1typeaddressnamedata_typecontrol_addresspics_addresspics_data_typenotes
2Input_Register300549Register_300549_Bitsuint16400549bit 0=1: Way2_Grounded; bit 1=2: Way2_Open; bit 2=4: Way2_Closed; bit 3=8: Way1_Tripped; bit 4=16: Way1_Grounded; bit 5=32: Way1_Open; bit 6=64: Way1_Closed; bit 7=128: Tank_Pressure
3Holding_Register400549Register_300549_Bits_Ovruint16410001Integer
4Input_Register300550Register_300550_Bitsuint16400550bit 0=1: Way4_Grounded; bit 1=2: Way4_Open; bit 2=4: Way4_Closed; bit 3=8: Way3_Tripped; bit 4=16: Way3_Grounded; bit 5=32: Way3_Open; bit 6=64: Way3_Closed; bit 7=128: Way2_Tripped
5Holding_Register400550Register_300550_Bits_Ovruint16410003Integer
6Input_Register300551Register_300551_Bitsuint16400551bit 3=8: Way5_Tripped; bit 4=16: Way5_Grounded; bit 5=32: Way5_Open; bit 6=64: Way5_Closed; bit 7=128: Way4_Tripped
7Holding_Register400551Register_300551_Bits_Ovruint16410005Integer