle Bypass Enabled
1491WA3252_AFD_0103_2_BYPASS459011.05Boolean1R/W1000RWPS Pump 2 HMI Lockout Command
1492WA3252_AFD_0103_2_FA.ACKN419840.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Acknowledge Alarm
1493WA3252_AFD_0103_2_FA.AKED419840.11Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : At Least One Alarm is Acknowledged
1494WA3252_AFD_0103_2_FA.Alarm.Ack419848.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1495WA3252_AFD_0103_2_FA.Alarm.Acked419848.11Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1496WA3252_AFD_0103_2_FA.Alarm.ACKN419846.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowledge Command
1497WA3252_AFD_0103_2_FA.Alarm.AEShelveTMRDN419847.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1498WA3252_AFD_0103_2_FA.Alarm.AKED419846.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1499WA3252_AFD_0103_2_FA.Alarm.Alarm419848.12Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Command to AE Server
1500WA3252_AFD_0103_2_FA.Alarm.AlarmState419846.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1501WA3252_AFD_0103_2_FA.Alarm.ALRM419846.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1502WA3252_AFD_0103_2_FA.Alarm.ANUN419846.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1503WA3252_AFD_0103_2_FA.Alarm.Bad419847.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1504WA3252_AFD_0103_2_FA.Alarm.Disable419848.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1505WA3252_AFD_0103_2_FA.Alarm.Disabled419848.10Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1506WA3252_AFD_0103_2_FA.Alarm.Enable419848.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1507WA3252_AFD_0103_2_FA.Alarm.Fault419846.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1508WA3252_AFD_0103_2_FA.Alarm.FaultInAlarm419846.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1509WA3252_AFD_0103_2_FA.Alarm.GlobalReset419846.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1510WA3252_AFD_0103_2_FA.Alarm.MCmd_Disable419846.12Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1511WA3252_AFD_0103_2_FA.Alarm.MCmd_Enable419846.11Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1512WA3252_AFD_0103_2_FA.Alarm.OCmd_Shelve419846.13Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1513WA3252_AFD_0103_2_FA.Alarm.OCmd_Unshelve419846.14Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1514WA3252_AFD_0103_2_FA.Alarm.Reset419848.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Reset Command to AE Server
1515WA3252_AFD_0103_2_FA.Alarm.Resetable419846.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1516WA3252_AFD_0103_2_FA.Alarm.REST419846.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Reset this alarm only
1517WA3252_AFD_0103_2_FA.Alarm.SCmd_Suppress419846.15Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1518WA3252_AFD_0103_2_FA.Alarm.SCmd_UnSuppress419847.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1519WA3252_AFD_0103_2_FA.Alarm.Shelve419848.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1520WA3252_AFD_0103_2_FA.Alarm.Shelved419848.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1521WA3252_AFD_0103_2_FA.Alarm.Suppress419848.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1522WA3252_AFD_0103_2_FA.Alarm.Suppressed419848.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1523WA3252_AFD_0103_2_FA.Alarm.UACK419846.10Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Remove the Acknowledge Status
1524WA3252_AFD_0103_2_FA.Alarm.UnShelve419848.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1525WA3252_AFD_0103_2_FA.Alarm.UnSuppress419848.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1526WA3252_AFD_0103_2_FA.Alarm_EN419840.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : 0 = enable alarm
1527WA3252_AFD_0103_2_FA.Alarm_Fault419841.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Alarm is in fault
1528WA3252_AFD_0103_2_FA.AlarmState419840.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Input value signifying alarm
1529WA3252_AFD_0103_2_FA.almPLCFault.Ack419860.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowlege Command to AE Server
1530WA3252_AFD_0103_2_FA.almPLCFault.Acked419860.11Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1531WA3252_AFD_0103_2_FA.almPLCFault.ACKN419858.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowledge Command
1532WA3252_AFD_0103_2_FA.almPLCFault.AEShelveTMRDN419859.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1533WA3252_AFD_0103_2_FA.almPLCFault.AKED419858.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1534WA3252_AFD_0103_2_FA.almPLCFault.Alarm419860.12Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Command to AE Server
1535WA3252_AFD_0103_2_FA.almPLCFault.AlarmState419858.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1536WA3252_AFD_0103_2_FA.almPLCFault.ALRM419858.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1537WA3252_AFD_0103_2_FA.almPLCFault.ANUN419858.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1538WA3252_AFD_0103_2_FA.almPLCFault.Bad419859.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1539WA3252_AFD_0103_2_FA.almPLCFault.Disable419860.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1540WA3252_AFD_0103_2_FA.almPLCFault.Disabled419860.10Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1541WA3252_AFD_0103_2_FA.almPLCFault.Enable419860.04Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1542WA3252_AFD_0103_2_FA.almPLCFault.Fault419858.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1543WA3252_AFD_0103_2_FA.almPLCFault.FaultInAlarm419858.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1544WA3252_AFD_0103_2_FA.almPLCFault.GlobalReset419858.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1545WA3252_AFD_0103_2_FA.almPLCFault.MCmd_Disable419858.12Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1546WA3252_AFD_0103_2_FA.almPLCFault.MCmd_Enable419858.11Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1547WA3252_AFD_0103_2_FA.almPLCFault.OCmd_Shelve419858.13Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1548WA3252_AFD_0103_2_FA.almPLCFault.OCmd_Unshelve419858.14Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1549WA3252_AFD_0103_2_FA.almPLCFault.Reset419860.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Reset Command to AE Server
1550WA3252_AFD_0103_2_FA.almPLCFault.Resetable419858.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1551WA3252_AFD_0103_2_FA.almPLCFault.REST419858.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Reset this alarm only
1552WA3252_AFD_0103_2_FA.almPLCFault.SCmd_Suppress419858.15Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1553WA3252_AFD_0103_2_FA.almPLCFault.SCmd_UnSuppress419859.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1554WA3252_AFD_0103_2_FA.almPLCFault.Shelve419860.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1555WA3252_AFD_0103_2_FA.almPLCFault.Shelved419860.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1556WA3252_AFD_0103_2_FA.almPLCFault.Suppress419860.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1557WA3252_AFD_0103_2_FA.almPLCFault.Suppressed419860.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1558WA3252_AFD_0103_2_FA.almPLCFault.UACK419858.10Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Remove the Acknowledge Status
1559WA3252_AFD_0103_2_FA.almPLCFault.UnShelve419860.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1560WA3252_AFD_0103_2_FA.almPLCFault.UnSuppress419860.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1561WA3252_AFD_0103_2_FA.ALRM419840.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : At Least One Alarm is Active
1562WA3252_AFD_0103_2_FA.ANUN419840.10Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : At Least One Alarm is Annunciating
1563WA3252_AFD_0103_2_FA.Fault419840.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Input tag to monitor for alarm
1564WA3252_AFD_0103_2_FA.Faulted419840.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Input is in fault
1565WA3252_AFD_0103_2_FA.FaultInAlarm419840.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Fault Is In Alarm (on longer than the delay)
1566WA3252_AFD_0103_2_FA.GlobalReset419841.00Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Reset all Alarms On this PLC
1567WA3252_AFD_0103_2_FA.InputAlarm419840.15Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure :
1568WA3252_AFD_0103_2_FA.MCmd_Disable419840.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Maintenance Command to Disable Alarm
1569WA3252_AFD_0103_2_FA.MCmd_Enable419840.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Maintenance Command to Enable Alarm
1570WA3252_AFD_0103_2_FA.PCSuppress419841.01Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Suppress Alarm from Program Control
1571WA3252_AFD_0103_2_FA.PCUnshelve419841.03Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Unshelve Alarm from Program Control
1572WA3252_AFD_0103_2_FA.PCUnSuppress419841.02Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : UnSuppress Alarm from Program Control
1573WA3252_AFD_0103_2_FA.PLCF419841.08Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1574WA3252_AFD_0103_2_FA.PLCIOFault419841.07Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1575WA3252_AFD_0103_2_FA.Resetable419840.12Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : At least one alarm is latched and all latched alarms are resetable
1576WA3252_AFD_0103_2_FA.REST419840.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Reset Alarm
1577WA3252_AFD_0103_2_FA.Shelve419840.13Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Shelve Command from HMI
1578WA3252_AFD_0103_2_FA.Shelved419841.05Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Shelved Status
1579WA3252_AFD_0103_2_FA.Suppress419840.14Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Suppress Command from HMI
1580WA3252_AFD_0103_2_FA.Suppressed419841.06Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Suppressed Status
1581WA3252_AFD_0103_2_FA.TAGR419841.09Boolean1R/W1000RWPS Pump 2 Cooling Water Flow Failure : Tagged Out of Service
1582WA3252_AFD_0103_2_HS459011.06Boolean1R/W1000RWPS Pump 2 Scada Lockout
1583WA3252_AFD_0103_2_IR459004.02Boolean1R/W1000RWPS Pump 2 Scada Enabled
1584WA3252_AFD_0103_2_LOCKOUT459011.07Boolean1R/W1000RWPS Pump 2 HMI Lockout Command
1585WA3252_AFD_0103_2_LOCKOUTRST459011.08Boolean1R/W1000RWPS Pump 2 HMI Lockout Reset
1586WA3252_AFD_0103_2_MB459006.14Boolean1R/W1000RWPS Pump 2 Scada Stop
1587WA3252_AFD_0103_2_MBU459014.11Boolean1R/W1000RWPS Pump 2 Scada Unplanned Stop
1588WA3252_AFD_0103_2_MD459006.13Boolean1R/W1000RWPS Pump 2 Scada Start
1589WA3252_AFD_0103_2_MF.ACKN460810.06Boolean1R/W1000Pump 2 Motor Seal Leak: Acknowledge Alarm
1590WA3252_AFD_0103_2_MF.AKED460810.11Boolean1R/W1000Pump 2 Motor Seal Leak: At Least One Alarm is Acknowledged
1591WA3252_AFD_0103_2_MF.Alarm.Ack460818.06Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1592WA3252_AFD_0103_2_MF.Alarm.Acked460818.11Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1593WA3252_AFD_0103_2_MF.Alarm.ACKN460816.09Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowledge Command
1594WA3252_AFD_0103_2_MF.Alarm.AEShelveTMRDN460817.01Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1595WA3252_AFD_0103_2_MF.Alarm.AKED460816.06Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1596WA3252_AFD_0103_2_MF.Alarm.Alarm460818.12Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Command to AE Server
1597WA3252_AFD_0103_2_MF.Alarm.AlarmState460816.01Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1598WA3252_AFD_0103_2_MF.Alarm.ALRM460816.04Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1599WA3252_AFD_0103_2_MF.Alarm.ANUN460816.05Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1600WA3252_AFD_0103_2_MF.Alarm.Bad460817.02Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1601WA3252_AFD_0103_2_MF.Alarm.Disable460818.05Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1602WA3252_AFD_0103_2_MF.Alarm.Disabled460818.10Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1603WA3252_AFD_0103_2_MF.Alarm.Enable460818.04Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1604WA3252_AFD_0103_2_MF.Alarm.Fault460816.00Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1605WA3252_AFD_0103_2_MF.Alarm.FaultInAlarm460816.03Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1606WA3252_AFD_0103_2_MF.Alarm.GlobalReset460816.02Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1607WA3252_AFD_0103_2_MF.Alarm.MCmd_Disable460816.12Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1608WA3252_AFD_0103_2_MF.Alarm.MCmd_Enable460816.11Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1609WA3252_AFD_0103_2_MF.Alarm.OCmd_Shelve460816.13Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1610WA3252_AFD_0103_2_MF.Alarm.OCmd_Unshelve460816.14Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1611WA3252_AFD_0103_2_MF.Alarm.Reset460818.07Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Reset Command to AE Server
1612WA3252_AFD_0103_2_MF.Alarm.Resetable460816.07Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1613WA3252_AFD_0103_2_MF.Alarm.REST460816.08Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Reset this alarm only
1614WA3252_AFD_0103_2_MF.Alarm.SCmd_Suppress460816.15Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1615WA3252_AFD_0103_2_MF.Alarm.SCmd_UnSuppress460817.00Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1616WA3252_AFD_0103_2_MF.Alarm.Shelve460818.02Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1617WA3252_AFD_0103_2_MF.Alarm.Shelved460818.09Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1618WA3252_AFD_0103_2_MF.Alarm.Suppress460818.00Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1619WA3252_AFD_0103_2_MF.Alarm.Suppressed460818.08Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1620WA3252_AFD_0103_2_MF.Alarm.UACK460816.10Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Remove the Acknowledge Status
1621WA3252_AFD_0103_2_MF.Alarm.UnShelve460818.03Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1622WA3252_AFD_0103_2_MF.Alarm.UnSuppress460818.01Boolean1R/W1000Pump 2 Motor Seal Leak: ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1623WA3252_AFD_0103_2_MF.Alarm_EN460810.04Boolean1R/W1000Pump 2 Motor Seal Leak: 0 = enable alarm
1624WA3252_AFD_0103_2_MF.Alarm_Fault460811.04Boolean1R/W1000Pump 2 Motor Seal Leak: Alarm is in fault
1625WA3252_AFD_0103_2_MF.AlarmState460810.02Boolean1R/W1000Pump 2 Motor Seal Leak: Input value signifying alarm
1626WA3252_AFD_0103_2_MF.almPLCFault.Ack460830.06Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Acknowlege Command to AE Server
1627WA3252_AFD_0103_2_MF.almPLCFault.Acked460830.11Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1628WA3252_AFD_0103_2_MF.almPLCFault.ACKN460828.09Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Acknowledge Command
1629WA3252_AFD_0103_2_MF.almPLCFault.AEShelveTMRDN460829.01Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1630WA3252_AFD_0103_2_MF.almPLCFault.AKED460828.06Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1631WA3252_AFD_0103_2_MF.almPLCFault.Alarm460830.12Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Command to AE Server
1632WA3252_AFD_0103_2_MF.almPLCFault.AlarmState460828.01Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1633WA3252_AFD_0103_2_MF.almPLCFault.ALRM460828.04Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1634WA3252_AFD_0103_2_MF.almPLCFault.ANUN460828.05Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1635WA3252_AFD_0103_2_MF.almPLCFault.Bad460829.02Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1636WA3252_AFD_0103_2_MF.almPLCFault.Disable460830.05Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1637WA3252_AFD_0103_2_MF.almPLCFault.Disabled460830.10Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1638WA3252_AFD_0103_2_MF.almPLCFault.Enable460830.04Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1639WA3252_AFD_0103_2_MF.almPLCFault.Fault460828.00Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1640WA3252_AFD_0103_2_MF.almPLCFault.FaultInAlarm460828.03Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1641WA3252_AFD_0103_2_MF.almPLCFault.GlobalReset460828.02Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1642WA3252_AFD_0103_2_MF.almPLCFault.MCmd_Disable460828.12Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1643WA3252_AFD_0103_2_MF.almPLCFault.MCmd_Enable460828.11Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1644WA3252_AFD_0103_2_MF.almPLCFault.OCmd_Shelve460828.13Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1645WA3252_AFD_0103_2_MF.almPLCFault.OCmd_Unshelve460828.14Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1646WA3252_AFD_0103_2_MF.almPLCFault.Reset460830.07Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Reset Command to AE Server
1647WA3252_AFD_0103_2_MF.almPLCFault.Resetable460828.07Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1648WA3252_AFD_0103_2_MF.almPLCFault.REST460828.08Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Reset this alarm only
1649WA3252_AFD_0103_2_MF.almPLCFault.SCmd_Suppress460828.15Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1650WA3252_AFD_0103_2_MF.almPLCFault.SCmd_UnSuppress460829.00Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1651WA3252_AFD_0103_2_MF.almPLCFault.Shelve460830.02Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1652WA3252_AFD_0103_2_MF.almPLCFault.Shelved460830.09Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1653WA3252_AFD_0103_2_MF.almPLCFault.Suppress460830.00Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1654WA3252_AFD_0103_2_MF.almPLCFault.Suppressed460830.08Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1655WA3252_AFD_0103_2_MF.almPLCFault.UACK460828.10Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Remove the Acknowledge Status
1656WA3252_AFD_0103_2_MF.almPLCFault.UnShelve460830.03Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1657WA3252_AFD_0103_2_MF.almPLCFault.UnSuppress460830.01Boolean1R/W1000Pump 2 Motor Seal Leak: PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1658WA3252_AFD_0103_2_MF.ALRM460810.09Boolean1R/W1000Pump 2 Motor Seal Leak: At Least One Alarm is Active
1659WA3252_AFD_0103_2_MF.ANUN460810.10Boolean1R/W1000Pump 2 Motor Seal Leak: At Least One Alarm is Annunciating
1660WA3252_AFD_0103_2_MF.Fault460810.00Boolean1R/W1000Pump 2 Motor Seal Leak: Input tag to monitor for alarm
1661WA3252_AFD_0103_2_MF.Faulted460810.01Boolean1R/W1000Pump 2 Motor Seal Leak: Input is in fault
1662WA3252_AFD_0103_2_MF.FaultInAlarm460810.03Boolean1R/W1000Pump 2 Motor Seal Leak: Fault Is In Alarm (on longer than the delay)
1663WA3252_AFD_0103_2_MF.GlobalReset460811.00Boolean1R/W1000Pump 2 Motor Seal Leak: Reset all Alarms On this PLC
1664WA3252_AFD_0103_2_MF.InputAlarm460810.15Boolean1R/W1000Pump 2 Motor Seal Leak:
1665WA3252_AFD_0103_2_MF.MCmd_Disable460810.08Boolean1R/W1000Pump 2 Motor Seal Leak: Maintenance Command to Disable Alarm
1666WA3252_AFD_0103_2_MF.MCmd_Enable460810.07Boolean1R/W1000Pump 2 Motor Seal Leak: Maintenance Command to Enable Alarm
1667WA3252_AFD_0103_2_MF.PCSuppress460811.01Boolean1R/W1000Pump 2 Motor Seal Leak: Suppress Alarm from Program Control
1668WA3252_AFD_0103_2_MF.PCUnshelve460811.03Boolean1R/W1000Pump 2 Motor Seal Leak: Unshelve Alarm from Program Control
1669WA3252_AFD_0103_2_MF.PCUnSuppress460811.02Boolean1R/W1000Pump 2 Motor Seal Leak: UnSuppress Alarm from Program Control
1670WA3252_AFD_0103_2_MF.PLCF460811.08Boolean1R/W1000Pump 2 Motor Seal Leak: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1671WA3252_AFD_0103_2_MF.PLCIOFault460811.07Boolean1R/W1000Pump 2 Motor Seal Leak: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1672WA3252_AFD_0103_2_MF.Resetable460810.12Boolean1R/W1000Pump 2 Motor Seal Leak: At least one alarm is latched and all latched alarms are resetable
1673WA3252_AFD_0103_2_MF.REST460810.05Boolean1R/W1000Pump 2 Motor Seal Leak: Reset Alarm
1674WA3252_AFD_0103_2_MF.Shelve460810.13Boolean1R/W1000Pump 2 Motor Seal Leak: Shelve Command from HMI
1675WA3252_AFD_0103_2_MF.Shelved460811.05Boolean1R/W1000Pump 2 Motor Seal Leak: Shelved Status
1676WA3252_AFD_0103_2_MF.Suppress460810.14Boolean1R/W1000Pump 2 Motor Seal Leak: Suppress Command from HMI
1677WA3252_AFD_0103_2_MF.Suppressed460811.06Boolean1R/W1000Pump 2 Motor Seal Leak: Suppressed Status
1678WA3252_AFD_0103_2_MF.TAGR460811.09Boolean1R/W1000Pump 2 Motor Seal Leak: Tagged Out of Service
1679WA3252_AFD_0103_2_ML459004.03Boolean1R/W1000RWPS Pump 2 Ready
1680WA3252_AFD_0103_2_MN459004.04Boolean1R/W1000RWPS Pump 2 Run Status
1681WA3252_AFD_0103_2_MY.ACKN419960.06Boolean1R/W1000RWPS Pump 2 E. Stop : Acknowledge Alarm
1682WA3252_AFD_0103_2_MY.AKED419960.11Boolean1R/W1000RWPS Pump 2 E. Stop : At Least One Alarm is Acknowledged
1683WA3252_AFD_0103_2_MY.Alarm.Ack419968.06Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
1684WA3252_AFD_0103_2_MY.Alarm.Acked419968.11Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
1685WA3252_AFD_0103_2_MY.Alarm.ACKN419966.09Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Acknowledge Command
1686WA3252_AFD_0103_2_MY.Alarm.AEShelveTMRDN419967.01Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
1687WA3252_AFD_0103_2_MY.Alarm.AKED419966.06Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1688WA3252_AFD_0103_2_MY.Alarm.Alarm419968.12Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm Command to AE Server
1689WA3252_AFD_0103_2_MY.Alarm.AlarmState419966.01Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
1690WA3252_AFD_0103_2_MY.Alarm.ALRM419966.04Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
1691WA3252_AFD_0103_2_MY.Alarm.ANUN419966.05Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1692WA3252_AFD_0103_2_MY.Alarm.Bad419967.02Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
1693WA3252_AFD_0103_2_MY.Alarm.Disable419968.05Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
1694WA3252_AFD_0103_2_MY.Alarm.Disabled419968.10Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
1695WA3252_AFD_0103_2_MY.Alarm.Enable419968.04Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
1696WA3252_AFD_0103_2_MY.Alarm.Fault419966.00Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
1697WA3252_AFD_0103_2_MY.Alarm.FaultInAlarm419966.03Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
1698WA3252_AFD_0103_2_MY.Alarm.GlobalReset419966.02Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
1699WA3252_AFD_0103_2_MY.Alarm.MCmd_Disable419966.12Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
1700WA3252_AFD_0103_2_MY.Alarm.MCmd_Enable419966.11Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
1701WA3252_AFD_0103_2_MY.Alarm.OCmd_Shelve419966.13Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
1702WA3252_AFD_0103_2_MY.Alarm.OCmd_Unshelve419966.14Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
1703WA3252_AFD_0103_2_MY.Alarm.Reset419968.07Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Reset Command to AE Server
1704WA3252_AFD_0103_2_MY.Alarm.Resetable419966.07Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
1705WA3252_AFD_0103_2_MY.Alarm.REST419966.08Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Reset this alarm only
1706WA3252_AFD_0103_2_MY.Alarm.SCmd_Suppress419966.15Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
1707WA3252_AFD_0103_2_MY.Alarm.SCmd_UnSuppress419967.00Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
1708WA3252_AFD_0103_2_MY.Alarm.Shelve419968.02Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
1709WA3252_AFD_0103_2_MY.Alarm.Shelved419968.09Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
1710WA3252_AFD_0103_2_MY.Alarm.Suppress419968.00Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
1711WA3252_AFD_0103_2_MY.Alarm.Suppressed419968.08Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
1712WA3252_AFD_0103_2_MY.Alarm.UACK419966.10Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Remove the Acknowledge Status
1713WA3252_AFD_0103_2_MY.Alarm.UnShelve419968.03Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
1714WA3252_AFD_0103_2_MY.Alarm.UnSuppress419968.01Boolean1R/W1000RWPS Pump 2 E. Stop : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
1715WA3252_AFD_0103_2_MY.Alarm_EN419960.04Boolean1R/W1000RWPS Pump 2 E. Stop : 0 = enable alarm
1716WA3252_AFD_0103_2_MY.Alarm_Fault419961.04Boolean1R/W1000RWPS Pump 2 E. Stop : Alarm is in fault
1717WA3252_AFD_0103_2_MY.AlarmState419960.02Boolean1R/W1000RWPS Pump 2 E. Stop : Input value signifying alarm
1718WA3252_AFD_0103_2_MY.almPLCFault.Ack419980.06Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Acknowlege Command to AE Server
1719WA3252_AFD_0103_2_MY.almPLCFault.Acked419980.11Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1720WA3252_AFD_0103_2_MY.almPLCFault.ACKN419978.09Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Acknowledge Command
1721WA3252_AFD_0103_2_MY.almPLCFault.AEShelveTMRDN419979.01Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
1722WA3252_AFD_0103_2_MY.almPLCFault.AKED419978.06Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1723WA3252_AFD_0103_2_MY.almPLCFault.Alarm419980.12Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm Command to AE Server
1724WA3252_AFD_0103_2_MY.almPLCFault.AlarmState419978.01Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1725WA3252_AFD_0103_2_MY.almPLCFault.ALRM419978.04Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1726WA3252_AFD_0103_2_MY.almPLCFault.ANUN419978.05Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1727WA3252_AFD_0103_2_MY.almPLCFault.Bad419979.02Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1728WA3252_AFD_0103_2_MY.almPLCFault.Disable419980.05Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
1729WA3252_AFD_0103_2_MY.almPLCFault.Disabled419980.10Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
1730WA3252_AFD_0103_2_MY.almPLCFault.Enable419980.04Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
1731WA3252_AFD_0103_2_MY.almPLCFault.Fault419978.00Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
1732WA3252_AFD_0103_2_MY.almPLCFault.FaultInAlarm419978.03Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1733WA3252_AFD_0103_2_MY.almPLCFault.GlobalReset419978.02Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
1734WA3252_AFD_0103_2_MY.almPLCFault.MCmd_Disable419978.12Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
1735WA3252_AFD_0103_2_MY.almPLCFault.MCmd_Enable419978.11Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
1736WA3252_AFD_0103_2_MY.almPLCFault.OCmd_Shelve419978.13Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
1737WA3252_AFD_0103_2_MY.almPLCFault.OCmd_Unshelve419978.14Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
1738WA3252_AFD_0103_2_MY.almPLCFault.Reset419980.07Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Reset Command to AE Server
1739WA3252_AFD_0103_2_MY.almPLCFault.Resetable419978.07Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1740WA3252_AFD_0103_2_MY.almPLCFault.REST419978.08Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Reset this alarm only
1741WA3252_AFD_0103_2_MY.almPLCFault.SCmd_Suppress419978.15Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
1742WA3252_AFD_0103_2_MY.almPLCFault.SCmd_UnSuppress419979.00Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1743WA3252_AFD_0103_2_MY.almPLCFault.Shelve419980.02Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
1744WA3252_AFD_0103_2_MY.almPLCFault.Shelved419980.09Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
1745WA3252_AFD_0103_2_MY.almPLCFault.Suppress419980.00Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
1746WA3252_AFD_0103_2_MY.almPLCFault.Suppressed419980.08Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
1747WA3252_AFD_0103_2_MY.almPLCFault.UACK419978.10Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Remove the Acknowledge Status
1748WA3252_AFD_0103_2_MY.almPLCFault.UnShelve419980.03Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
1749WA3252_AFD_0103_2_MY.almPLCFault.UnSuppress419980.01Boolean1R/W1000RWPS Pump 2 E. Stop : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1750WA3252_AFD_0103_2_MY.ALRM419960.09Boolean1R/W1000RWPS Pump 2 E. Stop : At Least One Alarm is Active
1751WA3252_AFD_0103_2_MY.ANUN419960.10Boolean1R/W1000RWPS Pump 2 E. Stop : At Least One Alarm is Annunciating
1752WA3252_AFD_0103_2_MY.Fault419960.00Boolean1R/W1000RWPS Pump 2 E. Stop : Input tag to monitor for alarm
1753WA3252_AFD_0103_2_MY.Faulted419960.01Boolean1R/W1000RWPS Pump 2 E. Stop : Input is in fault
1754WA3252_AFD_0103_2_MY.FaultInAlarm419960.03Boolean1R/W1000RWPS Pump 2 E. Stop : Fault Is In Alarm (on longer than the delay)
1755WA3252_AFD_0103_2_MY.GlobalReset419961.00Boolean1R/W1000RWPS Pump 2 E. Stop : Reset all Alarms On this PLC
1756WA3252_AFD_0103_2_MY.InputAlarm419960.15Boolean1R/W1000RWPS Pump 2 E. Stop :
1757WA3252_AFD_0103_2_MY.MCmd_Disable419960.08Boolean1R/W1000RWPS Pump 2 E. Stop : Maintenance Command to Disable Alarm
1758WA3252_AFD_0103_2_MY.MCmd_Enable419960.07Boolean1R/W1000RWPS Pump 2 E. Stop : Maintenance Command to Enable Alarm
1759WA3252_AFD_0103_2_MY.PCSuppress419961.01Boolean1R/W1000RWPS Pump 2 E. Stop : Suppress Alarm from Program Control
1760WA3252_AFD_0103_2_MY.PCUnshelve419961.03Boolean1R/W1000RWPS Pump 2 E. Stop : Unshelve Alarm from Program Control
1761WA3252_AFD_0103_2_MY.PCUnSuppress419961.02Boolean1R/W1000RWPS Pump 2 E. Stop : UnSuppress Alarm from Program Control
1762WA3252_AFD_0103_2_MY.PLCF419961.08Boolean1R/W1000RWPS Pump 2 E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1763WA3252_AFD_0103_2_MY.PLCIOFault419961.07Boolean1R/W1000RWPS Pump 2 E. Stop : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
1764WA3252_AFD_0103_2_MY.Resetable419960.12Boolean1R/W1000RWPS Pump 2 E. Stop : At least one alarm is latched and all latched alarms are resetable
1765WA3252_AFD_0103_2_MY.REST419960.05Boolean1R/W1000RWPS Pump 2 E. Stop : Reset Alarm
1766WA3252_AFD_0103_2_MY.Shelve419960.13Boolean1R/W1000RWPS Pump 2 E. Stop : Shelve Command from HMI
1767WA3252_AFD_0103_2_MY.Shelved419961.05Boolean1R/W1000RWPS Pump 2 E. Stop : Shelved Status
1768WA3252_AFD_0103_2_MY.Suppress419960.14Boolean1R/W1000RWPS Pump 2 E. Stop : Suppress Command from HMI
1769WA3252_AFD_0103_2_MY.Suppressed419961.06Boolean1R/W1000RWPS Pump 2 E. Stop : Suppressed Status
1770WA3252_AFD_0103_2_MY.TAGR419961.09Boolean1R/W1000RWPS Pump 2 E. Stop : Tagged Out of Service
1771WA3252_AFD_0103_2_SI.ACKN401402.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Acknowledge Command from Logic to Acknowledge All Alarms in this DFB
1772WA3252_AFD_0103_2_SI.AKED401401.07Boolean1R/W1000RWPS AFD Pump 2 Speed : At Least One Alarm is Acknowledged
1773WA3252_AFD_0103_2_SI.almBrokenLoop.Ack401490.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Acknowlege Command to AE Server
1774WA3252_AFD_0103_2_SI.almBrokenLoop.Acked401490.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm Acknowledged Status from AE Server
1775WA3252_AFD_0103_2_SI.almBrokenLoop.ACKN401488.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Acknowledge Command
1776WA3252_AFD_0103_2_SI.almBrokenLoop.AEShelveTMRDN401489.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm and Events Shelve Timer Done
1777WA3252_AFD_0103_2_SI.almBrokenLoop.AKED401488.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1778WA3252_AFD_0103_2_SI.almBrokenLoop.Alarm401490.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm Command to AE Server
1779WA3252_AFD_0103_2_SI.almBrokenLoop.AlarmState401488.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Value of the Fault input that indicates an alarm condition
1780WA3252_AFD_0103_2_SI.almBrokenLoop.ALRM401488.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1781WA3252_AFD_0103_2_SI.almBrokenLoop.ANUN401488.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1782WA3252_AFD_0103_2_SI.almBrokenLoop.Bad401489.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1783WA3252_AFD_0103_2_SI.almBrokenLoop.Disable401490.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Disable Alarm Command to AE Server
1784WA3252_AFD_0103_2_SI.almBrokenLoop.Disabled401490.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm Disabled Status from AE Server
1785WA3252_AFD_0103_2_SI.almBrokenLoop.Enable401490.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Enable Alarm Command to AE Server
1786WA3252_AFD_0103_2_SI.almBrokenLoop.Fault401488.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Discrete input condition indicating a faulted state.
1787WA3252_AFD_0103_2_SI.almBrokenLoop.FaultInAlarm401488.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Fault Is In Alarm (on longer than the delay)
1788WA3252_AFD_0103_2_SI.almBrokenLoop.GlobalReset401488.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Used to reset all alarms in the PLC
1789WA3252_AFD_0103_2_SI.almBrokenLoop.MCmd_Disable401488.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Maintenance Command to Disable Alarm
1790WA3252_AFD_0103_2_SI.almBrokenLoop.MCmd_Enable401488.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Maintenance Command to Enable Alarm
1791WA3252_AFD_0103_2_SI.almBrokenLoop.OCmd_Shelve401488.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Operator Command to Shelve Alarm
1792WA3252_AFD_0103_2_SI.almBrokenLoop.OCmd_Unshelve401488.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Operator Command to UnShelve Alarm
1793WA3252_AFD_0103_2_SI.almBrokenLoop.Reset401490.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Reset Command to AE Server
1794WA3252_AFD_0103_2_SI.almBrokenLoop.Resetable401488.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1795WA3252_AFD_0103_2_SI.almBrokenLoop.REST401488.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Reset this alarm only
1796WA3252_AFD_0103_2_SI.almBrokenLoop.SCmd_Suppress401488.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Supervisor Command to Suppress Alarm
1797WA3252_AFD_0103_2_SI.almBrokenLoop.SCmd_UnSuppress401489.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Supervisor Command to Unsuppress Alarm
1798WA3252_AFD_0103_2_SI.almBrokenLoop.Shelve401490.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Shelve Alarm Command to AE Server
1799WA3252_AFD_0103_2_SI.almBrokenLoop.Shelved401490.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm Shelved Status from AE Server
1800WA3252_AFD_0103_2_SI.almBrokenLoop.Suppress401490.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Suppress Alarm Command to AE Server
1801WA3252_AFD_0103_2_SI.almBrokenLoop.Suppressed401490.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Alarm Suppressed Status from AE Server
1802WA3252_AFD_0103_2_SI.almBrokenLoop.UACK401488.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Remove the Acknowledge Status
1803WA3252_AFD_0103_2_SI.almBrokenLoop.UnShelve401490.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: Unshelve Alarm Command to AE Server
1804WA3252_AFD_0103_2_SI.almBrokenLoop.UnSuppress401490.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm DDT: UnSuppress Alarm Command to AE Server
1805WA3252_AFD_0103_2_SI.almHigh.Ack401454.06Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Acknowlege Command to AE Server
1806WA3252_AFD_0103_2_SI.almHigh.Acked401454.11Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm Acknowledged Status from AE Server
1807WA3252_AFD_0103_2_SI.almHigh.ACKN401452.09Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Acknowledge Command
1808WA3252_AFD_0103_2_SI.almHigh.AEShelveTMRDN401453.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm and Events Shelve Timer Done
1809WA3252_AFD_0103_2_SI.almHigh.AKED401452.06Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1810WA3252_AFD_0103_2_SI.almHigh.Alarm401454.12Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm Command to AE Server
1811WA3252_AFD_0103_2_SI.almHigh.AlarmState401452.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Value of the Fault input that indicates an alarm condition
1812WA3252_AFD_0103_2_SI.almHigh.ALRM401452.04Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1813WA3252_AFD_0103_2_SI.almHigh.ANUN401452.05Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1814WA3252_AFD_0103_2_SI.almHigh.Bad401453.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1815WA3252_AFD_0103_2_SI.almHigh.Disable401454.05Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Disable Alarm Command to AE Server
1816WA3252_AFD_0103_2_SI.almHigh.Disabled401454.10Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm Disabled Status from AE Server
1817WA3252_AFD_0103_2_SI.almHigh.Enable401454.04Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Enable Alarm Command to AE Server
1818WA3252_AFD_0103_2_SI.almHigh.Fault401452.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Discrete input condition indicating a faulted state.
1819WA3252_AFD_0103_2_SI.almHigh.FaultInAlarm401452.03Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Fault Is In Alarm (on longer than the delay)
1820WA3252_AFD_0103_2_SI.almHigh.GlobalReset401452.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Used to reset all alarms in the PLC
1821WA3252_AFD_0103_2_SI.almHigh.MCmd_Disable401452.12Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Maintenance Command to Disable Alarm
1822WA3252_AFD_0103_2_SI.almHigh.MCmd_Enable401452.11Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Maintenance Command to Enable Alarm
1823WA3252_AFD_0103_2_SI.almHigh.OCmd_Shelve401452.13Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Operator Command to Shelve Alarm
1824WA3252_AFD_0103_2_SI.almHigh.OCmd_Unshelve401452.14Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Operator Command to UnShelve Alarm
1825WA3252_AFD_0103_2_SI.almHigh.Reset401454.07Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Reset Command to AE Server
1826WA3252_AFD_0103_2_SI.almHigh.Resetable401452.07Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1827WA3252_AFD_0103_2_SI.almHigh.REST401452.08Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Reset this alarm only
1828WA3252_AFD_0103_2_SI.almHigh.SCmd_Suppress401452.15Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Supervisor Command to Suppress Alarm
1829WA3252_AFD_0103_2_SI.almHigh.SCmd_UnSuppress401453.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Supervisor Command to Unsuppress Alarm
1830WA3252_AFD_0103_2_SI.almHigh.Shelve401454.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Shelve Alarm Command to AE Server
1831WA3252_AFD_0103_2_SI.almHigh.Shelved401454.09Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm Shelved Status from AE Server
1832WA3252_AFD_0103_2_SI.almHigh.Suppress401454.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Suppress Alarm Command to AE Server
1833WA3252_AFD_0103_2_SI.almHigh.Suppressed401454.08Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Alarm Suppressed Status from AE Server
1834WA3252_AFD_0103_2_SI.almHigh.UACK401452.10Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Remove the Acknowledge Status
1835WA3252_AFD_0103_2_SI.almHigh.UnShelve401454.03Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: Unshelve Alarm Command to AE Server
1836WA3252_AFD_0103_2_SI.almHigh.UnSuppress401454.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm DDT: UnSuppress Alarm Command to AE Server
1837WA3252_AFD_0103_2_SI.almHighHigh.Ack401442.06Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Acknowlege Command to AE Server
1838WA3252_AFD_0103_2_SI.almHighHigh.Acked401442.11Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm Acknowledged Status from AE Server
1839WA3252_AFD_0103_2_SI.almHighHigh.ACKN401440.09Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Acknowledge Command
1840WA3252_AFD_0103_2_SI.almHighHigh.AEShelveTMRDN401441.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm and Events Shelve Timer Done
1841WA3252_AFD_0103_2_SI.almHighHigh.AKED401440.06Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1842WA3252_AFD_0103_2_SI.almHighHigh.Alarm401442.12Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm Command to AE Server
1843WA3252_AFD_0103_2_SI.almHighHigh.AlarmState401440.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Value of the Fault input that indicates an alarm condition
1844WA3252_AFD_0103_2_SI.almHighHigh.ALRM401440.04Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1845WA3252_AFD_0103_2_SI.almHighHigh.ANUN401440.05Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1846WA3252_AFD_0103_2_SI.almHighHigh.Bad401441.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1847WA3252_AFD_0103_2_SI.almHighHigh.Disable401442.05Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Disable Alarm Command to AE Server
1848WA3252_AFD_0103_2_SI.almHighHigh.Disabled401442.10Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm Disabled Status from AE Server
1849WA3252_AFD_0103_2_SI.almHighHigh.Enable401442.04Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Enable Alarm Command to AE Server
1850WA3252_AFD_0103_2_SI.almHighHigh.Fault401440.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Discrete input condition indicating a faulted state.
1851WA3252_AFD_0103_2_SI.almHighHigh.FaultInAlarm401440.03Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Fault Is In Alarm (on longer than the delay)
1852WA3252_AFD_0103_2_SI.almHighHigh.GlobalReset401440.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Used to reset all alarms in the PLC
1853WA3252_AFD_0103_2_SI.almHighHigh.MCmd_Disable401440.12Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Maintenance Command to Disable Alarm
1854WA3252_AFD_0103_2_SI.almHighHigh.MCmd_Enable401440.11Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Maintenance Command to Enable Alarm
1855WA3252_AFD_0103_2_SI.almHighHigh.OCmd_Shelve401440.13Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Operator Command to Shelve Alarm
1856WA3252_AFD_0103_2_SI.almHighHigh.OCmd_Unshelve401440.14Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Operator Command to UnShelve Alarm
1857WA3252_AFD_0103_2_SI.almHighHigh.Reset401442.07Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Reset Command to AE Server
1858WA3252_AFD_0103_2_SI.almHighHigh.Resetable401440.07Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1859WA3252_AFD_0103_2_SI.almHighHigh.REST401440.08Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Reset this alarm only
1860WA3252_AFD_0103_2_SI.almHighHigh.SCmd_Suppress401440.15Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Supervisor Command to Suppress Alarm
1861WA3252_AFD_0103_2_SI.almHighHigh.SCmd_UnSuppress401441.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Supervisor Command to Unsuppress Alarm
1862WA3252_AFD_0103_2_SI.almHighHigh.Shelve401442.02Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Shelve Alarm Command to AE Server
1863WA3252_AFD_0103_2_SI.almHighHigh.Shelved401442.09Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm Shelved Status from AE Server
1864WA3252_AFD_0103_2_SI.almHighHigh.Suppress401442.00Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Suppress Alarm Command to AE Server
1865WA3252_AFD_0103_2_SI.almHighHigh.Suppressed401442.08Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Alarm Suppressed Status from AE Server
1866WA3252_AFD_0103_2_SI.almHighHigh.UACK401440.10Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Remove the Acknowledge Status
1867WA3252_AFD_0103_2_SI.almHighHigh.UnShelve401442.03Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: Unshelve Alarm Command to AE Server
1868WA3252_AFD_0103_2_SI.almHighHigh.UnSuppress401442.01Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm DDT: UnSuppress Alarm Command to AE Server
1869WA3252_AFD_0103_2_SI.almLow.Ack401466.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Acknowlege Command to AE Server
1870WA3252_AFD_0103_2_SI.almLow.Acked401466.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm Acknowledged Status from AE Server
1871WA3252_AFD_0103_2_SI.almLow.ACKN401464.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Acknowledge Command
1872WA3252_AFD_0103_2_SI.almLow.AEShelveTMRDN401465.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm and Events Shelve Timer Done
1873WA3252_AFD_0103_2_SI.almLow.AKED401464.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1874WA3252_AFD_0103_2_SI.almLow.Alarm401466.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm Command to AE Server
1875WA3252_AFD_0103_2_SI.almLow.AlarmState401464.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Value of the Fault input that indicates an alarm condition
1876WA3252_AFD_0103_2_SI.almLow.ALRM401464.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1877WA3252_AFD_0103_2_SI.almLow.ANUN401464.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1878WA3252_AFD_0103_2_SI.almLow.Bad401465.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1879WA3252_AFD_0103_2_SI.almLow.Disable401466.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Disable Alarm Command to AE Server
1880WA3252_AFD_0103_2_SI.almLow.Disabled401466.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm Disabled Status from AE Server
1881WA3252_AFD_0103_2_SI.almLow.Enable401466.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Enable Alarm Command to AE Server
1882WA3252_AFD_0103_2_SI.almLow.Fault401464.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Discrete input condition indicating a faulted state.
1883WA3252_AFD_0103_2_SI.almLow.FaultInAlarm401464.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Fault Is In Alarm (on longer than the delay)
1884WA3252_AFD_0103_2_SI.almLow.GlobalReset401464.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Used to reset all alarms in the PLC
1885WA3252_AFD_0103_2_SI.almLow.MCmd_Disable401464.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Maintenance Command to Disable Alarm
1886WA3252_AFD_0103_2_SI.almLow.MCmd_Enable401464.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Maintenance Command to Enable Alarm
1887WA3252_AFD_0103_2_SI.almLow.OCmd_Shelve401464.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Operator Command to Shelve Alarm
1888WA3252_AFD_0103_2_SI.almLow.OCmd_Unshelve401464.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Operator Command to UnShelve Alarm
1889WA3252_AFD_0103_2_SI.almLow.Reset401466.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Reset Command to AE Server
1890WA3252_AFD_0103_2_SI.almLow.Resetable401464.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1891WA3252_AFD_0103_2_SI.almLow.REST401464.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Reset this alarm only
1892WA3252_AFD_0103_2_SI.almLow.SCmd_Suppress401464.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Supervisor Command to Suppress Alarm
1893WA3252_AFD_0103_2_SI.almLow.SCmd_UnSuppress401465.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Supervisor Command to Unsuppress Alarm
1894WA3252_AFD_0103_2_SI.almLow.Shelve401466.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Shelve Alarm Command to AE Server
1895WA3252_AFD_0103_2_SI.almLow.Shelved401466.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm Shelved Status from AE Server
1896WA3252_AFD_0103_2_SI.almLow.Suppress401466.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Suppress Alarm Command to AE Server
1897WA3252_AFD_0103_2_SI.almLow.Suppressed401466.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Alarm Suppressed Status from AE Server
1898WA3252_AFD_0103_2_SI.almLow.UACK401464.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Remove the Acknowledge Status
1899WA3252_AFD_0103_2_SI.almLow.UnShelve401466.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: Unshelve Alarm Command to AE Server
1900WA3252_AFD_0103_2_SI.almLow.UnSuppress401466.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm DDT: UnSuppress Alarm Command to AE Server
1901WA3252_AFD_0103_2_SI.almLowLow.Ack401478.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Acknowlege Command to AE Server
1902WA3252_AFD_0103_2_SI.almLowLow.Acked401478.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm Acknowledged Status from AE Server
1903WA3252_AFD_0103_2_SI.almLowLow.ACKN401476.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Acknowledge Command
1904WA3252_AFD_0103_2_SI.almLowLow.AEShelveTMRDN401477.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm and Events Shelve Timer Done
1905WA3252_AFD_0103_2_SI.almLowLow.AKED401476.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1906WA3252_AFD_0103_2_SI.almLowLow.Alarm401478.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm Command to AE Server
1907WA3252_AFD_0103_2_SI.almLowLow.AlarmState401476.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Value of the Fault input that indicates an alarm condition
1908WA3252_AFD_0103_2_SI.almLowLow.ALRM401476.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1909WA3252_AFD_0103_2_SI.almLowLow.ANUN401476.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1910WA3252_AFD_0103_2_SI.almLowLow.Bad401477.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1911WA3252_AFD_0103_2_SI.almLowLow.Disable401478.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Disable Alarm Command to AE Server
1912WA3252_AFD_0103_2_SI.almLowLow.Disabled401478.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm Disabled Status from AE Server
1913WA3252_AFD_0103_2_SI.almLowLow.Enable401478.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Enable Alarm Command to AE Server
1914WA3252_AFD_0103_2_SI.almLowLow.Fault401476.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Discrete input condition indicating a faulted state.
1915WA3252_AFD_0103_2_SI.almLowLow.FaultInAlarm401476.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Fault Is In Alarm (on longer than the delay)
1916WA3252_AFD_0103_2_SI.almLowLow.GlobalReset401476.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Used to reset all alarms in the PLC
1917WA3252_AFD_0103_2_SI.almLowLow.MCmd_Disable401476.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Maintenance Command to Disable Alarm
1918WA3252_AFD_0103_2_SI.almLowLow.MCmd_Enable401476.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Maintenance Command to Enable Alarm
1919WA3252_AFD_0103_2_SI.almLowLow.OCmd_Shelve401476.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Operator Command to Shelve Alarm
1920WA3252_AFD_0103_2_SI.almLowLow.OCmd_Unshelve401476.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Operator Command to UnShelve Alarm
1921WA3252_AFD_0103_2_SI.almLowLow.Reset401478.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Reset Command to AE Server
1922WA3252_AFD_0103_2_SI.almLowLow.Resetable401476.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1923WA3252_AFD_0103_2_SI.almLowLow.REST401476.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Reset this alarm only
1924WA3252_AFD_0103_2_SI.almLowLow.SCmd_Suppress401476.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Supervisor Command to Suppress Alarm
1925WA3252_AFD_0103_2_SI.almLowLow.SCmd_UnSuppress401477.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Supervisor Command to Unsuppress Alarm
1926WA3252_AFD_0103_2_SI.almLowLow.Shelve401478.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Shelve Alarm Command to AE Server
1927WA3252_AFD_0103_2_SI.almLowLow.Shelved401478.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm Shelved Status from AE Server
1928WA3252_AFD_0103_2_SI.almLowLow.Suppress401478.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Suppress Alarm Command to AE Server
1929WA3252_AFD_0103_2_SI.almLowLow.Suppressed401478.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Alarm Suppressed Status from AE Server
1930WA3252_AFD_0103_2_SI.almLowLow.UACK401476.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Remove the Acknowledge Status
1931WA3252_AFD_0103_2_SI.almLowLow.UnShelve401478.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: Unshelve Alarm Command to AE Server
1932WA3252_AFD_0103_2_SI.almLowLow.UnSuppress401478.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm DDT: UnSuppress Alarm Command to AE Server
1933WA3252_AFD_0103_2_SI.almOverRange.Ack401502.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Acknowlege Command to AE Server
1934WA3252_AFD_0103_2_SI.almOverRange.Acked401502.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm Acknowledged Status from AE Server
1935WA3252_AFD_0103_2_SI.almOverRange.ACKN401500.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Acknowledge Command
1936WA3252_AFD_0103_2_SI.almOverRange.AEShelveTMRDN401501.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm and Events Shelve Timer Done
1937WA3252_AFD_0103_2_SI.almOverRange.AKED401500.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1938WA3252_AFD_0103_2_SI.almOverRange.Alarm401502.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm Command to AE Server
1939WA3252_AFD_0103_2_SI.almOverRange.AlarmState401500.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Value of the Fault input that indicates an alarm condition
1940WA3252_AFD_0103_2_SI.almOverRange.ALRM401500.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1941WA3252_AFD_0103_2_SI.almOverRange.ANUN401500.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1942WA3252_AFD_0103_2_SI.almOverRange.Bad401501.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1943WA3252_AFD_0103_2_SI.almOverRange.Disable401502.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Disable Alarm Command to AE Server
1944WA3252_AFD_0103_2_SI.almOverRange.Disabled401502.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm Disabled Status from AE Server
1945WA3252_AFD_0103_2_SI.almOverRange.Enable401502.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Enable Alarm Command to AE Server
1946WA3252_AFD_0103_2_SI.almOverRange.Fault401500.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Discrete input condition indicating a faulted state.
1947WA3252_AFD_0103_2_SI.almOverRange.FaultInAlarm401500.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Fault Is In Alarm (on longer than the delay)
1948WA3252_AFD_0103_2_SI.almOverRange.GlobalReset401500.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Used to reset all alarms in the PLC
1949WA3252_AFD_0103_2_SI.almOverRange.MCmd_Disable401500.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Maintenance Command to Disable Alarm
1950WA3252_AFD_0103_2_SI.almOverRange.MCmd_Enable401500.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Maintenance Command to Enable Alarm
1951WA3252_AFD_0103_2_SI.almOverRange.OCmd_Shelve401500.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Operator Command to Shelve Alarm
1952WA3252_AFD_0103_2_SI.almOverRange.OCmd_Unshelve401500.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Operator Command to UnShelve Alarm
1953WA3252_AFD_0103_2_SI.almOverRange.Reset401502.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Reset Command to AE Server
1954WA3252_AFD_0103_2_SI.almOverRange.Resetable401500.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1955WA3252_AFD_0103_2_SI.almOverRange.REST401500.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Reset this alarm only
1956WA3252_AFD_0103_2_SI.almOverRange.SCmd_Suppress401500.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Supervisor Command to Suppress Alarm
1957WA3252_AFD_0103_2_SI.almOverRange.SCmd_UnSuppress401501.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Supervisor Command to Unsuppress Alarm
1958WA3252_AFD_0103_2_SI.almOverRange.Shelve401502.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Shelve Alarm Command to AE Server
1959WA3252_AFD_0103_2_SI.almOverRange.Shelved401502.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm Shelved Status from AE Server
1960WA3252_AFD_0103_2_SI.almOverRange.Suppress401502.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Suppress Alarm Command to AE Server
1961WA3252_AFD_0103_2_SI.almOverRange.Suppressed401502.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Alarm Suppressed Status from AE Server
1962WA3252_AFD_0103_2_SI.almOverRange.UACK401500.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Remove the Acknowledge Status
1963WA3252_AFD_0103_2_SI.almOverRange.UnShelve401502.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: Unshelve Alarm Command to AE Server
1964WA3252_AFD_0103_2_SI.almOverRange.UnSuppress401502.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm DDT: UnSuppress Alarm Command to AE Server
1965WA3252_AFD_0103_2_SI.almPLCFault.Ack401538.06Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Acknowlege Command to AE Server
1966WA3252_AFD_0103_2_SI.almPLCFault.Acked401538.11Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm Acknowledged Status from AE Server
1967WA3252_AFD_0103_2_SI.almPLCFault.ACKN401536.09Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Acknowledge Command
1968WA3252_AFD_0103_2_SI.almPLCFault.AEShelveTMRDN401537.01Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm and Events Shelve Timer Done
1969WA3252_AFD_0103_2_SI.almPLCFault.AKED401536.06Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
1970WA3252_AFD_0103_2_SI.almPLCFault.Alarm401538.12Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm Command to AE Server
1971WA3252_AFD_0103_2_SI.almPLCFault.AlarmState401536.01Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
1972WA3252_AFD_0103_2_SI.almPLCFault.ALRM401536.04Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
1973WA3252_AFD_0103_2_SI.almPLCFault.ANUN401536.05Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
1974WA3252_AFD_0103_2_SI.almPLCFault.Bad401537.02Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
1975WA3252_AFD_0103_2_SI.almPLCFault.Disable401538.05Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Disable Alarm Command to AE Server
1976WA3252_AFD_0103_2_SI.almPLCFault.Disabled401538.10Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm Disabled Status from AE Server
1977WA3252_AFD_0103_2_SI.almPLCFault.Enable401538.04Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Enable Alarm Command to AE Server
1978WA3252_AFD_0103_2_SI.almPLCFault.Fault401536.00Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Discrete input condition indicating a faulted state.
1979WA3252_AFD_0103_2_SI.almPLCFault.FaultInAlarm401536.03Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
1980WA3252_AFD_0103_2_SI.almPLCFault.GlobalReset401536.02Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Used to reset all alarms in the PLC
1981WA3252_AFD_0103_2_SI.almPLCFault.MCmd_Disable401536.12Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Maintenance Command to Disable Alarm
1982WA3252_AFD_0103_2_SI.almPLCFault.MCmd_Enable401536.11Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Maintenance Command to Enable Alarm
1983WA3252_AFD_0103_2_SI.almPLCFault.OCmd_Shelve401536.13Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Operator Command to Shelve Alarm
1984WA3252_AFD_0103_2_SI.almPLCFault.OCmd_Unshelve401536.14Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Operator Command to UnShelve Alarm
1985WA3252_AFD_0103_2_SI.almPLCFault.Reset401538.07Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Reset Command to AE Server
1986WA3252_AFD_0103_2_SI.almPLCFault.Resetable401536.07Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
1987WA3252_AFD_0103_2_SI.almPLCFault.REST401536.08Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Reset this alarm only
1988WA3252_AFD_0103_2_SI.almPLCFault.SCmd_Suppress401536.15Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Supervisor Command to Suppress Alarm
1989WA3252_AFD_0103_2_SI.almPLCFault.SCmd_UnSuppress401537.00Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
1990WA3252_AFD_0103_2_SI.almPLCFault.Shelve401538.02Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Shelve Alarm Command to AE Server
1991WA3252_AFD_0103_2_SI.almPLCFault.Shelved401538.09Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm Shelved Status from AE Server
1992WA3252_AFD_0103_2_SI.almPLCFault.Suppress401538.00Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Suppress Alarm Command to AE Server
1993WA3252_AFD_0103_2_SI.almPLCFault.Suppressed401538.08Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Alarm Suppressed Status from AE Server
1994WA3252_AFD_0103_2_SI.almPLCFault.UACK401536.10Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Remove the Acknowledge Status
1995WA3252_AFD_0103_2_SI.almPLCFault.UnShelve401538.03Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: Unshelve Alarm Command to AE Server
1996WA3252_AFD_0103_2_SI.almPLCFault.UnSuppress401538.01Boolean1R/W1000RWPS AFD Pump 2 Speed : PLC IO Fault Alarm DDT: UnSuppress Alarm Command to AE Server
1997WA3252_AFD_0103_2_SI.almRateOfChange.Ack401526.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Acknowlege Command to AE Server
1998WA3252_AFD_0103_2_SI.almRateOfChange.Acked401526.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm Acknowledged Status from AE Server
1999WA3252_AFD_0103_2_SI.almRateOfChange.ACKN401524.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Acknowledge Command
2000WA3252_AFD_0103_2_SI.almRateOfChange.AEShelveTMRDN401525.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm and Events Shelve Timer Done
2001WA3252_AFD_0103_2_SI.almRateOfChange.AKED401524.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2002WA3252_AFD_0103_2_SI.almRateOfChange.Alarm401526.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm Command to AE Server
2003WA3252_AFD_0103_2_SI.almRateOfChange.AlarmState401524.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Value of the Fault input that indicates an alarm condition
2004WA3252_AFD_0103_2_SI.almRateOfChange.ALRM401524.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2005WA3252_AFD_0103_2_SI.almRateOfChange.ANUN401524.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2006WA3252_AFD_0103_2_SI.almRateOfChange.Bad401525.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2007WA3252_AFD_0103_2_SI.almRateOfChange.Disable401526.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Disable Alarm Command to AE Server
2008WA3252_AFD_0103_2_SI.almRateOfChange.Disabled401526.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm Disabled Status from AE Server
2009WA3252_AFD_0103_2_SI.almRateOfChange.Enable401526.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Enable Alarm Command to AE Server
2010WA3252_AFD_0103_2_SI.almRateOfChange.Fault401524.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Discrete input condition indicating a faulted state.
2011WA3252_AFD_0103_2_SI.almRateOfChange.FaultInAlarm401524.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Fault Is In Alarm (on longer than the delay)
2012WA3252_AFD_0103_2_SI.almRateOfChange.GlobalReset401524.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Used to reset all alarms in the PLC
2013WA3252_AFD_0103_2_SI.almRateOfChange.MCmd_Disable401524.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Maintenance Command to Disable Alarm
2014WA3252_AFD_0103_2_SI.almRateOfChange.MCmd_Enable401524.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Maintenance Command to Enable Alarm
2015WA3252_AFD_0103_2_SI.almRateOfChange.OCmd_Shelve401524.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Operator Command to Shelve Alarm
2016WA3252_AFD_0103_2_SI.almRateOfChange.OCmd_Unshelve401524.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Operator Command to UnShelve Alarm
2017WA3252_AFD_0103_2_SI.almRateOfChange.Reset401526.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Reset Command to AE Server
2018WA3252_AFD_0103_2_SI.almRateOfChange.Resetable401524.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2019WA3252_AFD_0103_2_SI.almRateOfChange.REST401524.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Reset this alarm only
2020WA3252_AFD_0103_2_SI.almRateOfChange.SCmd_Suppress401524.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Supervisor Command to Suppress Alarm
2021WA3252_AFD_0103_2_SI.almRateOfChange.SCmd_UnSuppress401525.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Supervisor Command to Unsuppress Alarm
2022WA3252_AFD_0103_2_SI.almRateOfChange.Shelve401526.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Shelve Alarm Command to AE Server
2023WA3252_AFD_0103_2_SI.almRateOfChange.Shelved401526.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm Shelved Status from AE Server
2024WA3252_AFD_0103_2_SI.almRateOfChange.Suppress401526.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Suppress Alarm Command to AE Server
2025WA3252_AFD_0103_2_SI.almRateOfChange.Suppressed401526.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Alarm Suppressed Status from AE Server
2026WA3252_AFD_0103_2_SI.almRateOfChange.UACK401524.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Remove the Acknowledge Status
2027WA3252_AFD_0103_2_SI.almRateOfChange.UnShelve401526.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: Unshelve Alarm Command to AE Server
2028WA3252_AFD_0103_2_SI.almRateOfChange.UnSuppress401526.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate Of Change Alarm DDT: UnSuppress Alarm Command to AE Server
2029WA3252_AFD_0103_2_SI.almUnderRange.Ack401514.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Acknowlege Command to AE Server
2030WA3252_AFD_0103_2_SI.almUnderRange.Acked401514.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm Acknowledged Status from AE Server
2031WA3252_AFD_0103_2_SI.almUnderRange.ACKN401512.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Acknowledge Command
2032WA3252_AFD_0103_2_SI.almUnderRange.AEShelveTMRDN401513.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm and Events Shelve Timer Done
2033WA3252_AFD_0103_2_SI.almUnderRange.AKED401512.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2034WA3252_AFD_0103_2_SI.almUnderRange.Alarm401514.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm Command to AE Server
2035WA3252_AFD_0103_2_SI.almUnderRange.AlarmState401512.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Value of the Fault input that indicates an alarm condition
2036WA3252_AFD_0103_2_SI.almUnderRange.ALRM401512.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2037WA3252_AFD_0103_2_SI.almUnderRange.ANUN401512.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2038WA3252_AFD_0103_2_SI.almUnderRange.Bad401513.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2039WA3252_AFD_0103_2_SI.almUnderRange.Disable401514.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Disable Alarm Command to AE Server
2040WA3252_AFD_0103_2_SI.almUnderRange.Disabled401514.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm Disabled Status from AE Server
2041WA3252_AFD_0103_2_SI.almUnderRange.Enable401514.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Enable Alarm Command to AE Server
2042WA3252_AFD_0103_2_SI.almUnderRange.Fault401512.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Discrete input condition indicating a faulted state.
2043WA3252_AFD_0103_2_SI.almUnderRange.FaultInAlarm401512.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Fault Is In Alarm (on longer than the delay)
2044WA3252_AFD_0103_2_SI.almUnderRange.GlobalReset401512.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Used to reset all alarms in the PLC
2045WA3252_AFD_0103_2_SI.almUnderRange.MCmd_Disable401512.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Maintenance Command to Disable Alarm
2046WA3252_AFD_0103_2_SI.almUnderRange.MCmd_Enable401512.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Maintenance Command to Enable Alarm
2047WA3252_AFD_0103_2_SI.almUnderRange.OCmd_Shelve401512.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Operator Command to Shelve Alarm
2048WA3252_AFD_0103_2_SI.almUnderRange.OCmd_Unshelve401512.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Operator Command to UnShelve Alarm
2049WA3252_AFD_0103_2_SI.almUnderRange.Reset401514.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Reset Command to AE Server
2050WA3252_AFD_0103_2_SI.almUnderRange.Resetable401512.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2051WA3252_AFD_0103_2_SI.almUnderRange.REST401512.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Reset this alarm only
2052WA3252_AFD_0103_2_SI.almUnderRange.SCmd_Suppress401512.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Supervisor Command to Suppress Alarm
2053WA3252_AFD_0103_2_SI.almUnderRange.SCmd_UnSuppress401513.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Supervisor Command to Unsuppress Alarm
2054WA3252_AFD_0103_2_SI.almUnderRange.Shelve401514.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Shelve Alarm Command to AE Server
2055WA3252_AFD_0103_2_SI.almUnderRange.Shelved401514.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm Shelved Status from AE Server
2056WA3252_AFD_0103_2_SI.almUnderRange.Suppress401514.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Suppress Alarm Command to AE Server
2057WA3252_AFD_0103_2_SI.almUnderRange.Suppressed401514.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Alarm Suppressed Status from AE Server
2058WA3252_AFD_0103_2_SI.almUnderRange.UACK401512.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Remove the Acknowledge Status
2059WA3252_AFD_0103_2_SI.almUnderRange.UnShelve401514.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: Unshelve Alarm Command to AE Server
2060WA3252_AFD_0103_2_SI.almUnderRange.UnSuppress401514.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm DDT: UnSuppress Alarm Command to AE Server
2061WA3252_AFD_0103_2_SI.ALRM401401.05Boolean1R/W1000RWPS AFD Pump 2 Speed : At Least One Alarm is Active
2062WA3252_AFD_0103_2_SI.ANUN401401.06Boolean1R/W1000RWPS AFD Pump 2 Speed : At Least One Alarm is Annunciating
2063WA3252_AFD_0103_2_SI.BL_Alarm401401.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Alarm
2064WA3252_AFD_0103_2_SI.BL_Fault401401.13Boolean1R/W1000RWPS AFD Pump 2 Speed : Broken Loop Fault
2065WA3252_AFD_0103_2_SI.BLEN401400.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Broken Loop Alarm
2066WA3252_AFD_0103_2_SI.ConfigError401400.11Boolean1R/W1000RWPS AFD Pump 2 Speed : RawMin = RawMax: Causes division by zero
2067WA3252_AFD_0103_2_SI.GlobalReset401400.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Reset all Alarms On this PLC
2068WA3252_AFD_0103_2_SI.H_Alarm401400.13Boolean1R/W1000RWPS AFD Pump 2 Speed : High Alarm
2069WA3252_AFD_0103_2_SI.H_EN401400.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable High Alarm
2070WA3252_AFD_0103_2_SI.H_Fault401401.10Boolean1R/W1000RWPS AFD Pump 2 Speed : High Fault
2071WA3252_AFD_0103_2_SI.HH_Alarm401400.12Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Alarm
2072WA3252_AFD_0103_2_SI.HH_EN401400.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable High High Alarm
2073WA3252_AFD_0103_2_SI.HH_Fault401401.09Boolean1R/W1000RWPS AFD Pump 2 Speed : High High Fault
2074WA3252_AFD_0103_2_SI.INTK401402.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Locked by program (ESD)
2075WA3252_AFD_0103_2_SI.INTK_EN401402.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Interlock Alarm
2076WA3252_AFD_0103_2_SI.L_Alarm401400.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Alarm
2077WA3252_AFD_0103_2_SI.L_EN401400.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Low Alarm
2078WA3252_AFD_0103_2_SI.L_Fault401401.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Fault
2079WA3252_AFD_0103_2_SI.LL_Alarm401400.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Alarm
2080WA3252_AFD_0103_2_SI.LL_EN401400.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Low Low Alarm
2081WA3252_AFD_0103_2_SI.LL_Fault401401.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Low Low Fault
2082WA3252_AFD_0103_2_SI.OR_Alarm401401.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Alarm
2083WA3252_AFD_0103_2_SI.OR_EN401400.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Over Range Alarm
2084WA3252_AFD_0103_2_SI.OR_Fault401401.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Over Range Fault
2085WA3252_AFD_0103_2_SI.PCSuppress401402.12Boolean1R/W1000RWPS AFD Pump 2 Speed : Suppress Alarm from Program Control
2086WA3252_AFD_0103_2_SI.PCUnshelve401402.14Boolean1R/W1000RWPS AFD Pump 2 Speed : Unshelve Alarm from Program Control
2087WA3252_AFD_0103_2_SI.PCUnSuppress401402.13Boolean1R/W1000RWPS AFD Pump 2 Speed : UnSuppress Alarm from Program Control
2088WA3252_AFD_0103_2_SI.PLCFault401402.05Boolean1R/W1000RWPS AFD Pump 2 Speed : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2089WA3252_AFD_0103_2_SI.PLCIOFault401402.06Boolean1R/W1000RWPS AFD Pump 2 Speed : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2090WA3252_AFD_0103_2_SI.RC_EN401400.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Rate of Change Alarm
2091WA3252_AFD_0103_2_SI.Resetable401401.08Boolean1R/W1000RWPS AFD Pump 2 Speed : At least one alarm is latched and all latched alarms are resetable
2092WA3252_AFD_0103_2_SI.REST401401.04Boolean1R/W1000RWPS AFD Pump 2 Speed : Reset all Alarms in this DFB
2093WA3252_AFD_0103_2_SI.ROC_Alarm401401.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate of Change Alarm
2094WA3252_AFD_0103_2_SI.ROC_Fault401402.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Rate of Change Fault
2095WA3252_AFD_0103_2_SI.Shelve401402.08Boolean1R/W1000RWPS AFD Pump 2 Speed : Shelve Command from HMI
2096WA3252_AFD_0103_2_SI.Shelved401402.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Shelved Status
2097WA3252_AFD_0103_2_SI.Suppress401402.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Suppress Command from HMI
2098WA3252_AFD_0103_2_SI.SuppressAA401400.09Boolean1R/W1000RWPS AFD Pump 2 Speed : Suppress All Alarms
2099WA3252_AFD_0103_2_SI.Suppressed401402.11Boolean1R/W1000RWPS AFD Pump 2 Speed : Suppressed Status
2100WA3252_AFD_0103_2_SI.SuppressLA401400.10Boolean1R/W1000RWPS AFD Pump 2 Speed : Suppress Level Alarms (LL, L, H, HH, & ROC)
2101WA3252_AFD_0103_2_SI.TAGR401402.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Tagged Out of Service
2102WA3252_AFD_0103_2_SI.Tot_EN401402.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Set true to totalize flow.
2103WA3252_AFD_0103_2_SI.Totalize.EnableTot401548.01Boolean1R/W1000RWPS AFD Pump 2 Speed : Totalizer DDT: Start Totalizing becasue flow is above the minimum
2104WA3252_AFD_0103_2_SI.Totalize.First_Scan401548.00Boolean1R/W1000RWPS AFD Pump 2 Speed : Totalizer DDT: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:
2105WA3252_AFD_0103_2_SI.Totalize.REST401548.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Totalizer DDT: HMI Command to Reset Flow Totals
2106WA3252_AFD_0103_2_SI.Totalize.RollDay401548.03Boolean1R/W1000RWPS AFD Pump 2 Speed : Totalizer DDT:
2107WA3252_AFD_0103_2_SI.UR_Alarm401401.02Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Alarm
2108WA3252_AFD_0103_2_SI.UR_Fault401401.15Boolean1R/W1000RWPS AFD Pump 2 Speed : Under Range Fault
2109WA3252_AFD_0103_2_SI.UREN401400.07Boolean1R/W1000RWPS AFD Pump 2 Speed : Enable Under Range Alarm
2110WA3252_AFD_0103_2_UA.ACKN420080.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : Acknowledge Alarm
2111WA3252_AFD_0103_2_UA.AKED420080.11Boolean1R/W1000RWPS Pump 2 MPR Alarm : At Least One Alarm is Acknowledged
2112WA3252_AFD_0103_2_UA.Alarm.Ack420088.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
2113WA3252_AFD_0103_2_UA.Alarm.Acked420088.11Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
2114WA3252_AFD_0103_2_UA.Alarm.ACKN420086.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Acknowledge Command
2115WA3252_AFD_0103_2_UA.Alarm.AEShelveTMRDN420087.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
2116WA3252_AFD_0103_2_UA.Alarm.AKED420086.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2117WA3252_AFD_0103_2_UA.Alarm.Alarm420088.12Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm Command to AE Server
2118WA3252_AFD_0103_2_UA.Alarm.AlarmState420086.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
2119WA3252_AFD_0103_2_UA.Alarm.ALRM420086.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
2120WA3252_AFD_0103_2_UA.Alarm.ANUN420086.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2121WA3252_AFD_0103_2_UA.Alarm.Bad420087.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
2122WA3252_AFD_0103_2_UA.Alarm.Disable420088.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
2123WA3252_AFD_0103_2_UA.Alarm.Disabled420088.10Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
2124WA3252_AFD_0103_2_UA.Alarm.Enable420088.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
2125WA3252_AFD_0103_2_UA.Alarm.Fault420086.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
2126WA3252_AFD_0103_2_UA.Alarm.FaultInAlarm420086.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
2127WA3252_AFD_0103_2_UA.Alarm.GlobalReset420086.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
2128WA3252_AFD_0103_2_UA.Alarm.MCmd_Disable420086.12Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
2129WA3252_AFD_0103_2_UA.Alarm.MCmd_Enable420086.11Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
2130WA3252_AFD_0103_2_UA.Alarm.OCmd_Shelve420086.13Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
2131WA3252_AFD_0103_2_UA.Alarm.OCmd_Unshelve420086.14Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
2132WA3252_AFD_0103_2_UA.Alarm.Reset420088.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Reset Command to AE Server
2133WA3252_AFD_0103_2_UA.Alarm.Resetable420086.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
2134WA3252_AFD_0103_2_UA.Alarm.REST420086.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Reset this alarm only
2135WA3252_AFD_0103_2_UA.Alarm.SCmd_Suppress420086.15Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
2136WA3252_AFD_0103_2_UA.Alarm.SCmd_UnSuppress420087.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
2137WA3252_AFD_0103_2_UA.Alarm.Shelve420088.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
2138WA3252_AFD_0103_2_UA.Alarm.Shelved420088.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
2139WA3252_AFD_0103_2_UA.Alarm.Suppress420088.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
2140WA3252_AFD_0103_2_UA.Alarm.Suppressed420088.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
2141WA3252_AFD_0103_2_UA.Alarm.UACK420086.10Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Remove the Acknowledge Status
2142WA3252_AFD_0103_2_UA.Alarm.UnShelve420088.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
2143WA3252_AFD_0103_2_UA.Alarm.UnSuppress420088.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
2144WA3252_AFD_0103_2_UA.Alarm_EN420080.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : 0 = enable alarm
2145WA3252_AFD_0103_2_UA.Alarm_Fault420081.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : Alarm is in fault
2146WA3252_AFD_0103_2_UA.AlarmState420080.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : Input value signifying alarm
2147WA3252_AFD_0103_2_UA.almPLCFault.Ack420100.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Acknowlege Command to AE Server
2148WA3252_AFD_0103_2_UA.almPLCFault.Acked420100.11Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
2149WA3252_AFD_0103_2_UA.almPLCFault.ACKN420098.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Acknowledge Command
2150WA3252_AFD_0103_2_UA.almPLCFault.AEShelveTMRDN420099.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
2151WA3252_AFD_0103_2_UA.almPLCFault.AKED420098.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2152WA3252_AFD_0103_2_UA.almPLCFault.Alarm420100.12Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm Command to AE Server
2153WA3252_AFD_0103_2_UA.almPLCFault.AlarmState420098.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
2154WA3252_AFD_0103_2_UA.almPLCFault.ALRM420098.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2155WA3252_AFD_0103_2_UA.almPLCFault.ANUN420098.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2156WA3252_AFD_0103_2_UA.almPLCFault.Bad420099.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2157WA3252_AFD_0103_2_UA.almPLCFault.Disable420100.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
2158WA3252_AFD_0103_2_UA.almPLCFault.Disabled420100.10Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
2159WA3252_AFD_0103_2_UA.almPLCFault.Enable420100.04Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
2160WA3252_AFD_0103_2_UA.almPLCFault.Fault420098.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
2161WA3252_AFD_0103_2_UA.almPLCFault.FaultInAlarm420098.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
2162WA3252_AFD_0103_2_UA.almPLCFault.GlobalReset420098.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
2163WA3252_AFD_0103_2_UA.almPLCFault.MCmd_Disable420098.12Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
2164WA3252_AFD_0103_2_UA.almPLCFault.MCmd_Enable420098.11Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
2165WA3252_AFD_0103_2_UA.almPLCFault.OCmd_Shelve420098.13Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
2166WA3252_AFD_0103_2_UA.almPLCFault.OCmd_Unshelve420098.14Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
2167WA3252_AFD_0103_2_UA.almPLCFault.Reset420100.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Reset Command to AE Server
2168WA3252_AFD_0103_2_UA.almPLCFault.Resetable420098.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2169WA3252_AFD_0103_2_UA.almPLCFault.REST420098.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Reset this alarm only
2170WA3252_AFD_0103_2_UA.almPLCFault.SCmd_Suppress420098.15Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
2171WA3252_AFD_0103_2_UA.almPLCFault.SCmd_UnSuppress420099.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
2172WA3252_AFD_0103_2_UA.almPLCFault.Shelve420100.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
2173WA3252_AFD_0103_2_UA.almPLCFault.Shelved420100.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
2174WA3252_AFD_0103_2_UA.almPLCFault.Suppress420100.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
2175WA3252_AFD_0103_2_UA.almPLCFault.Suppressed420100.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
2176WA3252_AFD_0103_2_UA.almPLCFault.UACK420098.10Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Remove the Acknowledge Status
2177WA3252_AFD_0103_2_UA.almPLCFault.UnShelve420100.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
2178WA3252_AFD_0103_2_UA.almPLCFault.UnSuppress420100.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
2179WA3252_AFD_0103_2_UA.ALRM420080.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : At Least One Alarm is Active
2180WA3252_AFD_0103_2_UA.ANUN420080.10Boolean1R/W1000RWPS Pump 2 MPR Alarm : At Least One Alarm is Annunciating
2181WA3252_AFD_0103_2_UA.Fault420080.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : Input tag to monitor for alarm
2182WA3252_AFD_0103_2_UA.Faulted420080.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : Input is in fault
2183WA3252_AFD_0103_2_UA.FaultInAlarm420080.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : Fault Is In Alarm (on longer than the delay)
2184WA3252_AFD_0103_2_UA.GlobalReset420081.00Boolean1R/W1000RWPS Pump 2 MPR Alarm : Reset all Alarms On this PLC
2185WA3252_AFD_0103_2_UA.InputAlarm420080.15Boolean1R/W1000RWPS Pump 2 MPR Alarm :
2186WA3252_AFD_0103_2_UA.MCmd_Disable420080.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : Maintenance Command to Disable Alarm
2187WA3252_AFD_0103_2_UA.MCmd_Enable420080.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : Maintenance Command to Enable Alarm
2188WA3252_AFD_0103_2_UA.PCSuppress420081.01Boolean1R/W1000RWPS Pump 2 MPR Alarm : Suppress Alarm from Program Control
2189WA3252_AFD_0103_2_UA.PCUnshelve420081.03Boolean1R/W1000RWPS Pump 2 MPR Alarm : Unshelve Alarm from Program Control
2190WA3252_AFD_0103_2_UA.PCUnSuppress420081.02Boolean1R/W1000RWPS Pump 2 MPR Alarm : UnSuppress Alarm from Program Control
2191WA3252_AFD_0103_2_UA.PLCF420081.08Boolean1R/W1000RWPS Pump 2 MPR Alarm : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2192WA3252_AFD_0103_2_UA.PLCIOFault420081.07Boolean1R/W1000RWPS Pump 2 MPR Alarm : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2193WA3252_AFD_0103_2_UA.Resetable420080.12Boolean1R/W1000RWPS Pump 2 MPR Alarm : At least one alarm is latched and all latched alarms are resetable
2194WA3252_AFD_0103_2_UA.REST420080.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : Reset Alarm
2195WA3252_AFD_0103_2_UA.Shelve420080.13Boolean1R/W1000RWPS Pump 2 MPR Alarm : Shelve Command from HMI
2196WA3252_AFD_0103_2_UA.Shelved420081.05Boolean1R/W1000RWPS Pump 2 MPR Alarm : Shelved Status
2197WA3252_AFD_0103_2_UA.Suppress420080.14Boolean1R/W1000RWPS Pump 2 MPR Alarm : Suppress Command from HMI
2198WA3252_AFD_0103_2_UA.Suppressed420081.06Boolean1R/W1000RWPS Pump 2 MPR Alarm : Suppressed Status
2199WA3252_AFD_0103_2_UA.TAGR420081.09Boolean1R/W1000RWPS Pump 2 MPR Alarm : Tagged Out of Service
2200WA3252_AFD_0103_2_UH.ACKN420200.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Acknowledge Alarm
2201WA3252_AFD_0103_2_UH.AKED420200.11Boolean1R/W1000RWPS Pump 2 High Rtd Temp : At Least One Alarm is Acknowledged
2202WA3252_AFD_0103_2_UH.Alarm.Ack420208.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
2203WA3252_AFD_0103_2_UH.Alarm.Acked420208.11Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
2204WA3252_AFD_0103_2_UH.Alarm.ACKN420206.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Acknowledge Command
2205WA3252_AFD_0103_2_UH.Alarm.AEShelveTMRDN420207.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
2206WA3252_AFD_0103_2_UH.Alarm.AKED420206.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2207WA3252_AFD_0103_2_UH.Alarm.Alarm420208.12Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Command to AE Server
2208WA3252_AFD_0103_2_UH.Alarm.AlarmState420206.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
2209WA3252_AFD_0103_2_UH.Alarm.ALRM420206.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
2210WA3252_AFD_0103_2_UH.Alarm.ANUN420206.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2211WA3252_AFD_0103_2_UH.Alarm.Bad420207.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
2212WA3252_AFD_0103_2_UH.Alarm.Disable420208.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
2213WA3252_AFD_0103_2_UH.Alarm.Disabled420208.10Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
2214WA3252_AFD_0103_2_UH.Alarm.Enable420208.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
2215WA3252_AFD_0103_2_UH.Alarm.Fault420206.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
2216WA3252_AFD_0103_2_UH.Alarm.FaultInAlarm420206.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
2217WA3252_AFD_0103_2_UH.Alarm.GlobalReset420206.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
2218WA3252_AFD_0103_2_UH.Alarm.MCmd_Disable420206.12Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
2219WA3252_AFD_0103_2_UH.Alarm.MCmd_Enable420206.11Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
2220WA3252_AFD_0103_2_UH.Alarm.OCmd_Shelve420206.13Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
2221WA3252_AFD_0103_2_UH.Alarm.OCmd_Unshelve420206.14Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
2222WA3252_AFD_0103_2_UH.Alarm.Reset420208.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Reset Command to AE Server
2223WA3252_AFD_0103_2_UH.Alarm.Resetable420206.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
2224WA3252_AFD_0103_2_UH.Alarm.REST420206.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Reset this alarm only
2225WA3252_AFD_0103_2_UH.Alarm.SCmd_Suppress420206.15Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
2226WA3252_AFD_0103_2_UH.Alarm.SCmd_UnSuppress420207.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
2227WA3252_AFD_0103_2_UH.Alarm.Shelve420208.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
2228WA3252_AFD_0103_2_UH.Alarm.Shelved420208.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
2229WA3252_AFD_0103_2_UH.Alarm.Suppress420208.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
2230WA3252_AFD_0103_2_UH.Alarm.Suppressed420208.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
2231WA3252_AFD_0103_2_UH.Alarm.UACK420206.10Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Remove the Acknowledge Status
2232WA3252_AFD_0103_2_UH.Alarm.UnShelve420208.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
2233WA3252_AFD_0103_2_UH.Alarm.UnSuppress420208.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
2234WA3252_AFD_0103_2_UH.Alarm_EN420200.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : 0 = enable alarm
2235WA3252_AFD_0103_2_UH.Alarm_Fault420201.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Alarm is in fault
2236WA3252_AFD_0103_2_UH.AlarmState420200.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Input value signifying alarm
2237WA3252_AFD_0103_2_UH.almPLCFault.Ack420220.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Acknowlege Command to AE Server
2238WA3252_AFD_0103_2_UH.almPLCFault.Acked420220.11Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
2239WA3252_AFD_0103_2_UH.almPLCFault.ACKN420218.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Acknowledge Command
2240WA3252_AFD_0103_2_UH.almPLCFault.AEShelveTMRDN420219.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
2241WA3252_AFD_0103_2_UH.almPLCFault.AKED420218.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2242WA3252_AFD_0103_2_UH.almPLCFault.Alarm420220.12Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm Command to AE Server
2243WA3252_AFD_0103_2_UH.almPLCFault.AlarmState420218.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
2244WA3252_AFD_0103_2_UH.almPLCFault.ALRM420218.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2245WA3252_AFD_0103_2_UH.almPLCFault.ANUN420218.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2246WA3252_AFD_0103_2_UH.almPLCFault.Bad420219.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2247WA3252_AFD_0103_2_UH.almPLCFault.Disable420220.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
2248WA3252_AFD_0103_2_UH.almPLCFault.Disabled420220.10Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
2249WA3252_AFD_0103_2_UH.almPLCFault.Enable420220.04Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
2250WA3252_AFD_0103_2_UH.almPLCFault.Fault420218.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
2251WA3252_AFD_0103_2_UH.almPLCFault.FaultInAlarm420218.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
2252WA3252_AFD_0103_2_UH.almPLCFault.GlobalReset420218.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
2253WA3252_AFD_0103_2_UH.almPLCFault.MCmd_Disable420218.12Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
2254WA3252_AFD_0103_2_UH.almPLCFault.MCmd_Enable420218.11Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
2255WA3252_AFD_0103_2_UH.almPLCFault.OCmd_Shelve420218.13Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
2256WA3252_AFD_0103_2_UH.almPLCFault.OCmd_Unshelve420218.14Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
2257WA3252_AFD_0103_2_UH.almPLCFault.Reset420220.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Reset Command to AE Server
2258WA3252_AFD_0103_2_UH.almPLCFault.Resetable420218.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2259WA3252_AFD_0103_2_UH.almPLCFault.REST420218.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Reset this alarm only
2260WA3252_AFD_0103_2_UH.almPLCFault.SCmd_Suppress420218.15Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
2261WA3252_AFD_0103_2_UH.almPLCFault.SCmd_UnSuppress420219.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
2262WA3252_AFD_0103_2_UH.almPLCFault.Shelve420220.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
2263WA3252_AFD_0103_2_UH.almPLCFault.Shelved420220.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
2264WA3252_AFD_0103_2_UH.almPLCFault.Suppress420220.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
2265WA3252_AFD_0103_2_UH.almPLCFault.Suppressed420220.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
2266WA3252_AFD_0103_2_UH.almPLCFault.UACK420218.10Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Remove the Acknowledge Status
2267WA3252_AFD_0103_2_UH.almPLCFault.UnShelve420220.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
2268WA3252_AFD_0103_2_UH.almPLCFault.UnSuppress420220.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
2269WA3252_AFD_0103_2_UH.ALRM420200.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : At Least One Alarm is Active
2270WA3252_AFD_0103_2_UH.ANUN420200.10Boolean1R/W1000RWPS Pump 2 High Rtd Temp : At Least One Alarm is Annunciating
2271WA3252_AFD_0103_2_UH.Fault420200.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Input tag to monitor for alarm
2272WA3252_AFD_0103_2_UH.Faulted420200.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Input is in fault
2273WA3252_AFD_0103_2_UH.FaultInAlarm420200.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Fault Is In Alarm (on longer than the delay)
2274WA3252_AFD_0103_2_UH.GlobalReset420201.00Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Reset all Alarms On this PLC
2275WA3252_AFD_0103_2_UH.InputAlarm420200.15Boolean1R/W1000RWPS Pump 2 High Rtd Temp :
2276WA3252_AFD_0103_2_UH.MCmd_Disable420200.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Maintenance Command to Disable Alarm
2277WA3252_AFD_0103_2_UH.MCmd_Enable420200.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Maintenance Command to Enable Alarm
2278WA3252_AFD_0103_2_UH.PCSuppress420201.01Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Suppress Alarm from Program Control
2279WA3252_AFD_0103_2_UH.PCUnshelve420201.03Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Unshelve Alarm from Program Control
2280WA3252_AFD_0103_2_UH.PCUnSuppress420201.02Boolean1R/W1000RWPS Pump 2 High Rtd Temp : UnSuppress Alarm from Program Control
2281WA3252_AFD_0103_2_UH.PLCF420201.08Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2282WA3252_AFD_0103_2_UH.PLCIOFault420201.07Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2283WA3252_AFD_0103_2_UH.Resetable420200.12Boolean1R/W1000RWPS Pump 2 High Rtd Temp : At least one alarm is latched and all latched alarms are resetable
2284WA3252_AFD_0103_2_UH.REST420200.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Reset Alarm
2285WA3252_AFD_0103_2_UH.Shelve420200.13Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Shelve Command from HMI
2286WA3252_AFD_0103_2_UH.Shelved420201.05Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Shelved Status
2287WA3252_AFD_0103_2_UH.Suppress420200.14Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Suppress Command from HMI
2288WA3252_AFD_0103_2_UH.Suppressed420201.06Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Suppressed Status
2289WA3252_AFD_0103_2_UH.TAGR420201.09Boolean1R/W1000RWPS Pump 2 High Rtd Temp : Tagged Out of Service
2290WA3252_AFD_0103_2_UY.ACKN420320.06Boolean1R/W1000RWPS Pump 2 MPR Trip : Acknowledge Alarm
2291WA3252_AFD_0103_2_UY.AKED420320.11Boolean1R/W1000RWPS Pump 2 MPR Trip : At Least One Alarm is Acknowledged
2292WA3252_AFD_0103_2_UY.Alarm.Ack420328.06Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
2293WA3252_AFD_0103_2_UY.Alarm.Acked420328.11Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
2294WA3252_AFD_0103_2_UY.Alarm.ACKN420326.09Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Acknowledge Command
2295WA3252_AFD_0103_2_UY.Alarm.AEShelveTMRDN420327.01Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
2296WA3252_AFD_0103_2_UY.Alarm.AKED420326.06Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2297WA3252_AFD_0103_2_UY.Alarm.Alarm420328.12Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm Command to AE Server
2298WA3252_AFD_0103_2_UY.Alarm.AlarmState420326.01Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
2299WA3252_AFD_0103_2_UY.Alarm.ALRM420326.04Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
2300WA3252_AFD_0103_2_UY.Alarm.ANUN420326.05Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2301WA3252_AFD_0103_2_UY.Alarm.Bad420327.02Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
2302WA3252_AFD_0103_2_UY.Alarm.Disable420328.05Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
2303WA3252_AFD_0103_2_UY.Alarm.Disabled420328.10Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
2304WA3252_AFD_0103_2_UY.Alarm.Enable420328.04Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
2305WA3252_AFD_0103_2_UY.Alarm.Fault420326.00Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
2306WA3252_AFD_0103_2_UY.Alarm.FaultInAlarm420326.03Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
2307WA3252_AFD_0103_2_UY.Alarm.GlobalReset420326.02Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
2308WA3252_AFD_0103_2_UY.Alarm.MCmd_Disable420326.12Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
2309WA3252_AFD_0103_2_UY.Alarm.MCmd_Enable420326.11Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
2310WA3252_AFD_0103_2_UY.Alarm.OCmd_Shelve420326.13Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
2311WA3252_AFD_0103_2_UY.Alarm.OCmd_Unshelve420326.14Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
2312WA3252_AFD_0103_2_UY.Alarm.Reset420328.07Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Reset Command to AE Server
2313WA3252_AFD_0103_2_UY.Alarm.Resetable420326.07Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
2314WA3252_AFD_0103_2_UY.Alarm.REST420326.08Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Reset this alarm only
2315WA3252_AFD_0103_2_UY.Alarm.SCmd_Suppress420326.15Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
2316WA3252_AFD_0103_2_UY.Alarm.SCmd_UnSuppress420327.00Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
2317WA3252_AFD_0103_2_UY.Alarm.Shelve420328.02Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
2318WA3252_AFD_0103_2_UY.Alarm.Shelved420328.09Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
2319WA3252_AFD_0103_2_UY.Alarm.Suppress420328.00Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
2320WA3252_AFD_0103_2_UY.Alarm.Suppressed420328.08Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
2321WA3252_AFD_0103_2_UY.Alarm.UACK420326.10Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Remove the Acknowledge Status
2322WA3252_AFD_0103_2_UY.Alarm.UnShelve420328.03Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
2323WA3252_AFD_0103_2_UY.Alarm.UnSuppress420328.01Boolean1R/W1000RWPS Pump 2 MPR Trip : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
2324WA3252_AFD_0103_2_UY.Alarm_EN420320.04Boolean1R/W1000RWPS Pump 2 MPR Trip : 0 = enable alarm
2325WA3252_AFD_0103_2_UY.Alarm_Fault420321.04Boolean1R/W1000RWPS Pump 2 MPR Trip : Alarm is in fault
2326WA3252_AFD_0103_2_UY.AlarmState420320.02Boolean1R/W1000RWPS Pump 2 MPR Trip : Input value signifying alarm
2327WA3252_AFD_0103_2_UY.almPLCFault.Ack420340.06Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Acknowlege Command to AE Server
2328WA3252_AFD_0103_2_UY.almPLCFault.Acked420340.11Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
2329WA3252_AFD_0103_2_UY.almPLCFault.ACKN420338.09Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Acknowledge Command
2330WA3252_AFD_0103_2_UY.almPLCFault.AEShelveTMRDN420339.01Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
2331WA3252_AFD_0103_2_UY.almPLCFault.AKED420338.06Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2332WA3252_AFD_0103_2_UY.almPLCFault.Alarm420340.12Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm Command to AE Server
2333WA3252_AFD_0103_2_UY.almPLCFault.AlarmState420338.01Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
2334WA3252_AFD_0103_2_UY.almPLCFault.ALRM420338.04Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2335WA3252_AFD_0103_2_UY.almPLCFault.ANUN420338.05Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2336WA3252_AFD_0103_2_UY.almPLCFault.Bad420339.02Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2337WA3252_AFD_0103_2_UY.almPLCFault.Disable420340.05Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
2338WA3252_AFD_0103_2_UY.almPLCFault.Disabled420340.10Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
2339WA3252_AFD_0103_2_UY.almPLCFault.Enable420340.04Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
2340WA3252_AFD_0103_2_UY.almPLCFault.Fault420338.00Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
2341WA3252_AFD_0103_2_UY.almPLCFault.FaultInAlarm420338.03Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
2342WA3252_AFD_0103_2_UY.almPLCFault.GlobalReset420338.02Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
2343WA3252_AFD_0103_2_UY.almPLCFault.MCmd_Disable420338.12Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
2344WA3252_AFD_0103_2_UY.almPLCFault.MCmd_Enable420338.11Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
2345WA3252_AFD_0103_2_UY.almPLCFault.OCmd_Shelve420338.13Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
2346WA3252_AFD_0103_2_UY.almPLCFault.OCmd_Unshelve420338.14Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
2347WA3252_AFD_0103_2_UY.almPLCFault.Reset420340.07Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Reset Command to AE Server
2348WA3252_AFD_0103_2_UY.almPLCFault.Resetable420338.07Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2349WA3252_AFD_0103_2_UY.almPLCFault.REST420338.08Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Reset this alarm only
2350WA3252_AFD_0103_2_UY.almPLCFault.SCmd_Suppress420338.15Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
2351WA3252_AFD_0103_2_UY.almPLCFault.SCmd_UnSuppress420339.00Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
2352WA3252_AFD_0103_2_UY.almPLCFault.Shelve420340.02Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
2353WA3252_AFD_0103_2_UY.almPLCFault.Shelved420340.09Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
2354WA3252_AFD_0103_2_UY.almPLCFault.Suppress420340.00Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
2355WA3252_AFD_0103_2_UY.almPLCFault.Suppressed420340.08Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
2356WA3252_AFD_0103_2_UY.almPLCFault.UACK420338.10Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Remove the Acknowledge Status
2357WA3252_AFD_0103_2_UY.almPLCFault.UnShelve420340.03Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
2358WA3252_AFD_0103_2_UY.almPLCFault.UnSuppress420340.01Boolean1R/W1000RWPS Pump 2 MPR Trip : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
2359WA3252_AFD_0103_2_UY.ALRM420320.09Boolean1R/W1000RWPS Pump 2 MPR Trip : At Least One Alarm is Active
2360WA3252_AFD_0103_2_UY.ANUN420320.10Boolean1R/W1000RWPS Pump 2 MPR Trip : At Least One Alarm is Annunciating
2361WA3252_AFD_0103_2_UY.Fault420320.00Boolean1R/W1000RWPS Pump 2 MPR Trip : Input tag to monitor for alarm
2362WA3252_AFD_0103_2_UY.Faulted420320.01Boolean1R/W1000RWPS Pump 2 MPR Trip : Input is in fault
2363WA3252_AFD_0103_2_UY.FaultInAlarm420320.03Boolean1R/W1000RWPS Pump 2 MPR Trip : Fault Is In Alarm (on longer than the delay)
2364WA3252_AFD_0103_2_UY.GlobalReset420321.00Boolean1R/W1000RWPS Pump 2 MPR Trip : Reset all Alarms On this PLC
2365WA3252_AFD_0103_2_UY.InputAlarm420320.15Boolean1R/W1000RWPS Pump 2 MPR Trip :
2366WA3252_AFD_0103_2_UY.MCmd_Disable420320.08Boolean1R/W1000RWPS Pump 2 MPR Trip : Maintenance Command to Disable Alarm
2367WA3252_AFD_0103_2_UY.MCmd_Enable420320.07Boolean1R/W1000RWPS Pump 2 MPR Trip : Maintenance Command to Enable Alarm
2368WA3252_AFD_0103_2_UY.PCSuppress420321.01Boolean1R/W1000RWPS Pump 2 MPR Trip : Suppress Alarm from Program Control
2369WA3252_AFD_0103_2_UY.PCUnshelve420321.03Boolean1R/W1000RWPS Pump 2 MPR Trip : Unshelve Alarm from Program Control
2370WA3252_AFD_0103_2_UY.PCUnSuppress420321.02Boolean1R/W1000RWPS Pump 2 MPR Trip : UnSuppress Alarm from Program Control
2371WA3252_AFD_0103_2_UY.PLCF420321.08Boolean1R/W1000RWPS Pump 2 MPR Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2372WA3252_AFD_0103_2_UY.PLCIOFault420321.07Boolean1R/W1000RWPS Pump 2 MPR Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2373WA3252_AFD_0103_2_UY.Resetable420320.12Boolean1R/W1000RWPS Pump 2 MPR Trip : At least one alarm is latched and all latched alarms are resetable
2374WA3252_AFD_0103_2_UY.REST420320.05Boolean1R/W1000RWPS Pump 2 MPR Trip : Reset Alarm
2375WA3252_AFD_0103_2_UY.Shelve420320.13Boolean1R/W1000RWPS Pump 2 MPR Trip : Shelve Command from HMI
2376WA3252_AFD_0103_2_UY.Shelved420321.05Boolean1R/W1000RWPS Pump 2 MPR Trip : Shelved Status
2377WA3252_AFD_0103_2_UY.Suppress420320.14Boolean1R/W1000RWPS Pump 2 MPR Trip : Suppress Command from HMI
2378WA3252_AFD_0103_2_UY.Suppressed420321.06Boolean1R/W1000RWPS Pump 2 MPR Trip : Suppressed Status
2379WA3252_AFD_0103_2_UY.TAGR420321.09Boolean1R/W1000RWPS Pump 2 MPR Trip : Tagged Out of Service
2380WA3252_AFD_0103_2_VA459004.05Boolean1R/W1000RWPS Pump 2 PFCC Online
2381WA3252_AFD_0103_2_XF.ACKN420440.06Boolean1R/W1000RWPS Pump 2 AFD Trip : Acknowledge Alarm
2382WA3252_AFD_0103_2_XF.AKED420440.11Boolean1R/W1000RWPS Pump 2 AFD Trip : At Least One Alarm is Acknowledged
2383WA3252_AFD_0103_2_XF.Alarm.Ack420448.06Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
2384WA3252_AFD_0103_2_XF.Alarm.Acked420448.11Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
2385WA3252_AFD_0103_2_XF.Alarm.ACKN420446.09Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Acknowledge Command
2386WA3252_AFD_0103_2_XF.Alarm.AEShelveTMRDN420447.01Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
2387WA3252_AFD_0103_2_XF.Alarm.AKED420446.06Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2388WA3252_AFD_0103_2_XF.Alarm.Alarm420448.12Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm Command to AE Server
2389WA3252_AFD_0103_2_XF.Alarm.AlarmState420446.01Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
2390WA3252_AFD_0103_2_XF.Alarm.ALRM420446.04Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
2391WA3252_AFD_0103_2_XF.Alarm.ANUN420446.05Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2392WA3252_AFD_0103_2_XF.Alarm.Bad420447.02Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
2393WA3252_AFD_0103_2_XF.Alarm.Disable420448.05Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
2394WA3252_AFD_0103_2_XF.Alarm.Disabled420448.10Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
2395WA3252_AFD_0103_2_XF.Alarm.Enable420448.04Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
2396WA3252_AFD_0103_2_XF.Alarm.Fault420446.00Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
2397WA3252_AFD_0103_2_XF.Alarm.FaultInAlarm420446.03Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
2398WA3252_AFD_0103_2_XF.Alarm.GlobalReset420446.02Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
2399WA3252_AFD_0103_2_XF.Alarm.MCmd_Disable420446.12Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
2400WA3252_AFD_0103_2_XF.Alarm.MCmd_Enable420446.11Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
2401WA3252_AFD_0103_2_XF.Alarm.OCmd_Shelve420446.13Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
2402WA3252_AFD_0103_2_XF.Alarm.OCmd_Unshelve420446.14Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
2403WA3252_AFD_0103_2_XF.Alarm.Reset420448.07Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Reset Command to AE Server
2404WA3252_AFD_0103_2_XF.Alarm.Resetable420446.07Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
2405WA3252_AFD_0103_2_XF.Alarm.REST420446.08Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Reset this alarm only
2406WA3252_AFD_0103_2_XF.Alarm.SCmd_Suppress420446.15Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
2407WA3252_AFD_0103_2_XF.Alarm.SCmd_UnSuppress420447.00Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
2408WA3252_AFD_0103_2_XF.Alarm.Shelve420448.02Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
2409WA3252_AFD_0103_2_XF.Alarm.Shelved420448.09Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
2410WA3252_AFD_0103_2_XF.Alarm.Suppress420448.00Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server
2411WA3252_AFD_0103_2_XF.Alarm.Suppressed420448.08Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Alarm Suppressed Status from AE Server
2412WA3252_AFD_0103_2_XF.Alarm.UACK420446.10Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Remove the Acknowledge Status
2413WA3252_AFD_0103_2_XF.Alarm.UnShelve420448.03Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: Unshelve Alarm Command to AE Server
2414WA3252_AFD_0103_2_XF.Alarm.UnSuppress420448.01Boolean1R/W1000RWPS Pump 2 AFD Trip : ddt_Alarm for handling alarms: UnSuppress Alarm Command to AE Server
2415WA3252_AFD_0103_2_XF.Alarm_EN420440.04Boolean1R/W1000RWPS Pump 2 AFD Trip : 0 = enable alarm
2416WA3252_AFD_0103_2_XF.Alarm_Fault420441.04Boolean1R/W1000RWPS Pump 2 AFD Trip : Alarm is in fault
2417WA3252_AFD_0103_2_XF.AlarmState420440.02Boolean1R/W1000RWPS Pump 2 AFD Trip : Input value signifying alarm
2418WA3252_AFD_0103_2_XF.almPLCFault.Ack420460.06Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Acknowlege Command to AE Server
2419WA3252_AFD_0103_2_XF.almPLCFault.Acked420460.11Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm Acknowledged Status from AE Server
2420WA3252_AFD_0103_2_XF.almPLCFault.ACKN420458.09Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Acknowledge Command
2421WA3252_AFD_0103_2_XF.almPLCFault.AEShelveTMRDN420459.01Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm and Events Shelve Timer Done
2422WA3252_AFD_0103_2_XF.almPLCFault.AKED420458.06Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2423WA3252_AFD_0103_2_XF.almPLCFault.Alarm420460.12Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm Command to AE Server
2424WA3252_AFD_0103_2_XF.almPLCFault.AlarmState420458.01Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Value of the Fault input that indicates an alarm condition
2425WA3252_AFD_0103_2_XF.almPLCFault.ALRM420458.04Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm: Output indicating a fault has progressed to alarm state.
2426WA3252_AFD_0103_2_XF.almPLCFault.ANUN420458.05Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2427WA3252_AFD_0103_2_XF.almPLCFault.Bad420459.02Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Discrete Input condition indicating a Bad Signal condition
2428WA3252_AFD_0103_2_XF.almPLCFault.Disable420460.05Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Disable Alarm Command to AE Server
2429WA3252_AFD_0103_2_XF.almPLCFault.Disabled420460.10Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm Disabled Status from AE Server
2430WA3252_AFD_0103_2_XF.almPLCFault.Enable420460.04Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Enable Alarm Command to AE Server
2431WA3252_AFD_0103_2_XF.almPLCFault.Fault420458.00Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Discrete input condition indicating a faulted state.
2432WA3252_AFD_0103_2_XF.almPLCFault.FaultInAlarm420458.03Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Fault Is In Alarm (on longer than the delay)
2433WA3252_AFD_0103_2_XF.almPLCFault.GlobalReset420458.02Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Used to reset all alarms in the PLC
2434WA3252_AFD_0103_2_XF.almPLCFault.MCmd_Disable420458.12Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Maintenance Command to Disable Alarm
2435WA3252_AFD_0103_2_XF.almPLCFault.MCmd_Enable420458.11Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Maintenance Command to Enable Alarm
2436WA3252_AFD_0103_2_XF.almPLCFault.OCmd_Shelve420458.13Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Operator Command to Shelve Alarm
2437WA3252_AFD_0103_2_XF.almPLCFault.OCmd_Unshelve420458.14Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Operator Command to UnShelve Alarm
2438WA3252_AFD_0103_2_XF.almPLCFault.Reset420460.07Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Reset Command to AE Server
2439WA3252_AFD_0103_2_XF.almPLCFault.Resetable420458.07Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm is latched but can be reset becasue condition is cleared.
2440WA3252_AFD_0103_2_XF.almPLCFault.REST420458.08Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Reset this alarm only
2441WA3252_AFD_0103_2_XF.almPLCFault.SCmd_Suppress420458.15Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Supervisor Command to Suppress Alarm
2442WA3252_AFD_0103_2_XF.almPLCFault.SCmd_UnSuppress420459.00Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Supervisor Command to Unsuppress Alarm
2443WA3252_AFD_0103_2_XF.almPLCFault.Shelve420460.02Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Shelve Alarm Command to AE Server
2444WA3252_AFD_0103_2_XF.almPLCFault.Shelved420460.09Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm Shelved Status from AE Server
2445WA3252_AFD_0103_2_XF.almPLCFault.Suppress420460.00Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Suppress Alarm Command to AE Server
2446WA3252_AFD_0103_2_XF.almPLCFault.Suppressed420460.08Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Alarm Suppressed Status from AE Server
2447WA3252_AFD_0103_2_XF.almPLCFault.UACK420458.10Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Remove the Acknowledge Status
2448WA3252_AFD_0103_2_XF.almPLCFault.UnShelve420460.03Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: Unshelve Alarm Command to AE Server
2449WA3252_AFD_0103_2_XF.almPLCFault.UnSuppress420460.01Boolean1R/W1000RWPS Pump 2 AFD Trip : PLC Fault Alarm DDT: UnSuppress Alarm Command to AE Server
2450WA3252_AFD_0103_2_XF.ALRM420440.09Boolean1R/W1000RWPS Pump 2 AFD Trip : At Least One Alarm is Active
2451WA3252_AFD_0103_2_XF.ANUN420440.10Boolean1R/W1000RWPS Pump 2 AFD Trip : At Least One Alarm is Annunciating
2452WA3252_AFD_0103_2_XF.Fault420440.00Boolean1R/W1000RWPS Pump 2 AFD Trip : Input tag to monitor for alarm
2453WA3252_AFD_0103_2_XF.Faulted420440.01Boolean1R/W1000RWPS Pump 2 AFD Trip : Input is in fault
2454WA3252_AFD_0103_2_XF.FaultInAlarm420440.03Boolean1R/W1000RWPS Pump 2 AFD Trip : Fault Is In Alarm (on longer than the delay)
2455WA3252_AFD_0103_2_XF.GlobalReset420441.00Boolean1R/W1000RWPS Pump 2 AFD Trip : Reset all Alarms On this PLC
2456WA3252_AFD_0103_2_XF.InputAlarm420440.15Boolean1R/W1000RWPS Pump 2 AFD Trip :
2457WA3252_AFD_0103_2_XF.MCmd_Disable420440.08Boolean1R/W1000RWPS Pump 2 AFD Trip : Maintenance Command to Disable Alarm
2458WA3252_AFD_0103_2_XF.MCmd_Enable420440.07Boolean1R/W1000RWPS Pump 2 AFD Trip : Maintenance Command to Enable Alarm
2459WA3252_AFD_0103_2_XF.PCSuppress420441.01Boolean1R/W1000RWPS Pump 2 AFD Trip : Suppress Alarm from Program Control
2460WA3252_AFD_0103_2_XF.PCUnshelve420441.03Boolean1R/W1000RWPS Pump 2 AFD Trip : Unshelve Alarm from Program Control
2461WA3252_AFD_0103_2_XF.PCUnSuppress420441.02Boolean1R/W1000RWPS Pump 2 AFD Trip : UnSuppress Alarm from Program Control
2462WA3252_AFD_0103_2_XF.PLCF420441.08Boolean1R/W1000RWPS Pump 2 AFD Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2463WA3252_AFD_0103_2_XF.PLCIOFault420441.07Boolean1R/W1000RWPS Pump 2 AFD Trip : Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted.
2464WA3252_AFD_0103_2_XF.Resetable420440.12Boolean1R/W1000RWPS Pump 2 AFD Trip : At least one alarm is latched and all latched alarms are resetable
2465WA3252_AFD_0103_2_XF.REST420440.05Boolean1R/W1000RWPS Pump 2 AFD Trip : Reset Alarm
2466WA3252_AFD_0103_2_XF.Shelve420440.13Boolean1R/W1000RWPS Pump 2 AFD Trip : Shelve Command from HMI
2467WA3252_AFD_0103_2_XF.Shelved420441.05Boolean1R/W1000RWPS Pump 2 AFD Trip : Shelved Status
2468WA3252_AFD_0103_2_XF.Suppress420440.14Boolean1R/W1000RWPS Pump 2 AFD Trip : Suppress Command from HMI
2469WA3252_AFD_0103_2_XF.Suppressed420441.06Boolean1R/W1000RWPS Pump 2 AFD Trip : Suppressed Status
2470WA3252_AFD_0103_2_XF.TAGR420441.09Boolean1R/W1000RWPS Pump 2 AFD Trip : Tagged Out of Service
2471WA3252_AFD_0103_2_YA.ACKN420560.06Boolean1R/W1000RWPS Pump 2 AFD E. Stop : Acknowledge Alarm
2472WA3252_AFD_0103_2_YA.AKED420560.11Boolean1R/W1000RWPS Pump 2 AFD E. Stop : At Least One Alarm is Acknowledged
2473WA3252_AFD_0103_2_YA.Alarm.Ack420568.06Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Acknowlege Command to AE Server
2474WA3252_AFD_0103_2_YA.Alarm.Acked420568.11Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Acknowledged Status from AE Server
2475WA3252_AFD_0103_2_YA.Alarm.ACKN420566.09Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Acknowledge Command
2476WA3252_AFD_0103_2_YA.Alarm.AEShelveTMRDN420567.01Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm and Events Shelve Timer Done
2477WA3252_AFD_0103_2_YA.Alarm.AKED420566.06Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups
2478WA3252_AFD_0103_2_YA.Alarm.Alarm420568.12Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Command to AE Server
2479WA3252_AFD_0103_2_YA.Alarm.AlarmState420566.01Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Value of the Fault input that indicates an alarm condition
2480WA3252_AFD_0103_2_YA.Alarm.ALRM420566.04Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm: Output indicating a fault has progressed to alarm state.
2481WA3252_AFD_0103_2_YA.Alarm.ANUN420566.05Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again.
2482WA3252_AFD_0103_2_YA.Alarm.Bad420567.02Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Discrete Input condition indicating a Bad Signal condition
2483WA3252_AFD_0103_2_YA.Alarm.Disable420568.05Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Disable Alarm Command to AE Server
2484WA3252_AFD_0103_2_YA.Alarm.Disabled420568.10Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Disabled Status from AE Server
2485WA3252_AFD_0103_2_YA.Alarm.Enable420568.04Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Enable Alarm Command to AE Server
2486WA3252_AFD_0103_2_YA.Alarm.Fault420566.00Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Discrete input condition indicating a faulted state.
2487WA3252_AFD_0103_2_YA.Alarm.FaultInAlarm420566.03Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Fault Is In Alarm (on longer than the delay)
2488WA3252_AFD_0103_2_YA.Alarm.GlobalReset420566.02Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Used to reset all alarms in the PLC
2489WA3252_AFD_0103_2_YA.Alarm.MCmd_Disable420566.12Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Disable Alarm
2490WA3252_AFD_0103_2_YA.Alarm.MCmd_Enable420566.11Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Maintenance Command to Enable Alarm
2491WA3252_AFD_0103_2_YA.Alarm.OCmd_Shelve420566.13Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Operator Command to Shelve Alarm
2492WA3252_AFD_0103_2_YA.Alarm.OCmd_Unshelve420566.14Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Operator Command to UnShelve Alarm
2493WA3252_AFD_0103_2_YA.Alarm.Reset420568.07Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Reset Command to AE Server
2494WA3252_AFD_0103_2_YA.Alarm.Resetable420566.07Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm is latched but can be reset becasue condition is cleared.
2495WA3252_AFD_0103_2_YA.Alarm.REST420566.08Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Reset this alarm only
2496WA3252_AFD_0103_2_YA.Alarm.SCmd_Suppress420566.15Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Suppress Alarm
2497WA3252_AFD_0103_2_YA.Alarm.SCmd_UnSuppress420567.00Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Supervisor Command to Unsuppress Alarm
2498WA3252_AFD_0103_2_YA.Alarm.Shelve420568.02Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Shelve Alarm Command to AE Server
2499WA3252_AFD_0103_2_YA.Alarm.Shelved420568.09Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Alarm Shelved Status from AE Server
2500WA3252_AFD_0103_2_YA.Alarm.Suppress420568.00Boolean1R/W1000RWPS Pump 2 AFD E. Stop : ddt_Alarm for handling alarms: Suppress Alarm Command to AE Server